User Manual
APAX-5520KW
Software Manual
Copyright
The documentation and the software included with this product are copyrighted 2009
by Advantech Co., Ltd. All rights are reserved. Advantech Co., Ltd. reserves the right
to make improvements in the products described in this manual at any time without
notice. No part of this manual may be reproduced, copied, translated or transmitted
in any form or by any means without the prior written permission of Advantech Co.,
Ltd. Information provided in this manual is intended to be accurate and reliable. However, Advantech Co., Ltd. assumes no responsibility for its use, nor for any infringements of the rights of third parties, which may result from its use.
Acknowledgements
Intel and Pentium are trademarks of Intel Corporation.
Microsoft Windows and MS-DOS are registered trademarks of Microsoft Corp.
MULTIPROG and ProConOS are registered trademarks of KW-Software GmbH
Lemgo (Germany)
All other product names or trademarks are properties of their respective owners.
Notes on the Manual
This is the Software Manual for the Advantech APAX-5520 product. This manual will
help guide the end user through implementation and use of the software portion of
this product.
What is covered in this manual:
This manual will give a general overview of the Windows CE operating system, most
of the applications that are included with Windows CE as well as the applications
added and/or created by Advantech Corporation in the Windows CE image. This
manual will also cover installation and use of development and utility software that is
needed. It will also reference optional software that can be used by the end user with
the Windows CE Operating system. There is a section on programming tips for the
MULTIPROG software, but this will not cover all MultiProg functions. This can be referenced from the online help from the MULTIPROG software.
What is not covered in this manual:
This manual will reference the hardware but does not contain hardware setup information, wiring information, electrical specifications or any detailed hardware information. Please refer to the hardware manual for this information.
For detailed MULTIPROG information or IEC-61131 programming, see the online
help when using MULTIPROG.
For detailed ProConOS information, see the ProConOS user's manual.
Edition 1
September 2009
APAX-5520 Software Manual
ii
Contents
Chapter
1
Introduction..........................................1
1.1
Overview ................................................................................................... 2
1.1.1 Development Software.................................................................. 2
1.1.2 Controller Software ....................................................................... 2
General Information .................................................................................. 3
1.2.1 Software Installation...................................................................... 3
1.2.2 ProConOS (Runtime).................................................................... 3
1.2
Chapter
2
Windows CE.NET.................................5
2.1
2.2
2.3
WinCE Image ............................................................................................ 6
Modification of Standard Image ................................................................ 6
Connecting to the Device .......................................................................... 6
2.3.1 DiagAnywhere............................................................................... 6
2.3.2 IP Address .................................................................................... 7
2.3.3 Connecting with MULTIPROG ...................................................... 8
WinCE Remote Tools................................................................................ 8
2.4.1 Remote Admin .............................................................................. 8
2.4.2 Remote Web Admin.................................................................... 10
2.4.3 Remote System Admin ............................................................... 11
WinCE Applications................................................................................. 12
2.5.1 APAX.NET Utility ........................................................................ 12
2.5.2 Advantech Configuration Utility................................................... 13
2.5.3 Advantech Version InformationTool............................................ 15
2.5.4 DiagAnywhere Server ................................................................. 15
2.4
2.5
Chapter
3
Programming .....................................17
3.1
Programming with MULTIPROG............................................................. 18
3.1.1 Licensing the Software................................................................ 18
3.1.2 Quick Start .................................................................................. 18
3.1.3 Notes on the Quick Start............................................................. 18
MULTIPROG Advantech Driver Interface ............................................... 29
3.2.1 Digital Input ................................................................................. 29
3.2.2 Analog Input................................................................................ 30
3.2.3 Modbus TCP Input ...................................................................... 32
3.2.4 Modbus/RTU Input...................................................................... 33
3.2.5 Digital Output .............................................................................. 34
3.2.6 Analog Output ............................................................................. 35
3.2.7 Modbus TCP Output ................................................................... 37
3.2.8 Modbus/RTU Output ................................................................... 38
3.2.9 Modbus/TCP Client General Settings ......................................... 39
3.2.10 Variables and Auto Declaration .................................................. 39
3.2.11 Direct Mapping Examples ........................................................... 41
3.2.12 Modbus Slave Operation (Server) .............................................. 42
3.2.13 MULTIPROG and ProConOS Highlights and Tips...................... 45
3.2.14 Project Tree Overview ................................................................ 46
3.2.15 Tasks .......................................................................................... 46
3.2.16 Edit Wizard.................................................................................. 49
3.2.17 Data Types.................................................................................. 49
3.2.18 Double Mapping Variables.......................................................... 50
3.2.19 Memory Variables ....................................................................... 51
3.2.20 Retentive Variables..................................................................... 51
3.2
iii
APAX-5520 Software Manual
3.2.21 Literals ........................................................................................ 51
3.2.22 Advantech Firmware Function Blocks ........................................ 52
Appendix A
Version & Firmware Information ..... 53
A.1
A.2
Version Information................................................................................. 54
A.1.1 ProConOS .................................................................................. 54
Firmware ................................................................................................. 55
Appendix B
APAX.NET Utility Operation............. 57
B.1
APAX.NET Utility General Window......................................................... 58
B.1.1 Menu........................................................................................... 59
B.1.2 Toolbar........................................................................................ 60
B.1.3 Module Tree Display Area .......................................................... 60
B.1.4 Status Display Area .................................................................... 60
General Configuration............................................................................. 61
I/O Modules Configuration ...................................................................... 62
B.3.1 Analog Input Modules ................................................................. 62
B.3.2 Analog Output Module ................................................................ 64
B.3.3 Digital Input Module .................................................................... 65
B.3.4 Digital Output Module ................................................................. 66
B.2
B.3
Appendix C
System Backup Functionality.......... 67
C.1
C.2
C.3
Introduction ............................................................................................. 68
Configuration........................................................................................... 68
Programming Backup in KW................................................................... 71
APAX-5520 Software Manual
iv
Chapter
1
Introduction
1
1.1 Overview
APAX-5520 is part of Advantech’s Programmable Automation Controller series.
APAX-5520 uses Windows CE.NET and its real-time capabilities along with controller
software provides a soft real-time controller. The controlling portion of this product
consists of two pieces of software, the development software (MULTIPROG) and the
runtime software ProConOS. MULTIPROG will reside on the developer’s computer,
where the developer will create programs to download to the runtime software on the
APAX-5520. The connection is a proprietary connection via TCP/IP.
Windows 95/98/NT/2K/XP
Multiprog
Programming Software
(Development)
APAX-5520
Windows CE.NET
TCP/IP
ProConOS
Runtime Software
(Controller)
1.1.1 Development Software
MULTIPROG provides the tools to develop and download the project to the runtime.
It also provides the developer with online capabilities for debugging and monitoring.
1.1.2 Controller Software
ProConOS stands for Programmable Controller Operating System. ProConOS is a
product from KW Software that has been integrated with Advantech’s APAX-5520
hardware. This is an executable program that uses the highest priority threads in
Windows CE to perform real time execution. In the case of Advantech’s implementation, Windows CE and ProConOS share processing time, each of which run at 1ms.
WinCE is interrupted at the lowest level to insure real time performance from ProConOS. In depth discussion of ProConOS is provided in the ProConOS Manual provided with this product. It is highly recommended that the end user read this manual
for a better understanding of ProConOS and its capabilities.
Note!
KW MultiProg and ProConOS are complaint with IEC 61131-3 to include
programs written by the popular programming languages:
Text Languages:
1. Instruction List (IL)
2. Structure Text (ST)
Graphic Languages:
3. Function Block Diagram (FBD)
4. Ladder Diagram (LD)
5. Sequential Function Chart (SFC)
KW supports cross-language programming. For example, you can use
Ladder Diagrams (LD) on the simple I/O module control, and use Function Block Diagrams (FBD) on process control for more advanced
expressions, and use Sequential Function Chart (SFC) for system configuration in hybrid control system such as water treatment applications.
