Download Viessmann WS3A Operating instructions
Transcript
Service instructions VIESMANN for heating engineers Vitodens 333 Type WS3A Compact gas fired condensing boiler 4.2 to 13 kW natural gas version 6.6 to 26 kW natural gas and LPG version For applicability, see the last page VITODENS 333 5692 619 GB 8/2005 Please keep safe Safety instructions Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions explained Danger This symbol warns against the risk of injury. ! Please note This symbol warns against the risk of material losses and environmental pollution. Note Details identified by the word "Note" contain additional information. Target group These instructions are exclusively designed for qualified personnel. & Work on gas equipment must only be carried out by a qualified gas fitter. & Work on electrical equipment must only be carried out by a qualified electrician. & The system must be commissioned by the system installer or a qualified person authorised by the installer. & the Code of Practice of relevant trade associations, & all current safety regulations as defined by DIN, EN, DVGW, TRGI, TRF, VDE and all locally applicable standards. If you smell gas Danger Escaping gas can lead to explosions which may result in serious injury. & Never smoke. Prevent naked flames and sparks. Never switch lights or electrical appliances ON or OFF. & Close the gas shut‐off valve. & Open windows and doors. & Remove all people from the danger zone. & Notify your gas or electricity supplier from outside the building. & Shut off the electricity supply to the building from a safe place (outside the building). Regulations 2 Danger Flue gas can lead to life‐threatening poisoning. & Shut down the heating system. & Ventilate the boiler room. & Close all doors leading to the living space. 5692 619 GB If you smell flue gas Observe the following when working on this system & all legal instructions regarding the prevention of accidents, & all legal instructions regarding environmental protection, Safety instructions Safety instructions (cont.) Working on the system & When using gas as fuel, also close the main gas shut‐off valve and safeguard against unauthorised reopening. & Isolate the system from the power supply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains isolator. & Safeguard the system against unauthorised reconnection. Please note Electronic modules can be damaged by electro‐static discharges. Touch earthed objects, such as heating or water pipes, to discharge static loads. ! Please note Repairing components which fulfil a safety function can compromise the safe operation of your heating system. Replace faulty components only with original Viessmann spare parts. Ancillary components, spare and wearing parts ! Please note Spare and wearing parts which have not been tested together with the heating system can compromise its function. Installing non‐authorised components and non‐approved modifications/conversion can compromise safety and may invalidate our warranty. For replacements, use only original spare parts from Viessmann or those which are approved by Viessmann. 5692 619 GB ! Repair work 3 Index Index Initial start-up, inspection, maintenance Steps – initial start-up, inspection and maintenance .................................... Further details regarding the individual steps .............................................. 5 7 Coding Code 1........................................................................................................ 39 Code 2........................................................................................................ 41 Resetting codes to the delivered condition .................................................. 60 Service scans Service level summary ................................................................................ Temperatures, boiler coding card and brief scans ....................................... Checking outputs (relay test) ...................................................................... Scanning operating conditions and sensors ................................................ 61 62 65 67 Troubleshooting Fault display ............................................................................................... Calling up fault codes from the fault memory (fault history) .......................... Fault codes................................................................................................. Repairs ...................................................................................................... 69 71 71 79 Function description Constant temperature control unit ............................................................... Weather–compensated control unit ............................................................. Extensions for external connections ............................................................ Control functions ........................................................................................ Remote control DIP switch .......................................................................... 90 92 95 99 105 Designs Connection and wiring diagram – internal connections ................................ 106 Connection and wiring diagram – external connections ............................... 108 Parts lists .................................................................................................. 110 Commissioning/service reports ............................................................... 117 Certificates Declaration of conformity ............................................................................ 119 Manufacturer's certificate according to the 1st BImSchV [Germany]............. 120 Keyword index .......................................................................................... 121 4 5692 619 GB Specification ............................................................................................. 118 Initial start-up, inspection, maintenance Steps – initial start-up, inspection and maintenance For further information regarding individual steps, see the pages indicated. ! • • • • • • • Commissioning steps ! • Inspection steps 5692 619 GB • • • • • • Page ! • 1. Filling the heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2. Venting the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 3. Venting the heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 4. Filling the siphon with water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 5. Checking all connections on the primary and DHW side for leaks 6. Checking the power supply connection • • • Maintenance steps • • • • • • • 7. Setting the time and date (if required) – only for weather-compensated control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 8. Language selection (if required) - only for weathercompensated control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 9. Pivot down the control unit for commissioning and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 10. Checking the gas type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 11. Gas type conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 12. Function sequence and possible faults . . . . . . . . . . . . . . . . . . . . . . . 12 13. Checking the static and supply pressure . . . . . . . . . . . . . . . . . . . . 13 14. Setting the max. output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 15. Checking the balanced flue system soundness (annular gap check) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 • • 16. Removing the burner and checking the burner gasket (replace gasket every two years) . . . . . . . . . . . . . . . . . . . . . . 17 • • • • 17. Checking the burner gauze assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 • • 19. Cleaning the combustion chamber/heating surfaces and fitting the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 18. Checking and adjusting the ignition and ionisation electrodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 5 Initial start-up, inspection, maintenance Steps – initial start-up, inspection and . . . (cont.) ! Commissioning steps ! • • Inspection steps Page ! • 20. Checking the condensate drain and cleaning the siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 • • 21. Checking the neutralising system (if installed) • • 23. Cleaning the DHW cylinder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 22. Testing the anode earth current with an anode tester . