Download Installation and operating instructions
Transcript
High limit safety cut-out changeover Adjustment of the high limit safety cut-out (STB) The high limit safety cut-out (STB) is factory-set to 110 °C. If required, it can be changed over to 100 °C. Such changes are irreversible. Disconnect the control unit from its power supply. Remove cap. Remove the cover from the high limit safety cut-out. Release the high limit safety cut-out fixing screws. Release the fixing screws of the control unit front cover and pivot forward. Remove the high limit safety cut-out. Release the clamping screw. Adjust the setting disc to 100 °C in accordance with the scale and retighten the clamping screw. Reassemble in reverse order. NB The maximum boiler water temperature (TK‑max) must not be set to 90 °C, if the high limit safety cut-out has been adjusted to 100 °C. 3061828_1210 29