Chapter 4: Installation Table 4-1. Terminal Block Connection Definitions Terminal Block Symbol TB1 Terminal Block 1 Section 1 Alarm Connections TB2 Terminal Block 2 Section 2 TB3 Terminal Block 3 Section 3 Alarm Connections Definitions ALM Alarm connections Alarm Form C relay changes state in Audio Alarm Conditions. These conditions are: Push-to-talk Button on MIC depressed. AUX initiated via CC or NAC, and IN1- IN8 inputs present. Contacts are rated at 24VDC, 2A. Resistive load. NO Normally open Alarm Relay contact open to Common (COM) in non-alarm condition. NC Normally closed Alarm Relay contact closed to Common (COM) in non-alarm condition. COM Common Alarm Relay Common (COM). System Trouble Connections TRB System Trouble connections Trouble Form C relay changes state in Trouble Conditions. Contacts are rated at 24VDC, 2A. Resistive load. NO Normally open Trouble Relay contact open to Common (COM) when a system trouble is NOT present. NC Normally closed Trouble Relay contact closed to Common (COM) when a system trouble is NOT present. COM Common Trouble Relay Common (COM). AC Trouble Connections AC TRB AC Trouble connections AC Trouble Form C relay changes state when primary power is missing or low. Contacts are rated at 24VDC, 2A. Resistive load. NO Normally open AC Trouble Relay contact open to common (COM) when primary power is sufficient. NC Normally closed AC Trouble Relay contact closed to common (COM) when primary power is sufficient. COM Common AC Trouble common (COM). SP40S Multi-Function Facility Communication System Manual, Revision D 3