Download Procon 15 Technical data
Transcript
Procon 13.0 Flue Terminal Positions The flue terminal of the Procon 15, 25, 45 & 75 boilers’ will plume water vapour, heavily and care must be taken when selecting the terminal position to ensure that a “nuisance situation” is not created. Where the flue terminal discharges within 2 metres of ground or any upper part of the building where people have general access, i.e. balcony level, etc., a terminal guard MUST be fitted to prevent the terminal from being touched. Fig 13.0 – Minimum Clearances Minimum Distance All Dimensions are in millimeters, See Fig 13.0 Dimension A B C D E F G H I Description Directly below an opening, air brick, window, etc. Below gutters, soil pipes, drain pipes, etc. Below eaves Below balconies, car port roof, etc. Vertically from soil pipes, drain pipes, etc. From internal or external corners. Above ground, intersecting roof, balcony level, etc. From a surface facing the terminal. From a terminal facing the terminal. Minimum Distance Dimension 300 J 75 K 200 L 200 M 150 N 300 P 300 Q 2000 R 2000 S Description From an opening, door, window, etc., in a car port Vertically from a terminal on the same wall. Horizontally from a terminal on the same wall. Above an opening, window, etc. Horizontally to an opening, window, etc. Above a level roof (base of terminal). Q From adjacent wall (edge of terminal). From adjacent opening window. From any other flue terminal. Minimum Distance 1200 1500 300 500 300 500 500 1000 600 Note: Dimensions highlighted in BOLD are not recommended locations. 15