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 24. Checking and replacing the magnesium anode (if required) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 • • • 25. Returning the DHW cylinder to use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 • • • • • • • • • • 27. Checking the function of all safety valves • • • • • • • • • 30. Flue gas emissions test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 26. Checking the diaphragm expansion vessel and system pressure 28. Checking the tightness of electrical connections 29. Checking all gas equipment for soundness at operating pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 31. Checking the ionisation current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 32. Checking the LPG external safety valve (if required) • • 33. Matching the control unit to the heating system . . . . . . 27 • 35. Connecting the control unit to the LON system (only for weather-compensated control units) . . . . . . . . . . 35 • 36. Implementing a user check (in conjunction with the LON system with a weather-compensated control unit) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 • 37. Instructing the system user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 34. Adjusting the heating curves (only for control units for weather-compensated operation) . . . . . . . . . . . . . . . . . 32 • 6 Maintenance steps 38. Scanning and resetting the "maintenance" display 38 5692 619 GB Initial start-up, inspection, maintenance Further details regarding the individual steps Filling the heating system ! Please note Unsuitable fill water increases the level of deposits and corrosion and may lead to boiler damage. & Thoroughly flush the entire heating system prior to filling with water. & Only use fill water of potable quality. & Fill water with a water hardness in excess of 3.58 mmol/l must be softened, e.g. with the small softening system for heating water (see the Vitoset pricelist). & An anti-freeze additive suitable for heating systems can be mixed with the fill water. 1. Check the inlet pressure of the diaphragm expansion vessel. 2. Close the gas shut-off valve. 3. Fill the heating system at the fill valve in the heating return (on the connection set or on site). Minimum system pressure > 0.8 bar). Note If the control unit has not been switched ON prior to filling the system, then the servomotor of the changeover valve will still be in its centre position, and the system will be completely filled. 4. If the control unit had already been switched ON before filling began: Start the control unit and activate the fill program via coding "2F:2". Note To call up coding level 1 and for setting the coding address, see page 39. For function and details of the fill program, see page 100. Whilst the fill program runs, the display shows "bF" (Vitotronic 100) or "Filling" (Vitotronic 200). 5. Close the boiler fill & drain valve. 5692 619 GB 6. Set code "2F:0". 7 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Venting the boiler 1. Close the shut-off valves on the primary side. 2. Connect the drain hose on valve A with a drain outlet. 3. Open valve A and fill valve in the heating return and vent at mains pressure, until no sound of escaping air can be heard. 4. Close valve A and fill valve in the heating return and open the primary shut-off valves. Venting the heating system 1. Close the gas shut-off valve and switch ON the control unit. 2. Activate the venting program via code "2F:1". Note To call up coding level 1 and for setting the coding address, see page 39. For the function and sequence of the venting program, see page 100. Whilst the venting program runs, the display shows "EL" (Vitotronic 100) or "Venting" (Vitotronic 200). 5692 619 GB 3. Check the system pressure. 8 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Filling the siphon with water 1. Remove the retaining clip and siphon A. 2. Fill the siphon with water. 3. Fit the siphon A and secure with the retaining clip. Setting the time and date (if required) – only for weathercompensated control units Note During commissioning, or after a prolonged time out of use, it may be necessary to reset the time and date, if the time flashes in the display. Press the following keys: 3. a/b for the current date. 1. a/b for the current time. 4. d 2. d to confirm. to confirm; "Date" is displayed. Language selection (if required) - only for weather-compensated control units Press the following keys: 3. c Press again. 1. c "Select a heating circuit" will be displayed. 4. b for the required language. 5. d to confirm. 5692 619 GB 2. d to confirm; wait approx. 4 s. 9 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Pivot down the control unit for commissioning and maintenance work A Control unit B Closures C Flap D Retaining frame 1. Open flap C. 3. Release the side screws and pivot control unit A down with its retaining frame D. 5692 619 GB 2. Release side closures B and pivot control unit A forward. 10 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Checking the gas type Note In the delivered condition, the Vitodens 333 is set up for natural gas E. The boiler can be operated in the Wobbe index range 12.0 to 16.1 kWh/m 3 (43.2 to 58.0 MJ/m 3 ). 1. Determine the gas type and Wobbe index (Wo) by asking your local mains gas or LPG supplier. 2. Compare the gas category (type) and group with the details on the burner label. 4. When converting to LPG (only 26 kW) Adjust coding address "1E:1" (see page 39). 5. Record the gas type in the service report on page 117. 3. The burner must be converted according to the details provided by the mains gas or the LPG supplier to match the fuel provided, if these details do not match. Conversion kit installation instructions. Wobbe index range after conversion: & Natural gas LL 10.0 to 13.1 kWh/m 3 (36.0 to 47.2 MJ/m 3 ) & LPG P (only 26 kW) 21.4 to 22.5 kWh/m 3 (76.9 to 81.0 MJ/m 3 ) Gas type conversion 5692 619 GB Gas restrictor installation instructions 11 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Gas restrictor allocation Rated output Gas restrictor, internal 7 Gas & Natural gas E & Natural gas LL & LPG P kW mm mm mm 13 26 4.8 5.3 — 5.95 6.73 4.4 Function sequence and possible faults Display screen No Measures Increase set value and ensure heat is drawn off No after approx. 51 s fault F5/F9 Check fan cables and plugs No after approx. 51 s fault E6/F5 Check fan cables and plugs, check fan No Fault F4 Check ignition module (control voltage 230 V across plugs "X2.1" and "X2.2") Control unit issues heat demand Yes Fan starts Yes Differential pressure sensor enables start (0.75 V across terminals "X8.5 "and "X8.6") Yes 5692 619 GB Ignition 12 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Yes Gas combination valve opens No Fault F4 Check the gas combination valve (control voltage 230 V); check the gas supply pressure No Fault F4 Check ionisation current, check electrode adjustment and gas pipe for airlocks. Stops below set boiler water temperature and restarts immediately Check flue gas system soundness (flue gas recirculation), check gas flow pressure Yes Ionisation current builds (higher than 2 µA) Symbol A Yes Burner starts No For further details regarding faults, see page 69. Checking the static and supply pressure Danger CO build-up as a result of incorrect burner setting can have serious health implications. Carry out a CO test prior to, and after, work on gas equipment. 5692 619 GB Operation with LPG (only 26 kW) Flush the LPG tank twice during commissioning/replacement. Thoroughly vent the tank and gas lines after flushing. 13 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) 4. Record the static pressure and record it in the service report on page 117. Set value: max. 57.5 mbar 5. Start up the boiler. Note During commissioning, the boiler can enter a fault state because of airlocks in the gas pipe. After approx. 5 s press "E" to reset the burner. 6. Check the supply (flow) pressure. 1. Close the gas shut-off valve. 2. Release screw A inside test nipple "PE" on the gas combination valve, but do not remove it; then connect the pressure gauge. 3. Open the gas shut-off valve. Set value: & Natural gas: 20 mbar & LPG (only 26 kW): 50 mbar Note Use suitable test equipment, with a resolution of at least 0.1 mbar, to measure the supply pressure. 7. Record the actual value in the service report on page 117. Take the action shown in the table. Supply (flow) pressure for natural gas below 17.4 mbar 5692 619 GB 17.4 to 57.5 mbar in excess of 57.5 mbar Supply (flow) Measures pressure for LPG (only 26 kW) below 42.5 mbar Never start up. Notify your mains gas or LPG supplier. 42.5 to 57.5 mbar Start up the boiler. in excess of Install a separate gas governor down57.5 mbar stream of the system and regulate the inlet pressure to 20 mbar for natural gas or 50 mbar for LPG. Notify your mains gas or LPG supplier. 14 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) 8. Shut down the boiler, close the gas shut-off valve, remove the pressure gauge and close test nipple A with the screw. 