2. Menu System Setup
The system setup menu is used to make settings that are necessary for the configuration of the system
during the startup. These settings are made by an authorised installer or by the service
staff of Paul Wärmerückgewinnung GmbH! Improper changes of the parameters listed here may
cause undesirable effects, the system may possibly work incorrect. Any customer service proven to
be caused by improper operator actions will be charged. The system setup is always programmed for the
highest configuration whether or not your specific system can use and evaluate all options mentioned
here.
9
0
1
2
3
4
5
6
7
8
-----------------------|System setup 9.0
|
|
|
| Enable
<-| TA1
|>Defroster
<
|
| Bypass Su/wi
|
| Brine/GHX
ok| TA2
| Heat pump
|
| Solar
|
| Duct heater
|
| Buffer-max
|
| Ventilation steps
|
| W-Settings
|
| ↓
↑
|
-----------------------TA5
TA4
TA3
Press TA4 and TA5 to scroll through menu 9.0 – 9.9, select item by pressing TA2. Press TA1 to return to
previous menu.
The menu items Heat pump, Solar and Buffer-max are only available for compakt 350DC series. The
remaining menu items need the corresponding hardware installed.
2.1
Menu System Setup - Defroster
----------------------|Defroster 9.0.0
|
|
<-| TA1
|PTC: yes/no
|
|on: T7< -> (x1)°C
|
|Hysteresis: (H1)°C |
|
| TA2
|
|
| ->
+ |
----------------------TA5
TA4
TA3
Press TA5 to select value and TA3 / TA4 to adjust value.
Example:
Setting:
on: T7 <
2°C
Hysteresis: 1°C
Defroster ON: T7 < 1,0 °C
Defroster OFF: T7 > 3,0 °C
Secondary conditions Defroster ON:
Defroster enabled
∗
Temperature limiter ok
∗
Flow sensor Fz1 ok
∗
Power input Fz1 ok
Temperature sensor T7 plausible
Ventilation enabled
Ventilation step not equal to zero
Secondary conditions Defroster OFF:
© Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland