Download Real Cable HDS-12 User guide
Transcript
Service clearance, floor cutout, and floor load rating This section describes the service clearance requirements for the HUS VM storage system, based on the clearance and required floor cutouts for cabling. • Make sure that the service clearance for maintenance is available. • Do not use the clearance space for storage • The floor cutout area and dimensions correspond to 19-inch rack specifications • Hitachi Data Systems recommends that you install the grid panel over 450 x 450 mm on the front side of the rack. • The floor must have a load rating between 660 lbs (300 Kg) and 1,540 lb (700 Kg) per square meter. Note: For safe and efficient maintenance operations, clearances should be made as large as possible. Actual clearances for installation should be determined after consulting with the site/facilities manager, as the clearances can vary, depending on building conditions. Single rack configuration The following figure shows the service clearances for a single rack configuration. 4–16 Site preparation Hitachi Unified Storage VM Block Module Hardware User Guide