9. Open the gas shut-off valve and start the boiler. Danger Gas escaping from the test nipple leads to a risk of explosion. Check test nipple A for soundness. Setting the max. output Note The maximum output can be limited for heating operation. You can limit the output via the modulation range. 1. Start up the boiler. 2. Press K + F simultaneously: "100" flashes (corresponds to 100% of rated output) and "A" is displayed. On weather-compensated control units, the display additionally shows "Max. output". a/b for the required value in % of rated output as max. output. d to confirm. 3. Record the setting for max. output on the additional type plate supplied with the "technical documentation". Affix the type plate next to the type plate on top of the boiler. 5692 619 GB Checking the balanced flue system soundness (annular gap check) For balanced flue systems tested together with the wall mounted gas fired boiler, some authorities waive the requirement for a soundness test (pressure test) during commissioning by the flue gas inspector. 15 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) We recommend that your heating engineer carries out a simple leak test during the commissioning of your system. For this it would be sufficient to check the CO 2 concentration in the combustion air at the annular gap of the balanced flue pipe. The flue pipe is deemed to be sound if the CO 2 concentration in the combustion air is no higher than 0.2 % or the O 2 concentration is at least 20.6 %. If actual CO2 values are higher or O 2 values are lower, then pressure check the flue pipe at a static pressure of 200 Pa. 5692 619 GB A Combustion air aperture (ventilation air) 16 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Removing the burner and checking the burner gasket (replace gasket every two years) A B C D E Nuts Differential pressure sensor Burner gasket Gas supply pipe Gas train 1. Switch OFF the control unit ON/ OFF switch and the power supply. 5692 619 GB 2. Close the gas shut-off valve and safeguard against reopening. 3. Pull off electrical cables from fan motor H, differential pressure sensor B, gas valve E, ionisation electrode F, ignition unit K and earth stud G. F G H K Ionisation electrode Earth stud Fan motor Ignition device 4. Release gas supply pipe fitting D. 5. Release four nuts A and remove the burner. ! Please note Prevent damage to the wire mesh. Never rest the burner on the gauze assembly. 17 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) 6. Check the burner gasket C for damage. Generally replace the burner gasket every 2 years. Checking the burner gauze assembly A Torx screws B Burner gauze C Burner gauze gasket D Ionisation electrode E Ignition electrodes 1. Remove electrodes D and E. 4. Insert a new burner gauze assembly with a new gasket and secure it with six Torx screws. 2. Release the six Torx screws A and remove the burner gauze assembly B. 3. Remove the old burner gauze gasket C. 18 Note Torque: 3.5 Nm 5692 619 GB Replace the burner gauze assembly if the wire mesh is damaged. Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Checking and adjusting the ignition and ionisation electrodes A Ignition electrodes B Ionisation electrode C Gasket 1. Check electrodes A and B for wear and contamination. 3. Check clearances. If the gaps are not as specified or the electrodes are damaged, replace and align the electrodes together with new gaskets C. Tighten the electrode fixing screws with 2 Nm. 2. Clean the electrodes with a small brush (not with a wire brush) or emery paper. Please note Never damage the wire mesh. 5692 619 GB ! 19 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Cleaning the combustion chamber/heating surfaces and fitting the burner 2. Apply a solvent/potassium-free cleaning agent if residues remain: & Remove soot deposits with alkaline cleaning agents with additional surfactants (e.g. Fauch 600). & Remove coatings and surface discolouration (yellow-brown) with slightly acidic, chloride-free cleaning agents based on phosphoric acid (e.g. Antox 75 E). & Thoroughly flush with water. 1. If required, clean the combustion chamber and heating surfaces A with a brush or flush with water. ! Please note Scratches on parts which are in contact with flue gases can lead to corrosion. Only use plastic brushes and NOT wire brushes. Note Fauch 600 and Antox 75 E are supplied by Hebro Chemie GmbH Rostocker Straße 40 D 41199 Mönchengladbach 3. Install the burner and torque nuts diagonally with 4 Nm. 4. Secure the gas supply pipe with a new gasket. 5. Check the gas connections for soundness. Danger Escaping gas leads to a risk of explosions. Check all fittings for soundness. 5692 619 GB 6. Connect the electrical cables/leads to each corresponding component. 20 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Checking the condensate drain and cleaning the siphon 1. Check that the condensate can freely drain at siphon A. 2. Remove the retaining clip and the siphon. 3. Clean the siphon. 4. Fit the siphon and secure with the retaining clip. Testing the anode earth current with an anode tester Note We recommend that the magnesium anode function is checked annually. This function test can be carried out without interrupting operation by measuring the earth current with an anode tester. 1. Remove cover A. 2. Pull earth cable B from push-on tab C. 5692 619 GB 3. Connect the tester (up to 5 mA) in series between push-on tab C and earth cable B. & The anode is OK if the indicated current is > 0.3 mA. & Visually inspect the anode if the current measures < 0.3 mA or if there is no current at all (see page 22). A Cover B Earth cable C Push-on tab 21 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Cleaning the DHW cylinder Note DIN 1988 requires a visual inspection and (if necessary) cleaning every two years after the cylinder has been taken into use and thereafter according to requirements. 4. Remove loose deposits with a high pressure cleaner. ! Please note Only use plastic utensils for cleaning the inside of the cylinder. 5. Use a chemical cleaning agent to remove hard deposits that cannot be removed by a high pressure cleaner. 1. Drain the DHW cylinder. 2. Remove flange lid A. 3. Disconnect the cylinder from the pipework to prevent contaminants entering the pipe system. ! Please note Never use hydrochloric cleaning agents. 6. Thoroughly flush the DHW cylinder after cleaning. Checking and replacing the magnesium anode (if required) 5692 619 GB Check the magnesium anode. We recommend you change the magnesium anode if it has been reduced down to 10 to 15 mm Ø. 22 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Returning the DHW cylinder to use A Flange lid B Gasket C Earth cable D Push-on tab 1. Reconnect the DHW cylinder to the pipework. 3. Fit the flange lid and tighten the screws with a maximum torque of 25 Nm. 2. Insert new gasket B underneath the flange lid A. 4. Push earth cable C onto push-on tab D. 5. Fill the cylinder with potable water. Checking all gas equipment for soundness at operating pressure 5692 619 GB Danger Escaping gas leads to a risk of explosions. Check gas equipment for soundness. 23 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Flue gas emissions test The Vitodens 333 is set up in the factory for natural gas E and can, with the aid of a conversion kit, be converted to natural gas LL or LPG P (only 26 kW). During commissioning or maintenance, check the CO 2 level at the flue outlet. Note The MatriX burner of the Vitodens 333 is preset for the entire gas group. Therefore, the burner requires no further setting or adjustment. Subject to the Wobbe index, the CO 2 content fluctuates between & 6.6 to 10.0% for natural gas E & 7.0 to 10.0% for natural gas LL & 8.5 to 10.5% for LPG P (only 26 kW) Compare the actual CO 2 value with the above CO 2 value ranges for the individual gas groups (check the gas group with your mains gas or LPG supplier). If the actual CO 2 value deviates by more than 1% for natural gas or 0.5% for LPG (only 26 kW), proceed as follows: & Check that the correct gas restrictor has been installed. & Check the balanced flue system for soundness, see page 16. Maintain limits to EN 483 and EN 297 (CO content < 1000 ppm). 2. Open the gas shut-off valve, start the boiler and create a heat demand. 1. Connect a flue gas analyser at the flue gas port A on the flue outlet. 24 4. Check the CO 2 content. If the value lies outside the above range, take the measures listed on page 24. 5692 619 GB 3. Select the lower rated output. Constant temperature control unit: Press K + d simultaneously: "1" is shown. Weather–compensated control unit: Press K + d simultaneously: "Relay test" and then "Base load" is shown. Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) 5. Record the actual value on page 117 of the commissioning/ service report. 7. Check the CO 2 content. If the value lies outside the above range, take the measures listed on page 24. 