APAX-5520 Software Manual
2
1.2.1 Software Installation
1.2.2 ProConOS (Runtime)
ProConOS and all the support software come pre-installed on the APAX module.
There is no configuration needed for ProConOS. ProConOS will automatically run
when the APAX is started and contains a server that will listen on the TCP/IP network
for a connection from MULTIPROG. The only configuration that has to be done to the
APAX is to set the IP address in Windows CE.
3
APAX-5520 Software Manual
Introduction
There are two main installations that are required for the APAX-5520 on the development computer, MULTIPROG and the Advantech MULTIPROG Add on. While the
MULTIPROG installation will provide a working development environment, it will not
work with Advantech products without first installing the “Advantech MULTIPROG
Add on” that is provided on the CD. The software requirements to run MULTIPROG
includes one of the following operating systems:
„ Microsoft Windows 95
„ Microsoft Windows 98
„ Microsoft Windows NT 4.0 (SP6)
„ Microsoft Windows 2000 (SP2)
„ Microsoft Windows XP
„ Microsoft Windows ME
„ Microsoft Internet Explorer 4.02 or greater
Chapter 1
1.2 General Information
APAX-5520 Software Manual
4
Chapter
2
Windows CE.NET
2
2.1 WinCE Image
Advantech has engineered the Windows CE.NET embedded image exclusively for
this hardware. It contains specific drivers for the APAX-5520 and is designed and
licensed only for this hardware.
2.2 Modification of Standard Image
While the WinCE image is considered an embedded image, it is possible for the
developer to add their own developed software to the image if done properly. This is
possible through the Microsoft Visual Studio .NET programming environment. Users
can create and deploy their own applications through this tool along with the libraries
distributed by Advantech (see below for more information). Users can also make
changes to an image and have that image deployed on subsequent purchased
images through a Configure to Order specification (CTO). There may be a situation
where a user needs modification of the standard image. Since the image is created
by Advantech, this may be possible depending on the user requirements. A non reoccurring engineering fee (NRE) would most likely be required to create a custom
image. Please check with your sales person for more information about the CTO and
NRE services.
2.3 Connecting to the Device
2.3.1 DiagAnywhere
“DiagAnywhere”, an abbreviation of “Diagnostic Anywhere”, is a networking solution
for remotely monitoring and controlling other Windows based devices. It is very similar to a remote desktop application with some additional features. Currently, “DiagAnywhere” includes the utility on client side, and the server on the other. The main
technology is based on Microsoft .NET Framework for the client. For this reason, the
PCs using this solution must have the Microsoft .NET Framework installed for Win32
platform. You can find the .NET Framework and DiagAnywhere client trial version on
the CD that comes with the APAX-5520.
“DiagAnywhere” server can only run on Advantech’s TPC, UNO, AMAX, APAX and
ADAM Windows based devices. The supported platforms include Windows XP, Windows XPe and Windows CE.
However, the server can accept only one connection from the utility at a time, and
other connection attempts will be rejected if there is a live connection. This server is
set up to automatically start when Windows CE starts. APAX-5520 has built-in
DiaAnywhere server and the server will launch automatically after the system boots.
You can use DiagAnywhere client (The trial version is provided in the CD) to connect
to the APAX-5520. There is no password by default. Then, you can remotely control
APAX-5520 through Ethernet, including file transferring.
APAX-5520 Software Manual
6
The APAX-5520 will come with a default IP address set to 10.0.0.1 and 10.0.0.2. This
IP address can be changed through DiagAnywhere to suit the users specific requirements. Refer to figure below. Double click the LAN port icon you want to change IP
through Start>>Setting>>Control Panel>>Network and Dial-up Connection. You will
see the configuration window as shown below. It is not recommended to use DHCP
for the APAX-5520 because the project and other items connecting to the APAX5520 will be programmed to specific IP address’.
You must save the registry after you update the IP address or your
changes will be discarded upon reboot. This can be done from the start
menu at “Start | Programs | Advantech | Registry Saver”.
7
APAX-5520 Software Manual
Windows CE.NET
Note!
Chapter 2
2.3.2 IP Address
2.3.3 Connecting with MULTIPROG
When developing with Multiprog, the IP address must be set in the project and ProConOS must be running to allow connection to the APAX . This will be covered further in the document.
2.4 WinCE Remote Tools
WinCE Remote tools are a set of Microsoft administration tools provided via web
server on the APAX-5520. The remote tools are accessed by a web browser. The IP
address of the APAX-5520 must be known in order to use the remote tools. It is
important that you find your IP address either by setting a static address or getting
the DHCP assigned address.
2.4.1 Remote Admin
Setup Administrator Password
The first time remote admin is connected to, the user must enter an administrator
password. It is important that this step is done to keep the APAX-5520 protected. If
the registry is lost or if the defaults are loaded, then this step must be done again.
Connect to the APAX-5520 via a web browser with the IP address that was previously set. Using the path xxx.xxx.xxx.xxx/RemoteAdmin
For the first time log on, the page will be redirected to the “DeviceConfig.htm” to set
up the Admin password. Enter the Admin password and click the apply button.
APAX-5520 Software Manual
8
Chapter 2
Windows CE.NET
When the Apply button is clicked, the gateway will reset and the user is then
prompted to log in with the new password.
Once logged in, the user must change the device name. The device name box may
have a sample such as APAX-5520. A suggestion is to change the name to “APAX5520-1”. Other controllers on the same network can have subsequent numbers or different names but all controller names on the same network must be unique.
9
APAX-5520 Software Manual
Once the device name is saved, the remote admin page will be displayed. From this
page the following functions can be managed:
„ Enable Network Adaptors for file share
„ Configure FTP Server
„ Configure TELNET Server
„ Add/Delete Users
„ Add/Delete file shares
„ Add/Delete Printers
2.4.2 Remote Web Admin
Windows CE provides remote web server administration. This is located on a virtual
root by typing in the address xxx.xxx.xxx.xxx/webadmin. The login and password will
be the same for Remote Web Admin as the Remote Admin that was set in the previous section. The Web Server Administration (WebAdmin) page for the Windows CE
Web Server enables you to remotely administer your Web server using your Web
browser. Use WebAdmin to manage the accessibility, security, and file sharing
features of your Web server, including the following tasks:
„ Configure which files are shared and how they are accessed.
„ Configure which users have access to which files.
„ Configure the authentication protocols the Web server will use.
„ View and configure the Web server log.
APAX-5520 Software Manual
10
Chapter 2
2.4.3 Remote System Admin
Windows CE provides a remote system administration. This is located on a virtual
root by typing in the address xxx.xxx.xxx.xxx/sysadmin. The login and password will
be the same as the Remote Admin login and password. This interface includes the
following tools:
„ System Information viewer
„ Process Management view and control
„ File browser
„ Registry editor
11
APAX-5520 Software Manual
Windows CE.NET
The web server configuration comes with its own instructions and help files. Please
see these documents for further information.
2.5 WinCE Applications
2.5.1 APAX.NET Utility
Advantech provides the APAX.NET utility which allows the developer/end user to
interrogate the APAX bus, see connected modules and do simple testing of the I/O.
This software can be helpful when checking wiring inputs prior to installing the runtime project. It is also able to detect and test other Advantech supported hardware for
this product.
The installation file is contained in the CD and on our website at: http://www.advantech.com in the download area under the support page.
Detailed operation for APAX.NET utility can be found in Appendix B.
APAX-5520 Software Manual
12
Advantech provides a tool called the Configuration Utility which can be accessed
from the start menu through Start >> Programs >> Advantech >> Configuration Utility.. This tool provides the following items:
General: System and disk information is available here.
„
Network: The two LAN port information (such as MAC address, IP address,
Subnet Mask, etc) is available here. If you configure the LAN port as DHCP,
click the Renew button to get another ID. Click the Ping button to ping another
device in the same network. Click the Advanced button for further information
such as DHCP server or DNS server.
