Download APC PDPB150G6F
Transcript
brkrThrMx Access: Administrator, Device Description. Configure the max load alarm threshold and critical alarm on the breaker selected by the brkrTarget and brkrPanel commands. Valid threshold values are 0-100% where ThrMx > ThrHi > ThrLo > ThrMn. Parameters: [<thresh>] [<enable|disable>] (Thresh = % rated load) Example: apc> brkrstatus 2 1. 1.2,Newname 1.2,Newloc 1.2,Unknown,30A,50A,Normal,30.2kW,60.2kWh,11/08/ 2012 2. 1.2,L1,10.2A,34.0%,1.4,L2,10.4A,34.6%,1.6,L3,10.6A,35.3% 3. 1.2,Enable,80%,24A,Enable,60%,18A,Enable,10%,3A,Enable,1%,0A,Enable apc> brkrthrMx 85 1. 1.2,Enable,85%,25A,Enable,60%,18A,Enable,10%,3A,Enable,1%,0A,Enable Error Messages: E102 brkrThrHi Access: Administrator, Device Description. Configure the high load alarm threshold and warning alarm on the breaker selected by the brkrTarget and brkrPanel commands. Valid threshold values are 0-100% where ThrMx > ThrHi > ThrLo > ThrMn. Parameters: [<thresh>] [<enable|disable>] (Thresh = % rated load ) Example: apc> brkrstatus 2 1. 1.2,Newname 1.2,Newloc 1.2,Unknown,30A,50A,Normal,30.2kW,60.2kWh,11/08/ 2012 2. 1.2,L1,10.2A,34.0%,1.4,L2,10.4A,34.6%,1.6,L3,10.6A,35.3% 3. 1.2,Enable,85%,25A,Enable,60%,18A,Enable,10%,3A,Enable,1%,0A,Enable apc> brkrthrHi 65 1. 1.2,Enable,85%,25A,Enable,65%,19A,Enable,10%,3A,Enable,1%,0A,Enable Error Messages: E102 46 User Guide InfraStruxure 150kVA Power Distribution Unit