6. Select the upper rated output. Constant temperature control unit: Press K + d simultaneously: "1" is shown. Press a: "2" is shown. Weather–compensated control unit: Press K + d simultaneously: "Relay test" is shown. Press a: "Full load" is shown. 8. After testing, press d. 5692 619 GB 9. Record the actual value on page 117 of the commissioning/ service report. 25 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Checking the ionisation current 2. Adjusting the upper output: Constant temperature control unit: Press K + d simultaneously: "1" is shown. Press a: "2" is shown. Weather–compensated control unit: Press K + d simultaneously: "Relay test" is shown in the display. Press a: "Full load" is shown in the display. A Adaptor line (accessories) 1. Connect the test instrument according to the adjacent diagram. 3. Ionisation current when the flame is first established: min. 2 µA Steps to take if the ionisation current < 2 µA: & Check the electrode gap, see page 19. & Check the control unit power supply. 5692 619 GB 4. Press d. Operation with the upper rated output is terminated. 26 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) 5. Record the actual value in the service report on page 117. Matching the control unit to the heating system Note The control unit must be matched to the system equipment. Various system components are recognised automatically by the control unit and the relevant codes adjusted automatically. & For the selection of an appropriate design, see the following diagrams. & For coding steps, see page 39. System version 1 5692 619 GB One heating circuit without mixer A1 ! Outside temperature sensor (only for control units for weather-compensated operation) or lH Vitotrol 100 (only for constant temperature control units) 27 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Required coding Operation with LPG 1E:1 System version 2 One heating circuit with mixer M2 and a low loss header ! ? sÖ lH aVG Outside temperature sensor Flow temperature sensor Heating circuit pump Power supply (extension kit) KM BUS A B C Low loss header Extension kit for a heating circuit with mixer Maximum temperature thermostat (underfloor heating) 1E:1 00:4 5692 619 GB Required coding Operation with LPG System with only one heating circuit with mixer and DHW heating 28 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) System version 3 One heating circuit without mixer A1 and one heating circuit with mixer M2 ! ? sÖ lH aVG Outside temperature sensor Flow temperature sensor Heating circuit pump Power supply (extension kit) KM BUS A B Maximum temperature thermostat (underfloor heating) Extension kit for a heating circuit with mixer Note The flow rate of the heating circuit without mixer must be at least 30% greater than the flow rate of the heating circuit with mixer. 1E:1 5692 619 GB Required coding Operation with LPG 29 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) System version 4 One heating circuit without mixer A1, one heating circuit with mixer M2 and system separation ! ? sÖ lH aVG Outside temperature sensor Flow temperature sensor Heating circuit pump Power supply (extension kit) KM BUS B C Extension kit for a heating circuit with mixer Maximum temperature thermostat (underfloor heating) Heat exchanger for system separation 1E:1 5692 619 GB Required coding Operation with LPG A 30 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) System version 5 One heating circuit with mixer M2 (with extension kit), one heating circuit with mixer (with the Vitotronic 050) and low loss header ! ? sÖ lH aVG A Outside temperature sensor Flow temperature sensor Heating circuit pump Power supply (extension kit) KM BUS Low loss header B C D Extension kit for a heating circuit with mixer Vitotronic 050 Maximum temperature thermostat (underfloor heating) 1E:1 00:4 5692 619 GB Required coding Operation with LPG System with only one heating circuit with mixer and DHW heating 31 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Adjusting the heating curves (only for control units for weather-compensated operation) The heating curves illustrate the relationship between the outside temperature and the boiler water or the flow temperature. To put it simply: The lower the outside temperature, the higher the boiler water or flow temperature. The room temperature, again, depends on the boiler water or the flow temperature. A Heating curve slope for underfloor heating systems B Heating curve slope for low temperature heating systems (according to the Energy Savings Order [Germany]) 5692 619 GB Settings in the delivered condition: & Slope = 1.4 & Level = 0 32 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Changing slope and level 1. Change the slope with coding address "d3" in code 1 (see page 39). Setting range 2 to 35 (equals slope 0.2 to 3.5). 2. Change the level in coding address "d4" in code 1 (see page 39). Setting range -13 to +40 K. 5692 619 GB A Changing the slope B Changing the level (vertical parallel offset of the heating curve) 33 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Adjusting the set room temperature Standard room temperature Press the following keys: 1. a "1r" flashes. 2. d to select heating circuit A1 (heating circuit without mixer) or 3. a "2r" flashes. 4. d to select heating circuit M2 (heating circuit with mixer) Example 1: Adjustment of the standard room temperature from 20 °C to 26 °C 5692 619 GB A Boiler water temperature or flow temperature in °C B Outside temperature in °C C Set room temperature in °C D Heating circuit pump "OFF" E Heating circuit pump "ON" 5. Adjust the set day temperature with rotary selector "ts". The value will be automatically accepted after approx. 2 s. Accordingly, the heating curve is adjusted along the set room temperature axis, which results in modified start-up/shutdown characteristics of the heating circuit pumps if heating circuit pump logic is active. 34 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Reduced room temperature Press the following keys: 1. a "1r" flashes. 2. d to select heating circuit A1 (heating circuit without mixer) or 3. a "2r" flashes. 4. d to select heating circuit M2 (heating circuit with mixer) 5. E Calling up the set night temperature. Example 2: Adjustment of the reduced room temperature from 5 °C to 14 °C A Boiler water temperature or flow temperature in °C B Outside temperature in °C C Set room temperature in °C D Heating circuit pump "OFF" E Heating circuit pump "ON" 6. a/b Change the value. 7. d Confirm the value. Connecting the control unit to the LON system (only for weather-compensated control units) The LON communication module (accessories) must be plugged in. Installation instructions LON communication module Note The data transfer via the LON system can take 2 to 3 min. Setting up LON user numbers In a LON system, the same number cannot be allocated twice. 5692 619 GB Adjust the user number via coding address "77" (see the following table). 35 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Updating the LON user list Note Only possible if all users are connected and the control unit is programmed to be fault manager (code "79:1"). Press the following keys: 1. L + d simultaneously for approx. 2 s User check initiated (see page 37). 2. e The user list is updated after approx. 2 min. The user check is completed. Single boiler system with Vitotronic 050 and Vitocom 300 Note In each heating system, only one Vitotronic may be programmed as fault manager. Boiler control unit Vitotronic 050 Vitotronic 050 Vitocom User no. 1 Code "77: 1" Control unit is fault manager Set code "79: 1" Send time via LON Code "7b: 1" Transmit outside temperature via LON Set code "97: 2" Fault monitoring LON user code "9C:20" User no. 10 Set code "77: 10" Control unit is not fault manager Code "79: 0" Time received via LON Set code "81: 3" The outside temperature is received via LON Set code "97: 1" Fault monitoring LON user code "9C:20" User no. 11 Set code "77: 11" Control unit is not fault manager Code "79: 0" Time received via LON Set code "81: 3" The outside temperature is received via LON Set code "97: 1" Fault monitoring LON user code "9C:20" User no. 99 36 Control unit is fault manager Time received via LON — 5692 619 GB — Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Implementing a user check (in conjunction with the LON system with a weather-compensated control unit) Communication with the system devices connected to the fault manager is tested with a user check. Preconditions: & The control unit must be programmed as fault manager (code "79:1"). & The LON user number must be programmed in all control units (see page 35). & The fault manager LON user list must be up to date (see page 35). 3. d A Consecutive number in the user list B User number Press the following keys: 1. L + d simultaneously for approx. 