13
APAX-5520 Software Manual
Windows CE.NET
„
Chapter 2
2.5.2 Advantech Configuration Utility
„
Watchdog: APAX-5520 offers built-in watchdog timer. It will continuously check
the system and automatically reset the system if the system fails. Choose the
periodical checking time for watchdog timer by the Response Time combo box
and then enable the watchdog timer by the Enable button. Here, you also can
test the watchdog timer.
„
Miscellaneous: You can define which program application should execute automatically when system boot-up by including it in the Startup Program. Use Add
and Delete buttons to decide which programs become startup programs. There
are other configuration for system such as Register, Web Server Root and FTP
Server root. Click the Reboot button can help to reboot the system without
power-off the system.
APAX-5520 Software Manual
14
Advantech provides a simple reporting tool that will provide necessary version information for the Windows CE operating system as well as any post OS Build installations from Advantech. This is an important tool for determining what versions of
Advantech Added software are on the APAX-5520 and may help during troubleshooting. Launch the Version Information Tool by selecting Start >> Programs >> Advantech >> Version Information.
Chapter 2
2.5.3 Advantech Version InformationTool
Windows CE.NET
2.5.4 DiagAnywhere Server
APAX-5520 provides the DiagAnywhere Server to allow a connection from the DiagAnywhere client. The application is automatically started. If you choose not to use
this program, you can disable the startup by using the Configuration Utility to remove
it from startup. (Refer to Section 2.5.2)
15
APAX-5520 Software Manual
APAX-5520 Software Manual
16
Chapter
3
Programming
3
3.1 Programming with MULTIPROG
3.1.1 Licensing the Software
Multiprog will work for a limited time without licensing the development software.
Once installed, you must enter the supplied license code as follows:
Select “?” from the menu bar and then “Register”.
Enter the license key.
3.1.2 Quick Start
This quick start section is exactly that. It will show you how to create a very simple
project, without drivers, download and run the project while seeing live variables in
remote debug mode.
3.1.3 Notes on the Quick Start
By using this quick start, you will be able to create a simple application using a template provided by Advantech for the APAX-5520 hardware. This application will create one integer variable (tag) and continuously add the value 1 to it each time the
PLC engine scan’s. The template comes with a “default” task, which runs as a background task. You will remove this task and replace it with a task that runs at a specified scan rate of 100ms. Once this is done, you will download and run the program
and see the live data update. This quick start should only take a few minutes to complete.
APAX-5520 Software Manual
18
Chapter 3
Create a Simple Project
1. Set the IP address for as shown in section “Connecting to Device”.
2. Open Multiprog, Select New Project, Select APAX-5520KW from the list.
Programming
3.
Right click “Resource” in the project tree and select settings.
19
APAX-5520 Software Manual
4.
Type in the IP address of the APAX-5520 as shown below. If this is disabled
then you must license the MULTIPROG software.
5.
Select the “Untitled” POU worksheet from the project tree by double click. Then
click into the workspace to the right.
APAX-5520 Software Manual
20
7.
Create a variable that will demonstrate the add function in use. Right click in the
program workspace and select “Variable”.
Programming
When you click into the workspace, it will enable the Edit Wizard available. If the
Edit wizard is not shown, then you can enable it from the view menu. Double
click the Add function and it will place this function in the workspace.
Chapter 3
6.
21
APAX-5520 Software Manual
8.
Specify a variable called SampleAdd. This variable will be a local integer.
9.
Once the variable is created, connect it to the Add function.
APAX-5520 Software Manual
22
Chapter 3
10. Right click “SampleAdd” and select copy. Right click in the workspace and
select paste to connect the variable to the output side of the Add function.
Programming
11. Insert the constant value of 1 on the upper input of the Add function. Select the
blue input dot on the Add function, right click and select Variable. This will
cause 1 to be added to SampleAdd each scan, and put the results into SampleAdd. This will increment the value by 1 each PLC scan.
23
APAX-5520 Software Manual
12. Right click the default task in the project tree and select Delete. This will remove
the default task as described in the notes at the beginning of the quick start section.
APAX-5520 Software Manual
24
Chapter 3
13. Right click “Tasks” and select insert Task. Name the task “Main” and make it
“Cyclic”.
Programming
25
APAX-5520 Software Manual
14. Now that you have a cyclic task that will run every 100ms, you need to assign
code that will run under that task. Right click the task and select “Insert | Program Instance”. Give the program instance a name and select the OK button.
15. Build the project. Select “Build | Make” from the menu. Verify there are no errors
in the message window.
APAX-5520 Software Manual
26
Chapter 3
16. Select the Project Control Dialog from the menu. If there is a connection established, you will be able to download the project. If there is not a connection
established, you must resolve this problem before continuing.
Programming
If not connected, check the following:
„ IP address set in the project matches the target system.
„ ProConOS running on target system.
„ Target system and Development system are on the same network.
„ Check network cables.
„ Ping target system from development system.
„ Verify OS Firewall allows outgoing connection for Multiprog.
17. Download project by selecting download from the Control Dialog shown above.
27
APAX-5520 Software Manual
18. Run the project by selecting “Cold” which will trigger a cold start of the system.
Cold start re-initializes all variables.
19. Select the online Icon which will allow live debugging of the program. You will
now see data updating in the project workspace.
APAX-5520 Software Manual
28
3.2.1 Digital Input
Select the digital input board. If you double click, it will append to the end of the list.
Once added to the list you must configure the board.
IO Group Name: Each I/O group has a unique name and this cannot be changed by
the user.
Board ID: This is the ID set on the front of the APAX-5520 module.
Start Address %IB: This is the starting physical address of the variables for this I/O
group. The board shown above has 24 Digital inputs. This will require either 24 Boolean addresses or 3 Byte addresses. The dialog will automatically suggest the next
available address.
Task: This is the task that this I/O group will be controlled by. Each time this task runs
it will read these inputs first before performing other items controlled by this task.
Variables Prefix: When the variables are auto created, they will have this text prior to
the Board ID, channel number and type of variable.
Enable Filter: This enables the high frequency change of state filter for the digital
input signal.
29
APAX-5520 Software Manual
Programming
Please read this section carefully as it may save you time and effort when developing
your project.
When you set up your communication driver interface, you will be adding driver
entries to the driver I/O configuration. Each Driver entry will set up the driver for one
input or output module, or one input or output group for distributed I/O. Each driver
entry will also be the connection for the variables (tags) for that I/O entry. There will
be one driver entry for each I/O module or distributed I/O group. This section will
describe each type of I/O group and explain the relationship with the variables.
Chapter 3
3.2 MULTIPROG Advantech Driver Interface
Filter: This defines the minimum acceptable signal width time. This will be the same
setting for both low pass and high pass filter settings. The signal must remain for this
length of time for a change of state to occur.
Data Type: This is the data type that will be created when the variables are created.
If BOOL is selected, there will be 24 BOOLS created and addressed. If BYTE is
selected, there will be three BYTE’S created and addressed.
Port: Each port is made up of 8 DI’s. If reverse logic is needed for an input, you can
individually control this by selecting the port and checking the box for each DI that
you want inverted in the KW Logic.
3.2.2 Analog Input
IO Group Name: Each I/O group has a unique name and this cannot be changed by
the user.
Board ID: This is the ID set on the front of the APAX-5520 module.
Start Address %IB: This is the starting physical address of the variables for this I/O
group. The dialog will automatically suggest the next available address. The size of
the group will depend on how the channels are configured. See channel configuration
below for more information.
Task: This is the task that this I/O group will be controlled by. Each time this task runs
it will read these inputs first before performing other items controlled by this task.
APAX-5520 Software Manual
30
Chapter 3
Variables Prefix: When the variables are auto created, they will have this text prior to
the Board ID, channel number and type of variable.
Channel Configuration
Each Analog Input channel can be individually configured to a different range and
return type. If all the channels will be configured the same, click the Apply to All button to configure all the channels to the currently selected channel.
Programming
Range: The range selections will be different depending on what Analog Input board
is selected.
Return type: If Raw Data is selected, the return type for that channel will be type
WORD which is 16 bit in size.
Note!
