Contractor level parameters HG01 15 Factory setting: 15 K Setting range: 5 to 30 K Individual setting:___________ The burner switching differential regulates the burner temperature within a set range by switching the burner ON and OFF. The higher the ON / OFF temperature differential, the higher the boiler water temperature fluctuation around the set value, resulting in longer burner runtimes and vice versa. Longer burner runtimes protect the environment and extend the service life of wearing parts. Switching differential (K) Burner switching differential (dynamic) Parameter HG01 Selected switching differential 15 K Hysteresis time 10 minutes Burner runtime (min.) Fig.: Time sequence of the dynamic burner switching differential for a user-defined burner switching differential of 15 K and a selected hysteresis time (parameter HG33) of 10 minutes. 3061828_1210 13