2 s The user check has been initiated. 2. a/b Activating a check. "Check" flashes until its completion. The display and all key illuminations for the selected user flash for approx. 60 s. & "Check OK" is displayed during communication between both devices. & "Check not OK" is displayed if there is no communication between both devices; check the LON connection. 4. Repeat points 2 and 3 to check further users. for the required user. 5. L + d simultaneously for approx. 1 s The user check is completed. 5692 619 GB Instructing the system user The system installer must hand the operating instructions to the system user and instruct him/her in the operation of the system. 37 Initial start-up, inspection, maintenance Further details regarding the individual steps (cont.) Scanning and resetting the "maintenance" display The red fault indicator flashes when the limits set via coding addresses "21" and "23" have been reached. As regards the programming unit display: & For a constant temperature control unit: The defaulted hours run or the defaulted interval with clock symbol "u" (subject to setting) & For a weather-compensated control unit: "Maintenance" Note Set code "24:1" and then code "24:0" if maintenance is carried out before maintenance is displayed; the set maintenance parameters for hours run and intervals are then reset to 0. Press the following keys: 1. c 3. d The maintenance scan is active. 2. a/b Scan maintenance messages. The maintenance display will be cleared (for a weather-compensated control unit: "Acknowledge: Yes" re-confirm with d). The red fault display continues to flash. Note An acknowledged maintenance message can be redisplayed by pressing d (approx. 3 s). 1. Reset code "24:1" to "24:0". The red fault indicator extinguishes. Note A new maintenance message will be displayed 7 days later, if coding address "24" is not reset. 38 2. Reset the burner hours run, burner starts and consumption, if required Press the following keys: c Scanning is active (see page 67). a/b for the selected value. e the selected value will be set to "0". a/b for further scans. d Scanning is completed. 5692 619 GB After maintenance has been carried out Coding Code 1 Calling up code 1 Note & On weather-compensated control units, codes are displayed as plain text. & Codes which are irrelevant (due to the system equipment level or the setting of other codes) will not be displayed. & For heating systems with one heating circuit without mixer and one heating circuit with mixer, initially the possible coding addresses "A0" to "d4" are scrolled for the heating circuit without mixer A1 and then those for the heating circuit with mixer M2. Press the following keys: 1. K + L simultaneously for approx. 2s. 2. a/b for the required coding address; the address flashes. 3. d to confirm. 4. a/b for the selected value. 5. d to confirm; the display briefly shows "accepted" (weather-compensated control unit); the address flashes again. 6. a/b for the selection of further addresses. 7. K + L simultaneously for approx. 1 s to terminate code 1. Summary Coding Coding in the delivered condition System designs 00:2 System version 1: 1 heating circuit without mixer A1, with DHW heating Possible change 00:4 5692 619 GB 00:6 System version 2, 5: 1 heating circuit with mixer M2, with DHW heating System version 3, 4: 1 heating circuit without mixer A1 and 1 heating circuit with mixer M2, with DHW heating 39 Coding Code 1 (cont.) Coding in the delivered condition Max. boiler temp. 06:... Maximum limit of the boiler water temperature, defaulted in °C by the boiler coding card Gas type 1E:0 Operation with natural gas Venting/filling 2F:0 Program enabled Possible change 06:20 to 06:127 Maximum limit of the boiler water temperature within the ranges defaulted by the boiler 1E:1 Operation with LPG 2F:1 Ventilation program disabled Filling program enabled 2F:2 User no. 77:1 LON user number (only for weather-compensated control units) 77:2 to 77:99 LON user number, adjustable from 1 to 99: 1 - 4 = Boiler 5 = Cascade 10 - 98 = Vitotronic 050 99 = Vitocom Summer econ. A1/M2 A5:5 With heating circuit logic function (only for weather-compensated control units) Min. flow temp. A1/M2 C5:20 Electronic minimum limit of the flow temperature 20 °C (only for weather-compensated control units) Max. flow temp. A1/M2 C6:75 Electronic maximum limit of the flow temperature 75 °C (only for weather-compensated control units) 40 A5:0 Without heating circuit pump logic function C5:1 to C5:127 Minimum limit adjustable from 1 to 127 °C C6:10 to C6:127 Maximum limit adjustable from 10 to 127 °C 5692 619 GB Note Allocate each number once only. Coding Code 1 (cont.) Coding in the delivered condition Slope A1/M2 d3:14 Heating curve slope = 1.4 (only for weathercompensated control units) Level A1/M2 d4:0 Heating curve slope = 0 (only for weather-compensated control units) Possible change d3:2 to d3:35 Heating curve slope adjustable from 0.2 to 3.5 (see page 32) d4:–13 to d4:40 Heating curve level adjustable from –13 to 40 (see page 32) Code 2 Calling up code 2 Note & On weather-compensated control units, codes are displayed as plain text. & Codes, which are irrelevant (due to the system equipment level or the setting of other codes) will not be displayed. 4. d to confirm; the value flashes. 5. a/b for the selected value. 6. d to confirm; the display briefly shows "accepted" (for weather-compensated control units); the address flashes again. 7. a/b for the selection of further addresses. Press the following keys: 1. L + G simultaneously for approx. 2s. 2. d to confirm. 3. a/b for the required coding address; the address flashes. 8. L + G simultaneously for approx. 1 s to terminate code 2. 5692 619 GB Overall summary The coding addresses are grouped according to the following function areas. The respective function area is shown on the display. 41 Coding Code 2 (cont.) The areas are scanned in the following sequence with a/b: Function area System design Boiler/burner DHW General Heating circuit A1 (heating circuit without mixer) Heating circuit M2 (heating circuit with mixer) Coding addresses 00 06 to 54 56 to 73 76 to 9F A0 to Fb A0 to Fb Note For heating systems with one heating circuit without mixer and one heating circuit with mixer, initially the possible coding addresses "A0" to "Fb" are scrolled for the heating circuit without mixer A1 and then those for the heating circuit with mixer M2. Coding Possible change 00:4 00:6 Boiler/burner 06:... Maximum limit of the boiler water temperature, defaulted in °C by the boiler coding card 1E:0 Operation with natural gas 21:0 No burner maintenance indication 42 06:20 to 06:127 1E:1 21:1 to 21:9999 System version 2, 5: 1 heating circuit with mixer M2, with DHW heating System version 3, 4: 1 heating circuit without mixer A1 and 1 heating circuit with mixer M2, with DHW heating Maximum limit of the boiler water temperature within the ranges defaulted by the boiler Operation with LPG The number of hours to run before the burner should be serviced is adjustable from 1 to 9999 h 5692 619 GB Coding in the delivered condition System designs 00:2 System version 1: 1 heating circuit without mixer A1, with DHW heating Coding Code 2 (cont.) Coding in the delivered condition 23:0 No time interval for burner maintenance 24:0 No "Maintenance" display 25:0 i: No outside temperature sensor or fault monitoring recognised (only for constant temperature control units) No burner interval ignition Without external extension Program disabled 28:0 2E:0 2F:0 30:1 Internal variable speed circulation pump (automatic adjustment) 31:... Set speed of the internal circulation pump when operated as boiler circuit pump in %, defaulted by the boiler coding card Influence of the signal "External blocking" on the circulation pumps: All pumps in control function 28:1 2E:1 2F:1 2F:2 30:0 31:0 to 31:100 32:1 to 32:15 The burner will be forcestarted for 30 s after 5 h With external extension (automatic recognition) Ventilation program enabled Filling program enabled Internal circulation pump without variable speed (e.g. temporarily for service) Set speed adjustable from 0 to 100 % Influence of the signal "External blocking" on the circulation pumps: see the following table 5692 619 GB 32:0 Possible change 23:1 Interval adjustable from 1 to to 24 months 23:24 24:1 "Maintenance" display (the address is automatically set and must be manually reset after a service has been carried out) 25:1 Outside temperature sensor and fault monitoring recognised 43 Coding Code 2 (cont.) Internal circulation pump 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Control funct. Control funct. Control funct. Control funct. Control funct. Control funct. Control funct. Control funct. OFF OFF OFF OFF OFF OFF OFF OFF Heating circuit pump Heating circuit without mixer Control funct. Control funct. Control funct. Control funct. OFF OFF OFF OFF Control funct. Control funct. Control funct. Control funct. OFF OFF OFF OFF Coding in the delivered condition Boiler/burner 34:0 Influence of the signal "External demand" on the circulation pumps: All pumps in control function Coding Internal circulation pump 0 1 2 3 4 5 6 Control funct. Control funct. Control funct. Control funct. Control funct. Control funct. Control funct. 