Even though the Raw Data selection is 16 Bit in size, the automatic Variable declaration will reserve 32 bits for each AI point in case the user
wants to make a change to Eng. Unit at some future point. This will keep
the user from having to re-align mapped data.
If you want a pre-scaled return value then select Eng. Unit and provide the minimum
and maximum values to scale the return value. Eng. Unit return type for that channel
will by type REAL which is 32 bit in size.
31
APAX-5520 Software Manual
3.2.3 Modbus TCP Input
IO Group Name: Each I/O group has a unique name and this cannot be changed by
the user.
Modbus Command: Four different functions are available for input. Two will read
inputs and two will read outputs.
Slave ID: Slave ID of Modbus Module. This is generally “1” but sometimes can be
something other than “1”. One example would be when using a MODBUS/TCP to
RTU gateway.
Slave IP: IP address of the slave module.
Data Type: This is the data type of what is being read by the driver. Coil status will
only offer BOOL and BYTE. Register status will provide several types that must be
decided by the user.
Modbus Start Address: Starting address of I/O to be read on Modbus device. Consult your hardware manual for this address.
No. of Points: Number of Modbus points being read by this I/O group.
Task: This is the task that this I/O group will be controlled by. Each time this task runs
it will read these inputs first before performing other items controlled by this task.
Start Address %IB: This is the starting physical address of the variables for this I/O
group in the KW software. The size of the group will depend on the Data type and
number of Points. The dialog will automatically suggest the next available address.
Variables Prefix: When the variables are auto created, they will have this text prior
to the rest of the variable name.
APAX-5520 Software Manual
32
Chapter 3
3.2.4 Modbus/RTU Input
Programming
IO Group Name: Each I/O group has a unique name and this cannot be changed by
the user.
COM: COM port for Modbus RTU.
Modbus Command: Four different functions are available for input. Two will read
inputs and two will read outputs.
Slave ID: Slave ID of Modbus Module
Modbus Start Address: Starting address of I/O to be read on Modbus device. Consult your hardware manual for this address.
No. of Points: Number of Modbus points being read by this I/O group.
Data Type: This is the data type of what is being read by the driver. Coil status will
only offer BOOL and BYTE. Register status will provide several types that must be
decided by the user.
Task: This is the task that this I/O group will be controlled by. Each time this task runs
it will read these inputs first before performing other items controlled by this task.
Start Address %IB: This is the starting physical address of the variables for this I/O
group. The size of the group will depend on the Data type and number of Points. The
dialog will automatically suggest the next available address.
Variables Prefix: When the variables are auto created, they will have this text prior
to the rest of the variable name.
33
APAX-5520 Software Manual
3.2.5 Digital Output
IO Group Name: Each I/O group has a unique name and this cannot be changed by
the user.
Board ID: This is the ID set on the front of the APAX-5520 I/O module.
Start Address %QB: This is the starting physical address of the variables for this I/O
group. The board shown above has 24 Digital outputs. This will require either 24
Boolean addresses or 3 Byte addresses. The dialog will automatically suggest the
next available address.
Task: This is the task that this I/O group will be controlled by. Each time this task runs
it will write these outputs first after performing other items controlled by this task.
Variables Prefix: When the variables are auto created, they will have this text prior to
the Board ID, channel number and type of variable.
Data Type: This is the data type that will be created when the variables are created.
If BOOL is selected, there will be 24 BOOLS created and addressed. If BYTE is
selected, there will be three BYTE’S created and addressed.
APAX-5520 Software Manual
34
Chapter 3
3.2.6 Analog Output
35
APAX-5520 Software Manual
Programming
IO Group Name: Each I/O group has a unique name and this cannot be changed by
the user.
Board ID: This is the ID set on the front of the APAX-5520 module.
Start Address %QB: This is the starting physical address of the variables for this I/O
group. The dialog will automatically suggest the next available address. The size of
the group will depend on how the channels are configured. See channel configuration
below for more information.
Task: This is the task that this I/O group will be controlled by. Each time this task runs
it will write these outputs after performing other items controlled by this task.
Variables Prefix: When the variables are auto created, they will have this text prior to
the Board ID, channel number and type of variable.
Channel Configuration
Each Analog Input channel can be individually configured to a different range and
return type. If all the channels will be configured the same, click the Apply to All button to configure all the channels to the currently selected channel.
Range: The range selections will be different depending on what Analog Output
board is selected.
Return type: If Raw Data is selected, the output type for that channel will be type
WORD which is 16 bit in size.
NOTE: Even though the Raw Data selection is 16 Bit in size, the automatic Variable
declaration will reserve 32 bits for each AO point in case the user wants to make a
change to Eng. Unit at some future point. This will keep the user from having to realign mapped data.
If you want a pre-scaled return value then select Eng. Unit and provide the minimum
and maximum values to scale the return value. Eng. Unit return type for that channel
will by type REAL which is 32 bit in size.
APAX-5520 Software Manual
36
Chapter 3
3.2.7 Modbus TCP Output
Programming
IO Group Name: Each I/O group has a unique name and this cannot be changed by
the user.
Modbus Command: Two functions are available for output. Write coil or write register.
Slave ID: Slave ID of Modbus Module. This is generally “1” but sometimes can be
something other than “1”. One example would be when using a MODBUS/TCP to
RTU gateway where each module has a different Slave ID.
Slave IP: IP address of the slave module.
Data Type: This is the data type of what is being written by the driver. Coil write will
only offer BOOL and BYTE. Register write will provide several types depending on
the register.
Modbus Start Address: Starting address of I/O to be written on Modbus device.
Consult your hardware manual for this address.
No. of Points: Number of Modbus points being written by this I/O group.
Task: This is the task that this I/O group will be controlled by. Each time this task runs
it will write these outputs after performing other items controlled by this task.
Start Address %QB: This is the starting physical address of the variables for this I/O
group in the KW software. The size of the group will depend on the Data type and
number of Points. The dialog will automatically suggest the next available address.
Variables Prefix: When the variables are auto created, they will have this text prior to
the rest of the variable name.
37
APAX-5520 Software Manual
3.2.8 Modbus/RTU Output
IO Group Name: Each I/O group has a unique name and this cannot be changed by
the user.
COM: COM port for Modbus RTU.
Modbus Command: 2 functions are available for output. Write coils and write registers.
Slave ID: Slave ID of Modbus Module
Modbus Start Address: Starting address of I/O to be written on Modbus device.
Consult your hardware manual for this address.
No. of Points: Number of Modbus points being written by this I/O group.
Data Type: This is the data type of what is being written by the driver. Coil write will
only offer BOOL and BYTE. Register write will provide several types.
Task: This is the task that this I/O group will be controlled by. Each time this task runs
it will write these outputs after performing other items controlled by this task.
Start Address %QB: This is the starting physical address of the variables for this I/O
group. The size of the group will depend on the Data type and number of Points. The
dialog will automatically suggest the next available address.
Variables Prefix: When the variables are auto created, they will have this text prior
to the rest of the variable name.
APAX-5520 Software Manual
38
Chapter 3
3.2.9 Modbus/TCP Client General Settings
3.2.10 Variables and Auto Declaration
Once the I/O configuration is set, Advantech has added a way to automatically
declare variables. This gives the developer an easy method and good starting point
for declaring variables. There is a button on the I/O configuration to do this called
“Create All Input Variables”. There is also one for the Output variables. This button
will automatically create and map the variables associated with configured I/O. The
Create All Input Variables button will create a variable based on the following example:
Example Variable: APAX5040_B02C014_I
APAX5040 = Name of I/O Module
B02 = Board ID 2
C014 = Channel 14, in this case it would be input 14 starting from zero.
I = Input
In this example, we have configured two APAX5040 modules.
APAX5040, Board ID 2, Data Type BOOL, Start Address %IX0.0
APAX5040, Board ID 5, Data Type BYTE, Start Address %IB4This will create two
Global Variable groups, one group for each I/O configuration. Since we have created
two of the same board with different DATA TYPE, you can see that the variables are
mapped differently. The first group has been mapped as individual bits. The second
group has been mapped as a packed byte.
