Download English
Transcript
Troubleshooting 8 Troubleshooting 8.1 WF2 Fault Codes Table 29 shows the fault codes that may be displayed, along with suggestions for recovering from the fault condition. Fault Code Fault Name Possible Cause(s) How to Recover 01 Watch Dog Trip Contact BERGES for further information. Contact BERGES for further information. 02 Power Bridge Id • • Ribbon cable not correctly seated be- • tween the power and control boards. Electrical noise. • Ensure that the ribbon cable is correctly seated. Determine the source of the noise and eliminate it. 03 Current Calibr Current sensors have an offset problem. Contact BERGES for further information. 04 TSP 24V Supply Overloaded +24 V DC supply. Check the loading on the +24 V DC supply and remove any excess load. 05 DC Volt Calibr DC voltage is outside of normal limits on • • power-up. This may be caused by: • High or low line voltage. • Supply Voltage parameter incorrectly set. Check line voltage. Check the Supply Voltage parameter (see page 106). 06 IOC Trip Output short-circuit. May also be caused • by a ground fault (see Fault Code 11 be- • • low). • Check motor wiring. Extend acceleration ramp. Reduce boost. Check for ground faults. 07 Ext Flt/Warning (Fault) The configured input sensed an external fault. Investigate why the external fault occurred and correct. 09 Inter-Proc Comm Loss of communication with the control terminal strip. Reset the drive by pressing the Stop key for more than 1 second. If problem persists, consult BERGES. 11 Ground Fault The drive detected that the sum of the mo- • tor phases’ current is not zero. This may • be caused by insulation failure in the mo• tor or the cables. 12 Input Phase Loss Current measurement detected an input phase with no current. 13 Overvoltage The voltage of the internal DC-link has ex- • ceeded 135% of the nominal voltage. This • may be caused by incorrect deceleration time or high overvoltage spikes on line. 14 Under Voltage The DC bus voltage fell below 65% of the nominal voltage. This may be due to line supply failure or internal failure of the drive. Reset fault and attempt to restart. Check the line for proper supply. If fault persists, an internal fault has occurred; contact BERGES. 15 DB Crct Failure The dynamic brake (DB) is overloaded. • • • Check motor wiring. Check for and remove any capacitive load. Check the motor and cabling for shorts to ground. Check input power cables. Adjust deceleration time. Add dynamic braking module. Check for an open DB resistor. Check for a shorted DB transistor. Consult BERGES. Table 29 07.11.03 08_GB TB Wood’s and Berges – All Rights Reserved WF2 — 0.75–55.0 141