BLCDN-8M12L-4AI-VI-4AI-VI 9 Mapping and diagnostics 9.1 I/O and Diagnostic Data mapping INPUT Diag. BYTE Bit 7 Bit 6 Bit 5 Bit 4 0 1 2 3 4 5 6 7 AI 0 LSB AI 0 MSB AI 1 LSB AI 1 MSB AI 2 LSB AI 2 MSB AI 3 LSB AI 3 MSB 8 9 10 Module number reporting diagnostic data Replace N/A Diag. Reserved station active Reserved 11 Reserved 12 Reserved 13 Reserved 14 Reserved 15 Reserved 16 Reserved 17 Reserved Bit 3 Bit 2 Bit 1 Bit 0 Range error CH 0 Range error CH 1 Range error CH 2 Range error CH 3 Range error CH 4 Range error CH 5 Range error CH 6 Range error CH 7 * The scheduled diagnostic information changes every 125 ms between slot 1 and 2, if both slots send active diagnostics. 9.2 4AI-VI - Diagnostic messages Edition • 2011-3-15 Diagnostic message Range error CH x 13 / 32011 Meaning The measurement range has been exceeded. The threshold is 1% of the positive measurement range end value. In current mode, an underflow diagnosis is only invalid for the value range 4...20 mA. Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com