39
APAX-5520 Software Manual
Programming
Scan Time: The execution of the Modbus TCP communication happens in its own
thread. This thread will send to all slaves and wait for all responses. The scan time is
the interval between start of current thread execution and the start of the next thread
execution.
Recover Time Out: Interval between reconnect attempts for a disconnected slave.
Receive Time Out: This value can only be multiples of 5. The maximum number of
retries are "Receive time out"/5. If "Receive Time Out" is 15 then The maximum number of retries are 3. Once the maximum retries are reached, then the slave goes to a
disconnected state and is handled by the recovery timeout.
The variable names are automatically created, but these names can be changed to
whatever is more relevant to the programmer. From the example above there have
been some changes as shown in the following example.
APAX-5520 Software Manual
40
Example Mapping: %IW7
% = Directly Mapped variable
I = Physical Input
W = Word Size
7 = Starting at Byte 7 and ending AFTER byte 8. The next available address would
be 9.
Example Mapping: %QX4.6
% = Directly Mapped variable
Q = Physical Input
X = Bit Size
4.6 = BYTE 4 Bit 6. Since Bytes are 8 bits, the bits are 0-7
41
APAX-5520 Software Manual
Programming
3.2.11 Direct Mapping Examples
Chapter 3
Important note: if the programmer decides to make changes to the driver such as
“Start Address” or “Board ID”, the driver interface will automatically remove the
mapped Variable group from being deleted, associated with it. Before making name
changes, make sure you have your I/O entry set up properly. If you would like to
make changes to the Start address or Board ID, but save your Variable Group, you
must change the name of the variable group first. Once this is done, you must also
change the mapping of the saved variable group to match the updated variable group
settings.
3.2.12 Modbus Slave Operation (Server)
Advantech has provided an interface to monitor and control tags in the APAX-5520.
This interface is accessible via Modbus/TCP as well as Modbus/RTU The APAX5520 can be treated as a MODBUS Slave. There are four different memory sections
offered to the user. Three of them require no configuration. The fourth section is user
configurable. These sections include the following:
Inputs - SCADA/HMI software can directly access the Input points of the APAX-5520
for monitoring.
Outputs - SCADA/HMI software can directly access the Output points of the APAX5520 for read only access. Direct control of the APAX-5520 outputs is not allowed.
Since the Output control is done via the controller software, direct control of Outputs
could cause problems as well as hidden programming problems and is therefore
restricted.
Shared Memory Area - SCADA/HMI software can directly access user configured
memory mapped variables of the APAX-5520 for Read/Write. The user configures
this area within the KW software and then decides on usage and access of the area.
Special Function Area – Reserved for future use.
Modbus/RTU Setup
Before the user can use the Modbus/RTU server, the Com Port must be setup. This
is done via the I/O Configuration on the COM port tab. The port settings are fixed at
the following:
Baud rate=57600, Data bits=8, Stop bits=1, Parity=no parity, Protocol=Modbus.
Once the port is set up as slave, it cannot be used as Master through the driver setup
section. This can cause errors if one port is set to both master and slave.
APAX-5520 Software Manual
42
Examples of Modbus addresses
KW Variable Address
KW Variable Size
Modbus command
Description
%IW0
Word – 16 bit
3x0001 1 data point
Read Input bytes 0-1
%IW4
Word – 16bit
3x0003 1 data point
Read Input bytes 4-5
%IW2-9
4 Words
3x0002 4 data points Read Input bytes 2-9
%IX0.0
BOOL – 1bit
1x0001 1 data point
Read Input bit 0.0
%IX1.1
BOOL – 1bit
1x0010 1 data point
Read Input bit 1.1
%IX1.0 - %IX3.7
24 BOOLS -24bits 1x0009 24 data points Read Input bits 1.0 –
3.7
KW BOOL Inputs and MODBUS 1x Function Mapping Alignment
%IB0
%IX0.0
%IX0.1
%IX0.2
%IX0.3
%IX0.4
%IX0.5
%IX0.6
%IX0.7
1x0001
1x0002
1x0003
1x0004
1x0005
1x0006
1x0007
1x0008
%IX1.0
%IX1.1
%IX1.2
%IX1.3
%IX1.4
%IX1.5
%IX1.6
%IX1.7
1x0009
1x0010
1x00011
1x0012
1x0013
1x0014
1x0015
1x0016
%IB1
KW WORD Inputs and MODBUS 3x Function Mapping Alignment
%IB0
%IB1
%IW0
%IB3
%IW2
3x0001
%IB10
%IB2
%IB12
%IB5
%IW4
3x0002
%IB11
%IB4
%IB7
%IW6
3x0003
%IB13
%IB6
%IB14
%IB16
3x0005
%IB17
%IB18
%IW10
%IW12
%IW14
%IW16
%IW18
3x0006
3x0007
3x0008
3x0009
3x0010
Note!
%IB9
%IW8
3x0004
%IB15
%IB8
%IB19
The most efficient way to use MODBUS communication is to pack as
many of the same kinds of data together, and read as many as possible
in one communication command.
43
APAX-5520 Software Manual
Programming
In the mapped input area, the first 1000 “Mapped” input WORDS (%IB0 - %IB1999)
OR the first 1000 BOOLS (%IX0.0- %IX124.7) are available via Modbus as READ
ONLY. All input variables that are mapped to this area are readable via standard
MODBUS functions.
Inputs can be read via 1x function or 3x function depending on user needs. It is possible to mix the data types. This area stores:
MODBUS Input Registers 3x0001 ~ 3x1000 (This function returns word values)
MODBUS Input Status 1x0001 ~ 1x1000 (This function returns bit values)
Chapter 3
Inputs
Outputs
In the mapped Output area, the first 2000 “Mapped” Output bytes (%QB0 %IQB1999) OR the first 1000 BOOLS (%QX0.0- %QX124.7) are available via MODBUS as READ ONLY. All Output variables that are mapped to this area are readable
via standard MODBUS functions.
Outputs can be read via 0x function or 4x function depending on user needs. It is
possible to mix the data types. This area stores:
MODBUS Input Registers 4x0001 ~ 4x1000 (This function returns word values)
MODBUS Input Status 0x0001 ~ 0x1000 (This function returns bit values)
Examples of MODBUS addresses
KW Variable Address KW Variable Size
MODBUS command
Description
%QW0
Word – 16 bit
4x0001 1 data point
Read Output bytes 0-1
%QW4
Word – 16bit
4x0003 1 data point
Read Output bytes 4-5
%QW2-9
4 Words
4x0002 4 data points
Read Output bytes 2-9
%QX0.0
BOOL – 1bit
0x0001 1 data point
Read Output bit 0.0
%QX1.1
BOOL – 1bit
0x0010 1 data point
Read Output bit 1.1
%QX1.0 - %QX3.7
24 BOOLS -24bits 0x0009 24 data points Read Output bits 1.0 – 3.7
KW BOOL Outputs and MODBUS 0x Function Mapping Alignment
%QB0
%QX0.0
%QX0.1
%QX0.2
%QX0.3
%QX0.4
%QX0.5
%QX0.6
%QX0.7
0x0001
0x0002
0x0003
0x0004
0x0005
0x0006
0x0007
0x0008
%QX1.0
%QX1.1
%QX1.2
%QX1.3
%QX1.4
%QX1.5
%QX1.6
%QX1.7
0x0009
0x0010
0x00011
0x0012
0x0013
0x0014
0x0015
0x0016
%QB1
KW WORD Outputs and MODBUS 4x Function Mapping Alignment
%QB0
%QB1
%QB2
%QB3
%QB4
%QB5
%QB6
%QB7
%QB8
%QW0
%QW2
%QW4
%QW6
%QW8
4x0001
4x0002
4x0003
4x0004
4x0005
%QB9
%QB10 %QB11 %QB12 %QB13 %QB14 %QB15 %QB16 %QB17 %QB18 %QB19
%QW10
%QW12
%QW14
%QW16
%QW18
4x0006
4x0007
4x0008
4x0009
4x0010
Shared Memory Area
The APAX-5520 Controller reserves approximately 128K Bytes memory space for
general Modbus use. This shared memory block can store user’s data and exchange
the data through Modbus TCP and RTU protocol with a SCADA/HMI. The units in
Modbus 4X registers are Word size (16 bit), so there are a total of 64K Words available. The memory can be accessed as read or write with four different Modbus functions as shown below:
MODBUS Coil Status 0x2001~0x65536
MODBUS Input Status 1x2001~1x65536
MODBUS Input Registers 3x2001~3x65536
MODBUS Holding Registers 4x2001~4x65536
APAX-5520 Software Manual
44
Chapter 3
It is possible to mix the use of this area, using some for read and some for write, as
well as mixing of Coil and registers.
