Download Brother J430W Printer User Manual
Transcript
Operation 10.6 De-Energize Liebert APM with Maintenance Bypass Cabinet. ! CAUTION This procedure will remove power from the critical bus. To de-energize the system: 1. On the UPS control panel, press and hold the INVERTER OFF button for 2 seconds. 2. Open all battery circuit breakers(s) including internal battery breaker (if applicable). ! CAUTION Performing the next step will shut down the critical load. 3. If the MBC is an Emerson cabinet, open the Maintenance Isolation Circuit Breaker (MIB). If the MBC is a customer-issued switchgear or a non-Emerson cabinet, open the breaker(s) that supply power to the critical bus. 4. Open the Rectifier Input Circuit Breaker and Bypass Input Breaker (if dual input). If the MBC is a customer-issued switchgear or a non-Emerson cabinet, open the breaker(s) that supply power to the UPS input and bypass input (if dual input). 5. Allow 5 minutes for all DC circuits and capacitors to fully discharge. 6. Open the external feeder breaker to the MBC or bypass switchgear. 7. Install a Lockout/Tagout on the external feeder breaker to the MBC or bypass switchgear. 8. Use a digital multimeter to verify there is no AC or DC voltage present at the UPS input, output and bypass bus bars. 9. Use a digital multimeter to verify there is no AC or DC voltage present at the MBC BIB, MIB and MBB breakers. 96