Download Danfoss VLT 8000 AQUA Operating instructions
Transcript
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA Configurations properties (Nci) The VLT LonWorks option card supports LonMark network design to improve interoperability. The Controller Object contains the VLT Adjustable Frequency Drive profile. Function Nom. motor freq. 1) Nom. motor rpm Min. frequency 1) 1) Max. frequency 1) Ramp up time 1 1) Ramp down time 1 Heart beat time 1) 1) The configuration parameters are network variable inputs to the VLT. Configuration of parameters needs setting only one time, usually at installation. SNVT type Variable Name Units VLT 6000/8000 parameter VLT 5000 parameter SNVT_freq_hz nciNmlFreq 1 Hz 104 104 SNVT_rpm nciNmlSpeed 1 rpm 106 106 SNVT_lev_percent nciMinSpeed 0.005% 201 201 SNVT_lev_percent nciMaxSpeed 0.005% 202 202 SNVT_time_sec NciRampUpTime 1 sec 206 207 SNVT_time_sec NciRampDownTime 1 sec 207 208 SNVT_time_sec NciSndHrtBt 0.1 sec - - (EDIT SETUP SELECT) Part of the LonMark Functional Profile for Variable Speed Drive 6010 version 1.1 1) When the NciSndHrtBt time is active it will sent the following variables: • nvoDrvCurnt • nvoDrvSpeed • nvoDrvVolt • nvoDrvPwr NOTE Please note that writing to Configuration properties will be stored in the Non-Volatile memory. Continous writing to Configuration properties may damage the Non-Volatile memory. Please note that nciNmlFreq and nciNmlSpeed can only be written to when the VLT frequency converter is stopped. VLT 5000 parameters are shown in parenthesis, where applicable. MG.60.N2.02 - VLT is a registered Danfoss trademark 25