Since this area is fully configurable by the developer, it is up to them to keep track of
what values are in what position for MODBUS reads and writes.
Since the units of MW3.0 are BYTES, users need to map the I/O Address and
Modbus Address as follows.
For Bool data type: (0x and 1x functions)
MODBUS ADDRESS
Length
Data 1
%MX3.0.0
0x2001
1 Bit
Data 2
%MX3.0.1
0x2002
1 Bit
Data 3
%MX3.0.2
0x2003
1 Bit
For Byte and Word data type: (3x and 4x functions)
I/O Address
MODBUS ADDRESS
Length
Data 1
%MW3.0
4x2001
2 Bytes
Data 2
%MW3.2
4x2002
2 Bytes
Data 3
%MW3.4
4x2003
2 Bytes
For Dword and Real data type: (3x and 4x functions)
I/O Address
MODBUS ADDRESS
Length
Data 1
%MD3.0
4x2001 + 4x2002
4 Bytes
Data 2
%MD3.4
4x2003 + 4x2004
4 Bytes
Data 3
%MD3.8
4x2005 + 4x2006
4 Bytes
3.2.13 MULTIPROG and ProConOS Highlights and Tips
To help the end user, Advantech has added this section to show some of the more
important features of the software and some items that may not be explicitly covered
in the MULTIPROG online help. It is also intended to cover some basics of ProConOS. It should reduce the time needed to come up to speed on using this programming environment. It is not intended to be the only resource, but an additional
resource to help the end user get started and understand MULTIPROG. For more
information on MULTIPROG, see the online help. For more information on ProConOS, see the ProConOS user’s manual.
45
APAX-5520 Software Manual
Programming
I/O Address
3.2.14 Project Tree Overview
This section is a quick overview of what each part of the project tree is used for. More
detailed explanations are below and in the online help for MULTIPROG.
Libraries: This is where you can add libraries to your project. Libraries can include
Firmware libraries or User libraries. User libraries can be other Projects. So, the user
can develop a project with just a collection of Function blocks, save it as a project and
add it as a library at a later time.
Data Types: This section is where user data types are defined. This includes Arrays,
Structs and special string types.
Logical POUs: Program Organization Units can be Programs, Functions and Function blocks. Code does not execute from this section. Programs are added to tasks,
Functions and Function blocks are added to programs.
Configuration: One project can have multiple Configurations. This means one
project can share Libraries, Data Types and Logical POUs for two different hardware
platforms.
Resource: One configuration can have multiple Resources. One example is that one
project could connect and download to two APAX5520s on the same network.
Tasks: Each cyclic task is a separate thread in WinCE and can execute at its own
priority and scan rate. See below for a more detailed description of tasks.
Global_Variables: This is where all global variables are declared. Each POU can
have local variables as well as global variables.
Advantech_DAQ: This is the I/O configuration or hardware driver interface.
3.2.15 Tasks
Tasks are at the heart of ProConOS and deserve some explanation.
Task functions
Tasks have three functions in this order: Read inputs, execute code, write outputs.
APAX-5520 Software Manual
46
Chapter 3
Read Inputs for Attached I/O Groups
Execute code body’s in order
Tasks have Input groups, Output groups and Programs attached to them. The tasks
must be created before the Programs and I/O groups are created. This allows them
to be associated.
There are three types of tasks implemented on the APAX-5520:
Cyclic tasks
Cyclic tasks run on a timed basis set by the developer. The task is set up in the ProConOS Scheduler to start each time the interval is started. Once the task runs, it is
suspended until the next time interval.
System tasks
System tasks run based on a system event such as “Divide by Zero”, “Watchdog
error” or “Warm Start”. These tasks will run once when the event occurs.
Default task
There is only one Default task available and it runs in the background when CPU
time is available. This is considered a background task.
Task implementation
Below is a sample of task implementation.
Main – a cyclic task called Main with a scan rate of 200ms
T1ms – a cyclic task called T1ms with a scan rate of 1ms
T500ms – a cyclic task called T500ms with a scan rate of 500ms
T100ms – a cyclic task called T100ms with a scan rate of 100ms
The order of tasks in the task list is NOT important unless two tasks have the same
priority and interval. In that case the first one in the list will be executed first. When
adding a cyclic task, you give it an interval time (scan rate), a watchdog time and a
priority.
47
APAX-5520 Software Manual
Programming
Write Outputs for Attached I/O Groups
Watchdog time
If the task takes longer than the watchdog time to complete, then the system watchdog error will occur. The watchdog time should be set to the same as the interval
(scan time).
Priority
Tasks can be set at any of 16 priority levels. 0 is the highest priority and 15 is the lowest priority. If a low priority task is running and a higher priority task is scheduled to
run, the higher priority task will interrupt the lower priority task to execute. If both
tasks are the same priority level, then the second task will wait.
APAX-5520 Software Manual
48
The Edit wizard must be used for implementing functions and function blocks. To add
a function block in any language, click in the workspace first, then double click the
function to be added. Once the function or function block is added, then the user
must connect variables to the function or function block. Below are examples of add
function in the FBD language and ST language.
Chapter 3
Function Block Diagram. Variables or other functions must be connected to the
rails.
Programming
3.2.16 Edit Wizard
Structured Text. Comments must be replaced with variables.
3.2.17 Data Types
When implementing a Data type, it is best to use the Edit Wizard to start the process.
Below is an example of an Array:
Once it is defined, you can then implement this data type. It will show up in the list of
data types when you declare the variable:
NOTE: to see online values of Arrays or Structs, you must add the implemented
Array or Struct to the watch window and view it there. The value won’t show up in the
local or global variable list.
49
APAX-5520 Software Manual
3.2.18 Double Mapping Variables
One important concept is Double Mapping of physically located variables. This allows
the end user to accomplish some other tasks. For example we have a 5060 Digital
output board. When mapped as BOOL, it will create 16 variables. In the example
below an additional WORD variable has been added and mapped to the same memory location.
This allows control of all outputs on this board with one variable. If the user wants to
turn on three outputs, they can use three commands, one for each BOOL variable, or
control the whole board with one command as shown below.
This is also convenient for monitoring multiple inputs with one variable, reducing
code size. Double mapping is also an important concept for Memory variables. This
allows multiple memory mapped variables to be combined into one larger memory
mapped variable.
Users can also have two different variables mapped to the same address. This can
cause some confusion and use more memory, but this is possible.
APAX-5520 Software Manual
50
Memory variables are global variables that have an address assigned to them. When
a global variable is declared, its physical location in memory is decided by the compiler. This means that the only way to reference this variable is by name. If the user
wants to reference a variable by location as well as by name then memory variables
are used.
3.2.20 Retentive Variables
There is a checkbox in the Variable worksheet for local variables as well as global
variables that says “Retain”. This will ensure that on a hot or warm boot, that the variable will have the same value as when it was shut down. A cold restart will re-initialize ALL variables including the retained variables.
3.2.21 Literals
Sometimes the user will find that they want to put a constant number in place of a
variable. This is easy to accomplish, but there is something to note. If the constant is
anything other than an INT, then it must be explicitly defined when used. Some
examples are below:
Add Integer number 1.
Add Double Integer number 1. Defined explicitly as DINT#1.
