Attachment to the control valve – Mounting parts and accessories
4.8 Mounting the leakage
sensor
Fig. 19
Normally, the control valve is delivered with
positioner and leakage sensor already
mounted.
If the leakage sensor is mounted after the
valve has been installed or it is mounted onto another control valve, proceed as described in following.
NOTICE
Risk of malfunction due to incorrect
fastening!
Fasten the leakage sensor using a
torque of 20 ±5 Nm.
3
2
The M8 threaded connection on the NAMUR
rib should preferably be used to mount the
sensor (Fig. 19).
Tip:
If the positioner was mounted directly
onto the actuator (integral attachment), the NAMUR interfaces on either side of the valve yoke can be
used to mount the leakage sensor.
The start-up of the leakage sensor is described in detail in the Operating Instructions
for EXPERTplus Valve Diagnostics
u EB 8389-1 EN.
1
1 Leakage sensor
2 Screw
3 Plug connection
Fig. 19:Mounting the leakage sensor
48 EB 8384-6 EN