5.3 Operation Levels
Beside the direct data entry the operation and configuration of the controller takes place in 3 sublevels starting
from the main level:
a
Direct entry
Setpoint/
Degree of operation*
a
Actual-/setpoint value (control mode)
Main level
Actual value/degree of operation (manual
mode)
Information
Level
User Level
USEr
System Level
SYS
Enabling
User level
a
a
a
* Direct data en- Direct data entry of set point (the controller is in control mode) and degree of operation (the
try of set point controller is in manual mode) only for Ó[P099]Edit - Entry Mode Directly (page 38) = on.
and degree of
operation
Main level
In the main level actual value and set point and actual value and degree of operation respectively are displayed.
Display and operation of the often used process parameters (set point, manual mode, heating
Information Level current, alarm).
Is Loc displayed in the actual value display; see chapter ÓDisplay Loc (page 17).
User Level
USEr
Display and operation of parameters that are occasionally displayed and changed. The list of
parameters can be arranged individually.
Is Loc displayed in the actual value display; see chapter ÓDisplay Loc (page 17).
Display and operation of all parameters.
Unblocking at user level: Additionally to the parameter value each parameter has an unblock
information at user level. This defines the status of the parameter at user level:
System Level
SYS
Ú hidden
Ú visible/not changeable or
Ú visible/changeable.
The display at user level can individually be arranged for the application.
Is Loc displayed in the actual value display; see chapter ÓDisplay Loc (page 17).