Download Fujitsu TX200 S6 User's Manual
Transcript
CSS components Ê Install the new HDD module, as described in "Installing the HDD module" on page 101. V CAUTION! If you have removed a HDD module and do not install a new one in its place, put the dummy module back in its place for cooling, to comply with EMC regulations (regulations regarding electromagnetic compatibility), and for protection against fire. Ensure that the dummy module engages correctly in the bay. 8.2 Non-hot-plug components If a defective non-hot-plug component is detected (for more information, see chapter "Starting up and operation" on page 65 and the "ServerViewSuite Local Service Concept - LSC" manual on the ServerView Suite DVD 2), proceed as follows: Ê Exit all applications and shut down the server properly (see section "Switching the server on and off" on page 77). Ê Pull all power connectors out of the power outlets. Ê If the model is a rack model, remove the server from the rack (see section "Installing/removing the rack model" on page 49) and place the server on a table, for example. Ê Open the server (see section "Opening the server" on page 104). Ê Press the Indicate CSS button on the system board (see the technical manual for the system board D2799). The PRIMERGY Diagnostic LED of the defective CSS component lights up orange, thereby indicating which CSS component (memory module, fan or expansion card) on the system board must be replaced (see technical manual for the system board D2799). TX200 S6 Operating Manual 103