57-DVRS50 13 Installation Instructions Cont. The following vent systems are certified for use with the model 57-DVRS50 Duravent 5 x 8 Direct Vent Selkirk 5 x 8 Direct Vent Ameri-vent 5 x 8 Direct Vent ICI 5 x 8 Direct Vent Archgard 999-DV-8HTCL (Through the wall termination) Note: ONLY THE LISTED VENT MANUFACTURERS LIST ABOVE MAY BE USED NOTE: Please refer to vent manufactures instructions regarding sealing methods and additional installation instructions as all vent manufactures use there own methods for sealing and general installation. VENTING Clearance to combustibles The following clearances must be maintained around the vent pipe: Vertical runs: 1” Horizontal runs: 2” on top, 1” sides and bottom IMPORTANT: This appliance venting system is a sealed system (DV), which means that all combustion air is supplied from outdoors and the combustion products are exhausted to the outdoors. Note: Only venting systems listed in this manual may be used with the model 57-DVRS50 Planning your vent installation This type of direct vent system may terminate in one of two ways: vertical termination using a vent cap, or horizontally using a wall termination. There are limitations to the vertical and/or horizontal lengths (see page 17 for venting chart). When calculating the length of the vent pipe from the outlet of the appliance to termination, allowing for ceiling thickness, the vertical rise in the attic or second story and sufficient vertical height above the roof. Fire stops are required at each floor level the vent passes through.