Load Current Monitoring and Diagnostics Installation and O eration Handbook 9.10 THE SCALING FACTOR The value of the current displayed on the controller is scaled using the scaling factor. This is found in the list. It is set, by default, to 100 and assumes a single turn through the current transformer. If two turns are made through the current transformer it will be necessary to adjust the scaling factor to 50 to obtain the same reading. Under normal conditions you should not need to change the scaling factor. If, however, you wish to change the sensitivity of the current reading, for example, to read very low currents you may need to change the number of turns through the PDCTX and/or adjust the scaling factor to compensate. See also note 1 below. 9.10.1 To adjust the scaling factor Do This Press until This Is The Display You Should See button is displayed Press Additional Notes until is displayed or Press to change the scaling factor Minimum Resolvable Current TE10 4A RMS. It is not possible to read currents lower than 4A when using a TE10. PDCTX 4A RMS for a single turn through the PDCTX Should you wish to read currents lower than 4A using a PDCTX it is necessary to increase the number of turns through the PDCTX and adjust the scaling factor to compensate. For example: To read 1.0A wind 4 turns through the PDCTX and adjust the scaling factor to 25 as shown in the table below. Scalar = 100/N PDCTX N 1 2 4 5 10 Where N = Turns through Scalar 100 50 25 20 10 Maximum Resolvable Current TE10 Determined by the maximum range of the SSR PDCTX 100A (or 100 ampere turns) Finally Exit configuration level. See Chapter 5. 9-12 2208e and 2204e Controller