Setting the eBUS address
Setting the eBUS address
for cascade mode
Whenoperatingseveralboilers(upto4controlunitsR1)inconjunction
withacascadecontrollerKM,adjusttheeBUSaddressoftheboilersin
accordancewiththetable,below.
YouadjusttheeBUSaddressbyholdingdowntheresetbuttonwiththe
systemoperating.After5seconds,thecorrespondingflashingcodeappears
(inaccordancewiththetable)atthesignalring.Selectthecorresponding
eBUSaddresswiththeDHWtemperaturerotaryselector.Yourselectionof
therequiredeBUSaddressissavedbyreleasingtheresetbutton.
Boiler in
cascade
mode
individual
boiler*
1
eBUS
address
Position rotary
selector DHW
temp. selection
Display signal
ring
1
1
redflashing
2
3
2
3
2
3
4
4
4
yellowflashing
yellow/red
flashing
yellow/green
flashing
greenflashing*
*Factorysetting(individualboilerwithoutcascademode)
*Inconjunctionwithacascademodule,thefirstboilermustbesetto
BUSaddress1.
BUS address setting
TheassignmentofgasboilersorBUSaddresses(1),(2),(3)and(4)must
bemadeon-site.AllocateeachBUSaddressonlyonce.
Note: IfonlyoneBUSsubscriber(boilerorKM)isisolatedfromthepower
supply,thenstopandstartallsubscribersviaasystemswitch.
Resetbutton
Temperature
selectionDHW
Cascade operation
InconjunctionwiththeKMcascadecontroller,between1and4R1control
unitscanbelinkedup.
Communication is realised via the two-wire BUS. Each boiler has an
eBUSaddressassigned.TheKMprovideseachboilerwiththemodulation
level(0...100%)andanenablecommand,uponwhicheveryboilermust
operate.
TheR1startsassoonastheKMissuesamodulationlevelgreaterthan
0.CylinderheatingcontinuesintheR1.Theemissionstestoperationcan
onlybeenabledviatheheatingrotaryselectorattheR1.
Aftertheburnerhasbeenshutdowntherewillbenomorecyclingblock.
Incascademode(modulationlevel>0)theboilercircuitpumpautomatically
becomesthefeedpump.
Ifmodulationlevel>0thenpumpON.
3061809_1210
29