44 Heating circuit pump Heating circuit with mixer Control funct. Control funct. OFF OFF Control funct. Control funct. OFF OFF Control funct. Control funct. OFF OFF Control funct. Control funct. OFF OFF Cylinder primary pump Control funct. OFF Control funct. OFF Control funct. OFF Control funct. OFF Control funct. OFF Control funct. OFF Control funct. OFF Control funct. OFF Possible change 34:1 to 34:23 Heating circuit pump Heating circuit without mixer Control funct. Control funct. Control funct. Control funct. OFF OFF OFF Influence of the signal "External demand" on the circulation pumps: see the following table Heating circuit pump Heating circuit with mixer Control funct. Control funct. OFF OFF Control funct. Control funct. OFF Cylinder primary pump Control funct. OFF Control funct. OFF Control funct. OFF Control funct. 5692 619 GB Coding Coding Code 2 (cont.) Coding Internal circulation pump 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Control funct. OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON Heating circuit pump Heating circuit without mixer OFF Control funct. Control funct. Control funct. Control funct. OFF OFF OFF OFF Control funct. Control funct. Control funct. Control funct. OFF OFF OFF OFF Coding in the delivered condition Boiler/burner 52:0 Without flow temperature sensor for low loss header 54:0 Without solar control unit Heating circuit pump Heating circuit with mixer OFF Control funct. Control funct. OFF OFF Control funct. Control funct. OFF OFF Control funct. Control funct. OFF OFF Control funct. Control funct. OFF OFF Cylinder primary pump OFF Control funct. OFF Control funct. OFF Control funct. OFF Control funct. OFF Control funct. OFF Control funct. OFF Control funct. OFF Control funct. OFF Possible change 52:1 54:1 5692 619 GB 54:2 With flow temperature sensor for low loss header (automatic recognition) With Vitosolic 100 (automatic recognition) With Vitosolic 200 (automatic recognition) 45 Coding Code 2 (cont.) Coding in the delivered condition Domestic hot water 56:0 Set DHW temperature adjustable from 10 to 60 °C Possible change 56:1 Set DHW temperature adjustable from 10 to above 60 °C Note Maximum value subject to boiler coding card Observe the max. permissible DHW temperature Without auxiliary function for DHW heating 58:10 to 58:60 63:0 No default interval for auxiliary function for DHW heating (only for constant temperature control units) 63:1 65:... Information regarding the type of diverter valve; do not adjust. 67:40 With the Vitosolic: third set DHW temperature 40 °C 6C:100 6F:... 46 Set speed of the internal cylinder primary pump 100 % Maximum output for DHW heating in %; defaulted by the boiler coding card 63:2 to 63:14 63:15 65:0 65:1 65:2 65:3 67:0 67:1 to 67:60 6C:0 to 6C:100 6F:0 to 6F:100 Input of a second set DHW value, adjustable from 10 to 60 °C (observe the coding addresses "56" and "63") Auxiliary function for DHW heating, 1 x daily Every 2 days to every 14 days 2 x daily Without diverter valve Viessmann diverter valve Wilo diverter valve Grunfos diverter valve Without third set DHW temperature Third set DHW temperature adjustable from 1 to 60 °C (subject to the setting of coding address "56") Set speed adjustable from 0 to 100 % Max. output during DHW heating adjustable from min. output to 100 % 5692 619 GB 58:0 Coding Code 2 (cont.) Coding in the delivered condition 71:0 DHW circulation pump: "ON" subject to DHW time program (for the Vitotrol 300, separate switching times are possible) (only for weather-compensated control units) 72:0 DHW circulation pump: "ON" in accordance with the DHW time program (only for weathercompensated control units) 73:0 DHW circulation pump: "ON" in accordance with the DHW time program (only for weathercompensated control units) General 76:0 Without LON communication module (only for weather-compensated control units) 77:1 LON user number (only for weather-compensated control units) Possible change 71:1 "OFF" during DHW heating to the first set value 71:2 "ON" during DHW heating to the first set value 72:1 72:2 73:1 to 73:6 73:7 "OFF" during DHW heating to the second set value "ON" during DHW heating to the second set value During the time program 1x/h "ON" for 5 min up to 6x/h "ON" for 5 min Permanently "ON" 76:1 With LON communication module (automatic recognition) 77:2 to 77:99 LON user number, adjustable from 1 to 99: 1 - 4 = Boiler 5 = Cascade 10 - 98 = Vitotronic 050 99 = Vitocom Note Allocate each number once only. 5692 619 GB 79:0 The control unit is not the fault manager (only for weather-compensated control units) 79:1 Control unit is fault manager 47 Coding Code 2 (cont.) Coding in the delivered condition 7b:1 Without LON communication module (only for weather-compensated control units) 7F:1 Detached house (only for weather-compensated control units) Possible change 7b:0 Do not send time via LON 7F:0 80:1 A fault message is dis80:0 played, providing a fault 80:2 is active for at least 5 s to 80:199 81:1 Automatic summer/winter time changeover 81:0 81:2 88:0 81:3 88:1 90:1 to 90:199 Fast (low values) or slow (high values) matching of the flow temperature, subject to set value when the outside temperature changes; 1 step = 10 min 5692 619 GB 8A:175 90:128 Temperature displayed in °C (Celsius) Do not adjust Time constant for calculating the adjusted outside temperature 21.3 h Apartment block As option, separate adjustment of holiday program and time program for DHW heating Immediate fault message The minimum fault duration before a fault message is issued is adjustable from 10 s to 995 s; 1 step = 5 s Manual summer/winter time changeover Use of the radio clock receiver (automatic recognition) Accept time via LON Temperature displayed in °F (Fahrenheit) 48 Coding Code 2 (cont.) 5692 619 GB Coding in the delivered condition Possible change 91:0 No external heating pro- 91:1 The external heating program changeover via gram changeover affects external extension (only the heating circuit without for weather-compenmixer sated control units) 91:2 The external heating program changeover affects the heating circuit with mixer 91:3 The external heating program changeover affects the heating circuit without mixer and the heating circuit with mixer 95:0 Without Vitocom 100 95:1 With Vitocom 100 comcommunication intermunication interface face (automatic recognition) 97:1 The outside temperature 97:0 The outside temperais accepted by the LON ture of the sensor conBUS nected to the control unit is utilised internally 97:2 The outside temperature (only for weather-comof the sensor connected pensated control units) to the control unit will be utilised internally and is transmitted via the LON BUS to any connected Vitotronic 050. System number adjusta98:1 98:1 Viessmann system ble from 1 to 5 number (in conjunction to 98:5 with monitoring of several systems via Vitocom 300) Minimum set boiler water 9b:1 9b:0 Minimum set boiler temperature adjustable to water temperature for from 1 to 127 °C 9b:127 external demand 49 Coding Code 2 (cont.) Possible change 9C:0 No monitoring 9C:5 The time is adjustable to from 5 to 60 min 9C:60 9F:0 to 9F:40 Differential temperature adjustable from 0 to 40 K A0:1 With Vitotrol 200 (automatic recognition) With Vitotrol 300 (automatic recognition) A0:2 5692 619 GB Coding in the delivered condition 9C:20 Monitoring LON users. If a user fails to respond, the values defaulted inside the control unit will be used after 20 min. Only then will a fault message be issued (only for weather-compensated control units) 9F:8 Differential temperature 8 K; only in conjunction with the mixer circuit (only for weather-compensated control units) Heating circuit A1/M2 A0:0 Without remote control (only for weather-compensated control units) 50 Coding Code 2 (cont.) Coding in the delivered condition A3:2 Outside temperature below 1 °C: Heating circuit pump "ON" Outside temperature above 3 °C: Heating circuit pump "OFF" 5692 619 GB ! Parameters Address A3:... -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 to 15 Possible change A3:–9 Heating circuit pump to "ON/OFF" (see the folA3:15 lowing table) Please note When selecting a value below 1 °C there is a risk of pipes outside the thermal envelope of the house being damaged by frost. The standby mode, in particular, should be taken into consideration, e.g. during holidays. Heating circuit pump "ON" -10 °C -9 °C -8 °C -7 °C -6 °C -5 °C -4 °C -3 °C -2 °C -1 °C 0 °C 1 °C to 14 °C "OFF" -8 °C -7 °C -6 °C -5 °C -4 °C -3 °C -2 °C -1 °C 0 °C 1 °C 2 °C 3 °C 16 °C 51 Coding Code 2 (cont.) Coding in the delivered condition Heating circuit A1/M2 A4:0 With frost protection (only for weather-compensated control units) Possible change A4:1 No frost protection; this setting is only possible if code "A3:-9" has been selected. Note Observe the note for code "A3". A5:5 With heating circuit pump logic function (economy circuit): Heating circuit pump "OFF" when the outside temperature (AT) is 1 K higher than set room temperature (RT Set ) AT > RTSet + 1 K (only for weather-compensated control units) A5:1 to A5:15 Without heating circuit pump logic function With heating circuit pump logic function: Heating circuit pump "OFF" (see the following table) With heating circuit pump logic function: Heating circuit pump "OFF" AT > RTSet + 5 K AT > RTSet + 4 K AT > RTSet + 3 K AT > RTSet + 2 K AT > RTSet + 1 K AT > RTSet AT > RTSet -v1 K AT > RTSet - 9 K 5692 619 GB Parameter address A5:... 