Download Installation Manual - SMA CLUSTER CONTROLLER
Transcript
SMA Solar Technology AG / SMA America, LLC 6 Connection and Commissioning Figure 11: Pin assignment for network ports X9, X10, X13 and X14 Pin Designation Explanation 1 TX+ Data Out + 2 TX − Data Out − 3 RX+ Data In + 4 Not assigned Not assigned 5 Not assigned Not assigned 6 RX− Data In − 7 Not assigned Not assigned 8 Not assigned Not assigned Procedure: 1. Connect the Cluster Controller to the Speedwire network. Take the desired network topology into account: • When using a preassembled network cable, connect the network cable to network port X9 or X10. • When using a network cable that is to be assembled by the user, connect the RJ45 connector to the network cable (see the manual from manufacturer) and connect the network cable to network port X9 or X10 on the Cluster Controller. 2. Write down the terminal assignment on the supplied supplementary sheet. 3. Deactivate the Webconnect function on the inverters after completion of Cluster Controller commissioning (see the Cluster Controller user manual). 6.9 Connecting the Cluster Controller to the LAN Additionally required material (not included in the scope of delivery): ☐ 1 network cable (see Section 6.3 "Cable Requirements", page 30) Installation Manual ClusterController-IA-en-14 41