Download User Manual - MSR Electronic

Transcript
User Manual PolyGard® SPC 63-1181
Page 23
Connection Diagram
5
4
3
2
0(2) -10V
24 VDC
0 VDC
SPC-X3
Option
internal Buzzer
5
4
3
2
24 VDC
0 VDC
5 Analog_Inp
0V
R1
2 0 VDC
Bus_B
Bus_A
Option Communication
0V
24 VDC
X5 Option external
5 -----
Warning Light
6
NO_1
7
NC_1
8
COM_1
9
R2
1 24 VDC
X4
Analog
output
Analog Output Signal:
adjustable via jumper
(0)4-20mA / (0)2-10 V
4 Analog_Out
V- V+
24 VDC 230
VAC
L N PE
2
3
4
3
Flashlight
3 24 VDC_Out
7 BUS_B
6 BUS_A
X4
Option external
Buzzer
4
R4 Option int.
6 Bus_A
Option external
Transmitter (MP 02) X4
+ 24V
0V
7 Bus_B
Digital
Input
2
R3
4 -20mA
X5
DIO 1
NC NO
4.2
X5
11
COM_2
10 NO/NC_2
11
2
3
4
K3
*
14 12
* Pin 4 = Alarm 4
Pin 2 = Alarm 3
Option Power Relay K3
max. 250 VAC / 5 A
R1:
SPDT, 30 VAC/DC, 0,5 A
R2:
SPNO/SPNC, 30 VAC/DC, 0,5 A
R3/R4: Open Collector, 30 VDC, 50 mA
2 0 VDC
1 24 VDC
X4
2 0 VDC
1 24 VDC
X4
Option Power Supply 90 - 230 VAC
6
7
8
9
10
X5
11
K1
14 12
11
K2
14 12
Option Power Relay
max. 250 VAC / 5 A
Fig. 2 Connection diagram
* The analog input function is determined by the hardware. Each PCB has got a label with the specific type. See
fig. 4.
Note:
The alarm outputs R3 and R4 are designed as open collector outputs. Warning lamps / horn combination
units with common ground can therefore not be connected!
PolyGard is a registered trademark of MSR
Phone: 0049(0)8531/9004-0
Fax: 0049(0)8531/9004-54
MSR-Electronic GmbH, Würdinger Str. 27, D 94060 Pocking
GASPC631181_E_0115
www.msr-electronic.de
Specification subject to change without notice.
Printed in Germany