1 2 3 4 5 6 7 to 15 A5:0 52 Coding Code 2 (cont.) Coding in the delivered condition Heating circuit A1/M2 A6:36 Extended economy function disabled (only for weather-compensated control units) Possible change A6:5 to A6:35 A7:0 Without mixer economy A7:1 function (only for weather-compensated control units) A8:1 Heating circuit with mixer M2 creates a demand for the internal circulation pump (only for weather-compensated control units) 5692 619 GB A8:0 Extended economy function enabled, i.e. the burner and heating circuit pump will be switched OFF and the mixer will be closed at a variable value, which is adjustable between 5 and 35 °C plus 1 °C. This value is based on the adjusted outside temperature, comprising the actual outside temperature and a time constant, which takes the cooling down of an average building into consideration. With mixer economy function (extended heating circuit pump logic): Heating circuit pump also "OFF": If a mixer has been closed for longer than 20 min. Heating pump "ON": & If the mixer changes to control mode & After cylinder heating (for 20 min) & If there is a risk of frost Heating circuit M2 creates no demand for the internal circulation pump 53 Coding Code 2 (cont.) Possible change A9:0 Without pump idle period A9:1 With pump idle period, to adjustable from 1 to 15 A9:15 b0:1 b0:2 b0:3 b2:8 b5:0 54 With remote control unit and for the heating circuit, heating with room temperature hook-up must be encoded: Room influence factor 8 (only for weather-compensated control units; change the coding only for the heating circuit with mixer M2) With remote control: No room temperature-dependent heating circuit pump logic function (only for weather-compensated control units; change the coding only for the heating circuit with mixer M2) b2:0 b2:1 to b2:64 b5:1 to b5:8 Heating mode: weathercompensated Reduced mode: with room temperature hookup Heating mode: with room temperature hook-up Reduced mode: weathercompensated Heating mode/reduced mode: with room temperature hook-up Without room influence Room influence factor adjustable from 1 to 64 Heating circuit pump logic function, see the following table: 5692 619 GB Coding in the delivered condition A9:7 With pump idle period: Heating circuit pump "OFF" when the set value changes through a change in operating mode or through a change in the set room temperature (only for weather-compensated control units) b0:0 With remote control: Heating mode/reduced mode: weather-compensated (only for weather-compensated control units; change the coding only for the heating circuit with mixer M2) Coding Code 2 (cont.) Parameter address b5:... 1 2 3 4 5 6 7 8 With heating circuit pump logic function: Heating circuit pump "OFF" Heating circuit pump "ON" RTActual > RT Set + 5 K RTActual < RT Set + 4 K RTActual > RT Set + 4 K RTActual < RT Set + 3 K RTActual < RT Set + 2 K RTActual > RT Set + 3 K RTActual < RT Set + 1 K RTActual > RT Set + 2 K RTActual < RT Set RTActual > RT Set + 1 K RTActual > RT Set RTActual < RT Set - 1 K RTActual < RT Set - 2 K RTActual > RT Set - 1 K RTActual < RT Set - 3 K RTActual > RT Set - 2 K Possible change C5:1 to C5:127 Minimum limit adjustable from 1 to 127 °C C6:10 to C6:127 Maximum limit adjustable from 10 to 127 °C d3:2 to d3:35 Heating curve slope adjustable from 0.2 to 3.5 (see page 32) d4:–13 to d4:40 d5:1 Heating curve level adjustable from –13 to 40 (see page 32) The external heating program changeover changes the heating program to "Constant central heating with standard room temperature" 5692 619 GB Coding in the delivered condition Heating circuit A1/M2 C5:20 Electronic minimum limit of the flow temperature 20 °C (only for weather-compensated control units) C6:74 Electronic maximum limit of the flow temperature 74 °C (only for weather-compensated control units) d3:14 Heating curve slope = 1.4 (only for weathercompensated control units) d4:0 Heating curve slope = 0 (only for weather-compensated control units) d5:0 The external heating program changeover changes the heating program to "Constant operation with reduced room temperature" (only for weather-compensated control units) 55 Coding Code 2 (cont.) Possible change E1:0 Set day temperature adjustable from 3 to 23 °C E1:2 Set day temperature adjustable from 17 to 37 °C E2:0 to E2:49 E2:51 to E2:99 E5:1 Display correction –5 K to display correction -0.1 K Display correction +0.1 K to display correction +4.9 K With external variable speed heating circuit pump (automatic recognition) E6:0 to E6:100 Maximum speed adjustable from 0 to 100 % E7:0 to E7:100 Minimum speed adjustable from 0 to 100 % of max. speed E8:0 Speed subject to the setting in coding address "E7" 5692 619 GB Coding in the delivered condition E1:1 With remote control: The set day temperature is adjustable at the remote control unit from 10 to 30 °C (only for weather-compensated control units) E2:50 With remote control: No display correction for the actual room temperature (only for weather-compensated control units) E5:0 Without variable speed external heating circuit pump (only for weathercompensated control units) E6:100 Maximum speed of the external variable speed heating circuit pump: 100 % of the speed in standard mode (only for weather-compensated control units) E7:30 Minimum speed of the external variable speed heating circuit pump: 30 % of the maximum speed (only for weather-compensated control units) E8:1 Minimum speed in operation with reduced room temperature subject to the setting of coding address "E9" (only for weather-compensated control units) 56 Coding Code 2 (cont.) Coding in the delivered condition E9:45 Speed of the external variable speed heating circuit pump: 45 % of the maximum speed in reduced temperature mode (only for weathercompensated control units) F2:8 Time limit for party mode 8 h or external heating program changeover via the keyboard (only for weather-compensated control units) Possible change E9:0 Speed adjustable from 0 to to 100 % of maximum E9:100 speed during operation with reduced room temperature F2:0 F2:1 to F2:12 No time limit for party mode * 1 Time limit adjustable from 1 to 12 h* 1 *1 F5:12 F6:25 5692 619 GB F7:25 Run-on time of the internal circulation pump in heating mode (only for constant temperature control units) In the "DHW only" operating mode, the internal circulation pump is permanently ON (only for weather-compensated control units) F5:0 In the "Standby" operating mode, the internal circulation pump is permanently ON (only for constant temperature control units) F7:0 F5:1 to F5:20 F6:0 F6:1 to F6:24 F7:1 to F7:24 No run-on time of the internal circulation pump Run-on time of the internal circulation pump adjustable from 1 to 20 min In the "DHW only" operating mode, the internal circulation pump is permanently OFF In the "DHW only" operating mode, the internal circulation pump will be started 1 to 24 times per day for 10 min respectively. In "Standby mode", the internal circulation pump is permanently OFF In the "Standby" mode, the internal circulation pump in operating mode will be started 1 to 24 times per day for 10 min respectively. mode ends automatically in the "Heating and DHW" program, when the system changes over to operation with standard room temperature. *1 Party 57 Coding Code 2 (cont.) Possible change F8:+10 Temperature limit adjusto table from F8:–60 +10 to -60 °C F8:–61 Function disabled F9:+10 to F9:–60 Temperature limit adjustable from +10 to -60 °C FA:0 to FA:50 Temperature rise adjustable from 0 to 50% Fb:0 to Fb:150 Duration adjustable from 0 to 300 min; 1 step ≙ 2 min) 5692 619 GB Coding in the delivered condition F8:–5 Temperature limit for terminating the reduced mode -5 ºC, see example on page 103. Observe the setting of coding address "A3". (only for weather-compensated control units) F9:–14 Temperature limit for raising the reduced set room temp. -14 ºC, see example on page 103 (only for weather-compensated control units) FA:20 Raising the set boiler water temperature or the set flow temperature when changing from operation with reduced room temperature to operation with standard room temperature by 20 %. See example on page 104 (only for weather-compensated control units). Fb:30 Duration for raising the set boiler water temperature or the set flow temperature (see coding address "FA") 60 min. See example on page 104 (only for weather-compensated control units). 