Download Installation and operating instructions
Transcript
Contractor level parameters No. Explanation 2 Maximumthermostat Toenabletheburner,inputE1mustbeclosed.The burnerwillremainblockedforaslongasthecontactis open,eveninemissionstestmode,cascademodeand forDHWandcentralheatingfrostprotectionmode. 3 N/A 4 N/A 5 Fluegasdamper/ventilationairdamper Functionmonitoringofthefluegasdamper/ ventilationairdamperwithfloatingcontact.Closed contactConditionforburnerenableincentral heating,DHW,cascadeandemissionstestmode. Important: A1 (HG 14 = 7) must be programmed for flue gas damper / ventilation air damper function. 6 3061809_1210 DHWcirculationpushbutton(onsite) Afteractivatingthisbutton,theDHWcirculationpump isoperatedfor5minutes,independentof thetimeprogramorthepositionoftheprogram selector(BM). Important: In any case, output A1 must be programmed to setting 13. 17