Download Operating Instructions - Differential pressure transmitter DPT-10
Transcript
8 Setup Measurement setup for liquids A + B 6 7 + – I III II 1 3 2 III 4 5 Fig. 55: Preferred measurement setup for liquids IDPT10 II 3-fold valve block IIIPrecipitator 1.5Drain valves 2.4Inlet valves 3 Breather valve 6, 7 Vent valves on DPT10 A, BBlocking valves Prepare the adjustment Proceed as follows: 1. Close valve 3 2. Fill measuring system with medium. Open valves A, B, 2, 4: Medium flows in. If necessary, clean the differential pressure lines: - with gases by blowing out with compressed air - with liquids by rinsing.4) Close valve 2 and 4, block the instrument Open valve 1 and 5 Close valve 1 and 5 3. Remove air from instrument: Open valves 2 and 4: Medium flows in Close valve 4: Minus side is closed Open valve 3: Equalisation plus and minus side Briefly open valve 6 and 7, then close again: Fill the measuring instrument completely with the medium and remove air 4. Put measurement loop into operation: Close valve 3: Separate plus and minus side Open valve 4: Connect minus side Now: 4) 62 Arrangement with 5 valves. WIKA Operating Instructions - Differential pressure transmitter DPT-10