51
APAX-5520 Software Manual
Programming
When using Memory Variables, you must verify that the automatic declaration is
done. To do this go to Resource Settings and select the Data Area button and check
the box “Declare user memory automatically”.
Chapter 3
3.2.19 Memory Variables
Add Real number 1.0. Defined explicitly as REAL#1.0.
3.2.22 Advantech Firmware Function Blocks
Advantech has provided some firmware function block libraries. For help on these
functions, you can select help by right clicking on the graphical representation of the
function block or find the help file located in the same directory as the firmware function library. This will be located on your hard disk where KW Multiprog has been
installed at: \MULTIPROG\PLC\FW_LIB
APAX-5520 Software Manual
52
Appendix
A
A
Version & Firmware
Information
A.1 Version Information
A.1.1 ProConOS
There are two ways to find out the version of ProConOS.
The version is displayed when connected with the MULTIPROG development software. Select the Project Control dialog and click the Info button for the “Firmware”
version. This is referring to the Advantech build of ProConOS. The PLC version is
referring to the KW version number.
Use the Advantech Version tool that is supplied with the Windows CE. This will supply the version number that is written to the registry when ProConOS is installed in
the OS.
APAX-5520 Software Manual
54
The term firmware here is referring to driver firmware that is added to the ProConOS
software. Updates can be found via the Advantech web site. These are other drivers
that can change independently of ProConOS. These files contain the version number
in their file name. The files can be found and updated through explorer in the WinCE
OS. They can be found at \HardDisk\FW. Some examples appear below.
„
55
APAX-5520 Software Manual
Appendix A Version & Firmware Information
A.2 Firmware
APAX-5520 Software Manual
56
Appendix
B
B
APAX.NET Utility
Operation
B.1 APAX.NET Utility General Window
After you install the APAX.NET utility, you can launch it through Start>>Programs>>Advantech>>ApaxNET Utility. Refer to Section 2.5.1 for installation information. Or you can click the shortcut in the HarDisk folder under My Device.
Note!
It may take around 25 ~ 30 second to launch the utility.
Warning! We strongly suggest to close APAX.NET utility after you complete your
configuration to release system memory for other applications.
After you launch the utility, you should see the operation window as figure below.
Except APXA-5000 I/O modules, other devices such as ADAM-4000, ADAM-5000
and ADAM-6000 modules can also be searched and configured in this utility.
The operation window consists of four areas --- the Menu, the Toolbar, the Module
Tree Display Area and the Status Display Area.
APAX-5520 Software Manual
58
The menu at the top of the operation window contains:
„ The File menu
1. Open Favorite Group - You can configure your favorite group and save the
configuration into one file. Using this option, you can load your configuration file
for favorite group.
2. Save Favorite Group - You can configure your favorite group and save the configuration into one file. Using this option, you can save your favorite group into
one configuration file.
3. Auto-Initial Group - If you want to have the same favorite group configuration
when you exit APAX.NET utility and launch it again, you need to check this
option.
4. Exit - Exit APAX.NET Utility.
„
1.
2.
3.
4.
„
1.
2.
3.
4.
5.
„
1.
2.
The Tools menu
Search - Search if there are any remote I/O modules connected. For I/O modules communicated by serial (such as ADAM-4000 modules), click the COM1
item (COM 2 is an internal COM port) under Serial item in the Module Tree Display Area first before you click this button. For I/O modules communicated by
Ethernet (such as ADAM-6000 modules), click the Ethernet item in the Module
Tree Display Area first before you click this button.
Add Devices to Group - You can add any I/O modules to your favorite group by
this option. You need to select the device you want to add in the Module Tree
Display Area (it will be described below) first, and then select this option to add.
Terminal for Command Testing - ADAM modules support ASCII commands
and Modbus as communication protocol. You can launch the terminal to communicate with remote module by these two kinds of protocols directly. Refer to
ADAM-4000, ADAM-5000 and ADAM-6000 manual for ASCII and Modbus command.
Monitor Stream/ Event Data - ADAM-6000 modules support Data Stream function. You can use this to configure related setting for the connected ADAM-6000
modules connected. Refer to ADAM-6000 manual for more detail.
The Setup menu
Favorite Group - You can configure your favorite group including add one new
device (only for remote device), modify or delete one current device, sort current
devices and diagnose connection to one device.
Refresh COM and LAN node - APAX.NET utility will refresh the serial and LAN
network connection situation.
ShowTreeView - Check this option to display the Module Tree Display Area or
not.
Add COM Port Tree Nodes - This option is used to add serial COM ports in
APAX.NET Utility.
Delete the COM Port - This option is used to delete serial COM ports in
APAX.NET Utility.
The Help menu
Check Up-to-Date on the Web - Choose this option, it will automatically connect to Advantech download website. You can download the latest utility there.
About Apax.NET Utility - Choose this option, you can see version of
APAX.NET Utility installed on your computer.
59
APAX-5520 Software Manual
Appendix B APAX.NET Utility Operation
B.1.1 Menu
B.1.2 Toolbar
The six buttons on the toolbar represent the six commonly used items from the
Menus. Refer to figure below for the definition of each button:
B.1.3 Module Tree Display Area
APAX.NET Utility is one complete software tool that all APAX and ADAM I/O module
can be configure and operated in this utility. The Module Tree Display Area is on the
left part of the utility operation window. There are four categories in the Module Tree
Display Area:
„ Serial
All serial remote I/O Modules connected to APAX-5520 will be listed in this category.
You also can configure COM port parameter (such as baud rate, parity, stop bit, etc.)
here.
„ Ethernet
All Ethernet remote I/O Modules connected to APAX-5520 will be listed in this category.
„ APAX-5520
All APAX-5000 local I/O modules in the same system will be listed in this category.
Simply click this item all related modules will be displayed automatically.
„ Favorite Group
You can define which devices listed in Serial or Ethernet categories above into your
personal favorite group. This will make you easier to find your interested modules.
Click on the ADAM device item under Favorite group item, and select Favorite >>
New in Setup menu to create a new group. After you create your own group, click on
your group and select Favorite >> New in Setup menu to add any remote devices
into your group. You can also select Diagnose connection to check the communication.
B.1.4 Status Display Area
Status Display Area, on the right part of utility operation window, is the main screen
for operation. When you select different items in Modules Tree Display Area, Status
Display Area will change dependently. You can do all configurations and tests on
this area.
APAX-5520 Software Manual
60
If you click the APAX-5520 item in the Module Tree Display Area, the Status Display Area should looks similar to the figure below:
All I/O modules with its ID number are listed in the Description tab in the Module
Tree Display Area (the left tab) and Description tab on Status Display Area (the
right tab). You can see all I/O modules supported by APAX-5520 by the Support
Modules tab on Status Display Area. The Backup Setting check box is used to
enable or disable APAX-5520 backup function. Refer to Appendix C for more detail
about backup functionality.
61
APAX-5520 Software Manual
Appendix B APAX.NET Utility Operation
B.2 General Configuration
B.3 I/O Modules Configuration
When you click any I/O module in the Module Tree Display Area, the Status Display Area at the right side will automatically change to show the module's information. There will be two tabs displayed: Module Information and I/O Information.
(Refer to the figure below)
On the Module Information tab, information such as module name, switch ID, module description, and firmware version is displayed. You also can update related firmware to the specific module by the Download button.
On the I/O Information tab, you can write or read all channels' status and perform
related configuration and calibration. Refer to sections below for more detail.
B.3.1 Analog Input Modules
APAX-5520 Software Manual
62
If you want to configure specific input channels' range or integration time, select the
channels in the Channel Status Area. Choose appropriate range and integration
time by the Range and Integration Time combo boxes in the Setting Panel Area
and then click the Apply button to save the configuration. If you want to save the
same range setting for all channels, click the ApplyAll check box before you click the
Apply button.
Note!
In order to remove the noise from the power supply, APAX AI modules
feature built-in filter. Filters are used to remove noise generated from
environment. The integration time is used to configure the filter frequency.
You can define specific channels reading or not by the Enable and Disable button.
Refer to figure below, channel 3 and channel 4 are disabled that no data will be read.
