Download Submittal - Space Ray
Transcript
2) MINIMUM CLEARANCES TO COMBUSTIBLES Minimum clearances to combustibles shall be measured from the outer surfaces as shown in the following diagram: MINIMUM CLEARANCES TO COMBUSTIBLES Model No. ETS 40, 50 ETS 60, 75 ETS/ETU 80, 90 ETS/ETU 100 ETS/ETU 110, 120, 125, 130 ETS/ETU 140, 150 ETS/ETU 160, 175 ETS/ETU 180, 200 ETS/ETU 225, 250 Sides 24” 24” 26” 28” 32” 36” 42” 44” 56” Mounted Horizontally Ceiling* Below 6” 40” 6” 60” 6” 66” 6” 76” ** 6” 82” ** 6” 87” ** 6” 93” ** 6” 106” ** 6” 112” ** Ends 15” 15” 15” 15” 20” 20” 20” 20” 20” Angle Mounted at 45º 45º Front 45º Rear 40” 12” 52” 12” 52” 12” 60” 12” 66” 12” 70” 12” 77” 12” 84” 12” 90” 18” When used indirect vented, the clearance must be: 12” for ETS/ETU40-75 and 18” for ETS/ETU80-250. If optional corner reflectors are not used, the clearance must be 18”. Minimum Clearance BELOW reduces to 72” once you are 20 feet downstream from the control box. NOTE: The clearances specified above must be maintained to combustibles and other materials that may be damaged by temperatures 90ºF above ambient temperature. Clearances to combustibles are posted on the control box. In areas used for storage of combustible materials where they may be stacked below the heater, NFPA54 requires that the installer must post signs that will “specify the maximum permissible stacking height to maintain the required clearances from the heater to combustibles.” Space-Ray recommends posting these signs adjacent to the heater thermostat or other suitable location that will provide enhanced visibility. SUBMITTAL ♦ ETS/ETU 3 Jul-13