5. Carefully align the motherboard connector to the motherboard pin field.
Gently press the connector down until it is seated. If you feel significant resistance,
stop and check the pin alignment.
6. Replace the air duct.
See Section 4.2.2, “Installing the Air Duct” on page 4-11.
7. Return the server to operation.
a. Install the top cover.
See Section 6.1, “Installing the Top Cover” on page 6-2.
b. Slide the server into the rack.
See Section 6.3, “Returning the Server to the Normal Rack Position” on
page 6-4.
c. Reconnect the power cord (or cords) to the power supply (or supplies).
Verify that the AC Present LED is lit.
See Section 6.4, “Powering On the Server” on page 6-6.
d. Power on the server.
See Section 6.4, “Powering On the Server” on page 6-6.
5-28
Sun Fire X4250 Server Service Manual • November 2009