By clicking on the Auto button, you can perform auto calibration to the AI module.
The module will automatically calibrate itself.
63
APAX-5520 Software Manual
Appendix B APAX.NET Utility Operation
There are two parts for the I/O Information tab of APAX-5000 AI module. At the bottom is the Channel Status Area. You can see all channels' type, value, and range.
Above the Channel Status Area is the Setting Panel Area. If you don't want see the
Setting Panel Area, you can click the Hide Setting Panel check box to hide the Setting Panel Area. If you want to see the raw data (presented in Hexadecimal format)
from the input channels, click the Show Raw Data check box.
B.3.2 Analog Output Module
There are two parts for the I/O Information tab of APAX-5000 AO module. At the bottom is the Channel Status Area. You can see all channels' type, value, range and
startup value (the initial value when the AO module is power-on). Above the Channel
Status Area is the Setting Panel Area. If you don't want see the Setting Panel Area,
you can click the Hide Setting Panel check box to hide the Setting Panel Area. If
you want to see the raw data (presented in Hexadecimal format) from the output
channels, click the Show Raw Data check box.
If you want to configure specific output channels' range, select the channels in the
Channel Status Area. Choose appropriate range by the Range combo box in the
Setting Panel Area and then click the Apply button to save the configuration. If you
want to save the same range setting for all channels, click the ApplyAll check box
before you click the Apply button.
If you want to change specific output channel' output value, select that channel by
clicking the channel in the Channel Status Area or choosing it from Channel combo
box in the Setting Panel Area. Then define the output value by the Value text box or
the horizontal slide below in the Setting Panel Area. Then, click the Apply button to
save the configuration. You can see the channel output value changed in the Channel Status Area. Similarly, you can save the value in the Value text box to become
the startup value by the Set as Startup button. And you also can see the startup
value changed in the Channel Status Area.
By clicking the Span button and Zero button, you can perform span calibration and
zero calibration, separately. When you click the Zero button, you will see a dialog
popping-up as figure below. The specific channel will generate output signal using
the minimum value within range which is shown in the Calibration Value text box.
Connect that channel to an external accurate instrument and measure the output signal. Using the Counts to trim buttons to adjust until the output value real matches
the value in the Calibration Value text box. Then click the Apply button to save the
calibration configuration.
APAX-5520 Software Manual
64
B.3.3 Digital Input Module
65
APAX-5520 Software Manual
Appendix B APAX.NET Utility Operation
When you click the Span button, you will see a dialog popping-up as figure below.
The specific channel will generate output signal using the maximum value within
range which is shown in the Calibration Value text box. Connect that channel to an
external accurate instrument and measure the output signal. Using the Counts to
trim buttons to adjust until the output value real matches the value in the Calibration
Value text box. Then click the Apply button to save the calibration configuration.
There are two parts for the I/O Information tab of APAX-5000 DI module. At the bottom is the Channel Status Area. You can see all channels' type, value, and mode.
Above the Channel Status Area is the Setting Panel Area. If you don't want see the
Setting Panel Area, you can click the Hide Setting Panel check box to hide the Setting Panel Area.
If you want to configure specific output channels' filter status or minimum acceptable
pulse width, select the channels in the Channel Status Area. Click the DI Filter
Enable check box in the Setting Panel Area to enable filter for that channel. Type
the appropriate value (unit: 0.1 ms) into the Minimum signal width text box to configure acceptable minimum pulse width in the Setting Panel Area. After you complete the configuration, click the Apply button to save the configuration.
B.3.4 Digital Output Module
There are two parts for the I/O Information tab of APAX-5000 DO module. At the
bottom is the Channel Status Area. You can see all channels' type, value, and mode.
Above the Channel Status Area is the Setting Panel Area. If you don't want see the
Setting Panel Area, you can click the Hide Setting Panel check box to hide the Setting Panel Area.
If you want to change specific output channels' output value, select those channels
by clicking the channel in the Channel Status Area. Then define the output value by
the Set True button or Set False button in the Setting Panel Area. Then, click the
Apply button to save the configuration. You can see the channel output value
changed in the Channel Status Area.
„
APAX-5520 Software Manual
66
Appendix
C
System Backup
Functionality
C
C.1 Introduction
APAX-5000 series delivers system backup functionality. To leverage this functionality,
two CPU modules (controllers), with the same control program, are installed in one
system. After both controllers' backup function is enabled, the APAX-5000 system
will automatically delegate one of the two controllers as the master controller.
The master controller will run the control program to execute the control process,
while another controller (the backup controller) is put on standby. The master controller will periodically send living message to the backup controller. If the backup controller dose not receive living message from master controller over 500 milliseconds,
it will automatically become master controller and take the control responsibility and
restarts the control process execution. The maximum operation time for the backup
controller to become master controller (the take over time) won't be greater than 1.5
second.
Changing master controller means there is something wrong for the previous master
controller. Therefore, engineers can check or change the previous master controller
with a new one and enable it to have backup functionality, becoming a second
backup controller. Then if the new master controller fails again, the second backup
controller will automatically take the control responsibility.
This mechanism ensures the control system will continuously run the control process. And the system won't be stopped even if controller fails.
C.2 Configuration
As you can see in the figure above, two APAX-5520 CPU modules are installed in
one system. APAX-5000 series will automatically decide which one is the master
controller.
APAX-5520 Software Manual
68
69
APAX-5520 Software Manual
Appendix C System Backup Functionality
Warning! The controller ID of the APAX-5520 module is auto-identified by the
location where the module is inserted on the APAX-5002 backplane
(Slot 1 or 2). Thus, be sure NOT to insert two APAX-5520 modules in
the same location on two backplanes. For example, if you insert one
APAX-5520 on slot 1 of one APAX-5002 backplane and insert the second on slot 1 of another APAX-5002 backplane in the same system,
APAX-5000 series cannot distinguish the two APAX-5520 modules.
Backup functionality needs to be enabled for both the two APAX-5520 modules, in
the APAX utility. Refer to figure below. Click the Backup Setting check box in Setting Panel Area and then click the Apply button to enable backup functionality for
APAX-5520.
Note!
After applying the configuration for the backup system, remember to
power cycle the whole system to run the backup functionality.
APAX-5520 Software Manual
70
After you enable backup functionality by utility, you can leverage the backup functionality into your KW program. Before you start your programming, you need add the
Backup I/O driver into the project for later use. Follow the procedure below to add the
Backup I/O driver:
In the Input tab of I/O configuration window, select the BackupSys component and
click the Apply button to add into project.
Then one pop-up window as shown by figure below will appear. You need to select
one task by the Task combo box for the BackupSys component to be added. As
described in Section C.1, the master controller will send living message to backup
controller periodically and the backup controller will automatically become master
controller if it does not receive living message within 500 ms. Therefore, remember to
select one task with cyclic type and less than 500 ms interval time.
After you select the task, click the OK button to finish the configuration.
Change the configuration window to Output tab. Run the same procedures to add
the BackupSys component into the project.
71
APAX-5520 Software Manual
Appendix C System Backup Functionality
C.3 Programming Backup in KW
Then you start to write your control program in KW MultiProg. To leverage backup
function, use the function block "AdvRdSysActiveState" (Refer to the figure below).
As described in Section C.1, APAX-5000 series will automatically assign the master
controller and backup controller. You can use this function block to know if the controller is master controller currently, by the parameter Value. If the Value responses
"True", it means the controller is master controller. If the Value responses "False", it
means the controller is backup controller. So your control program should use this
parameter to decide if the controller should execute the control or simply be put
standby.
APAX-5520 Software Manual
72
Appendix C System Backup Functionality
APAX-5520 Software Manual
73
www.advantech.com
Please verify specifications before quoting. This guide is intended for reference
purposes only.
All product specifications are subject to change without notice.
No part of this publication may be reproduced in any form or by any means,
electronic, photocopying, recording or otherwise, without prior written permission of the publisher.
All brand and product names are trademarks or registered trademarks of their
respective companies.
© Advantech Co., Ltd. 2009