Limiting the maximum output
MGK-130 / MGK-170 / MGK-210 / MGK-250 / MGK-300
Output setting (parameter GB04)
The output setting can be modified with Wolf control accessories with eBUS capability.
The heating output will be determined by the gas fan speed. By reducing the gas fan speed in accordance with the
table, the maximum output will be matched at 80/60 °C to natural gas H.
MGK-130
Output (kW)
Display value (%)
23
20
31
25
38
29
46
34
53
38
61
43
68
47
76
52
83
56
91
61
99
65
106
70
114
75
121
100
MGK-170
Output (kW)
Display value (%)
27
20
40
28
50
34
60
40
70
46
80
52
90
58
100
64
110
70
120
76
130
82
140
88
150
94
160
100
MGK 210
Output (kW)
34
40
55
70
85
100
115
130
145
160
175
190
200
Display value (%)
20
23
30
37
45
52
59
66
73
81
88
95
100
MGK 250
Output (kW)
Display value (%)
40
20
55
26
70
32
85
38
100
44
115
50
130
56
145
62
160
68
175
74
190
80
205
86
220
92
240
100
MGK-300
Output (kW)
Display value (%)
45
20
62
27
79
34
97
41
114
47
131
54
148
61
165
68
182
75
200
82
217
89
234
96
251
102
275
100
Table: Output setting Maximum output in [kW]
Limiting the maximum output relative to a flow/return temperature of 80/60 °C
Settings for parameter GB04 with eBUS-enabled Wolf connection accessories in [%]