76
Avocent PM PDU Installer/User Guide
CMN
Listed
Outlet
Bank
Input
Output
Bank Max
Branch
Input Voltage
Max
Max
Current Voltage
Unbalanced
Circuit
Current
Balanced
Current
Protection
Current
PM2004V401
PM3004V401
1068
EU three
phase 220240/381-415
VAC 3W + N +
PE 50/60Hz
IEC309
516P6W
16A per
phase
220-240
VAC
50/60
Hz
PM2006H401
PM3006H401
US three
phase 100120/200-208
1057VAC 3W + N +
264
PE, 50/60 Hz
NEMA L21L30P
24A per
phase
Unit
PM2001H401
PM3001H401
PM2001V401
PM3001V401
YAH3001V401
PM2003H401
PM3003H401
16A
(C19)
10A
(C13)
16A
16A
20A
200-208
VAC
16A
50/60
Hz
16A (see
note 1)
13.85A
30A
1059
US single
phase 200-240
VAC 2W + PE
24A
50/60 HZ
NEMA L6-30P
200-240
VAC
16A
50/60
Hz
16A (see
note 2)
8A
30A
1065
US single
phase 200-240
VAC 2W + PE
24A
50/60 HZ
NEMA L6-30P
200-240
VAC
50/60
Hz
16A
(C19)
12A
(C13)
16A (see
note 2)
8A
30A
1065
US single
phase 200-240
VAC 2W + PE
24A
50/60 HZ
NEMA L6-30P
200-240
VAC
12A
50/60
(C13)
Hz
16A (see
note 2)
8A
30A
1060
EU single
phase 220-240
VAC 2W + PE
32A
50/60 Hz
IEC309
332P6W
220-240
VAC
16A
50/60
Hz
16A (see
note 3)
10.66A
40A