58 Coding Code 2 (cont.) Coding in the delivered condition Heating circuit M2 F1:0 Screed drying function disabled (only for weather-compensated control units) Possible change F1:1 to F1:5 Screed drying function adjustable in accordance with five optional temperature/time profiles (see page 101) Note Observe the screed supplier's instructions. 5692 619 GB F1:6 to F1:15 Observe DIN 4725–2. The report to be provided by the heating contractor must contain the following heat-up details: & Heat-up data with respective flow temperatures & Max. flow temperature achieved & Operating condition and outside temperature during handover The function continues after a power failure or after the control unit has been switched OFF. Heating program "Heating and DHW" will be started after the screed function has been terminated or if the address is manually set to 0. Constant flow temperature 20 °C 59 Coding Resetting codes to the delivered condition Press the following keys: 3. d to confirm or 1. L + G simultaneously for approx. 2s 4. a/b to select "Basic setting? No". "Basic settings? Yes" is displayed. 5692 619 GB 2. e 60 Service scans Service level summary Function Temperatures, boiler coding card, brief scans Relay test 5692 619 GB Max. output (heating mode) Operating conditions and sensors Maintenance scan Key combination K and G simultaneously for approx. 2 s K and d simultaneously for approx. 2 s K and F simultaneously for approx. 2 s Press c Exit Press d Page 62 Press d 66 Press d 15 Press d 67 c (if "Maintenance" Press d flashes) Adjusting the display con- d and a simultaneously; – trast the display darkens d and b simultaneously; – the display becomes lighter Calling up acknowledged d for approx. 3 s fault messages Fault history G and d simultaneously Press d for approx. 2 s User check (in conjuncL and d simultaneously Press L tion with LON system) for approx. 2 s and d simultaneously F and E Emissions test function Weather–compensated or O and "S" control unit: F simultaF and E simultaneously for neously for approx. 2 s Constant temperature con- approx. 1 s, alternatively trol unit: will be seO and F simultalected autoneously for approx. 2 s matically after 30 min Coding level 1 K and L simultaneously K and L for approx. 2 s simultaneously for approx. 1 s Coding level 2 L and G simultaneously L and G for approx. 2 s simultaneously for approx. 1 s 38 – – 70 71 37 – 39 41 61 Service scans Service level summary (cont.) Function Resetting codes to the delivered condition Key combination Exit L and G simultaneously – for approx. 2 s; press e Page 60 Temperatures, boiler coding card and brief scans Constant temperature control unit Press the following keys: 2. a/b for the required scan. 1. K + G simultaneously for approx. 2 s 3. d End scan. 0 1 E 3 A 62 0 Software version Solar control unit 0: w/o solar control unit 0: w/o external demand 1: external demand 0 0 System deSoftware version Software signs 1 to 6 Control unit version Display in Programaccordance ming unit with the system equipment level Software version Software 0 Burner control unit version External extension 0: w/o external extension 0: w/o exExternal 0 to 10 V hook-up ternal Display in % blocking 0: w/o external hook-up 1: external blocking 0 Set boiler water temperature 0 Highest demand temperature 5692 619 GB The following values can be scanned, subject to the actual equipment level: Display screen Brief scan Service scans Temperatures, boiler coding card and brief . . . (cont.) Display screen Brief scan 4 0 5 b C c 0 0 0 0 d 0 Burner control unit type Boiler type 0 Set cylinder temperature 0 Max. output in % Boiler coding card (hexadecimal) Boiler Burner control unit version version 0 0 Variable Software speed version pump variable 0 w/o speed pump 1 Wilo 0: w/o vari2 Grundfos able speed pump 5692 619 GB Weather–compensated control unit Press the following keys: 2. a/b for the required scan. 1. K + G simultaneously for approx. 2 s 3. d Relay test ended. The following values can be scanned, subject to the actual equipment level: Display screen Explanation Slope A1 – level A1 Slope M2 – level M2 Adj. outside temperature The adjusted outside temperature can be reset Actual outside temperature to the actual outside temperature with e. Set boiler temp. Actual boiler temp. Set DHW temp. Actual DHW temp. Actual DHW outlet temperature Set DHW outlet temp. Set flow temperature Heating circuit with mixer Actual flow temperature Heating circuit with mixer 63 Service scans Temperatures, boiler coding card and brief . . . (cont.) Display screen Set mixed flow temp. Actual mixed flow temp. Boiler coding card Brief scan 1 to 8 Explanation Low loss header Low loss header Display screen Brief scan 1 2 3 4 5 Software version Burner control unit 0: w/o ex- 0: w/o ternal de- external blocking mand 1: exter- 1: external nal deblocking mand Number of LON users Equipment version Number of KM BUS users Burner control unit version Maximum demand temperature Software Software Software Software version version version version LON External Solar Mixer module extension control exten0: w/o 0: w/o exunit sion LON ternal ex0: w/o 0: w/o module tension solar mixer control extenunit sion Type Boiler type Burner control unit 0 External 0 to 10 V hook-up Display in % 0: w/o external hook-up Check digit Max. output Details in % 5692 619 GB 6 Software version Control unit System designs 01 to 06 Display in accordance with the system equipment level 0 Software version Programming unit 64 Service scans Temperatures, boiler coding card and brief . . . (cont.) Display screen Brief scan Boiler 7 8 0 0 Internal circulation pump Variable Software speed version pump variable 0: w/o speed 1: Wilo pump 2: Grun- 0: w/o dfos variable speed pump Heating circuit A1 Heating circuit M2 (w/o mixer) (with mixer) Remote Software Remote Software control version control version 0: w/o Remote 0: w/o Remote 1: Vitotr- control 1: Vitotr- control ol 200 0: w/o reol 200 0: w/o re2: Vitotr- mote 2: Vitotr- mote conol 300 control ol 300 trol Heating circuit pump to connection extension Variable Software Variable Software speed version speed version pump variable pump variable 0: w/o speed 0: w/o speed 1: Wilo pump 1: Wilo pump 2: Grun- 0: w/o vari2: Grun- 0: w/o dfos able speed dfos variable pump speed pump Checking outputs (relay test) 5692 619 GB Constant temperature control units Press the following keys: 2. a/b Control relay outputs. 1. K + d simultaneously for approx. 2 s 3. d Relay test ended. Subject to the actual equipment level, the following relay outputs can be controlled: Display screen Explanation 1 Burner modulation base load 65 Service scans Checking outputs (relay test) (cont.) Display screen 2 3 4 5 6 10 11 12 13 14 Explanation Burner modulation full load Internal pump / output 20 "ON" Heating mode diverter valve Valve, centre position DHW valve Output sK Internal extension Heating circuit pump A1 external extension Cylinder primary pump external extension DHW circulation pump external extension Central fault message external extension Weather–compensated control unit Press the following keys: 2. a/b Control relay outputs. 1. K + d simultaneously for approx. 2 s 3. d Relay test ended. 5692 619 GB Subject to the actual equipment level, the following relay outputs can be controlled: Display screen Explanation Base load Burner modulation lower output Full load Burner modulation upper output Int. pump ON Int. pump/output 20 "ON" Heating valve Diverter valve set to heating mode Valve central pos. Diverter valve in centre position (filling) DHW valve Diverter valve set to DHW mode Heat. circ. pump M2 ON Mixer extension Close mixer Mixer extension Open mixer Mixer extension Output int. Internal extension Heat. circ. pump A1 ON External extension Cylinder primary pump ON External extension DHW circ. pump ON External extension Central fault message ON External extension 66 Service scans Scanning operating conditions and sensors Constant temperature control units Press the following keys: 1. c 2. a/b for the required operating condition. 3. d End scan. Subject to the actual equipment level, the following operating conditions can be scanned: Display screen Explanation 1 15 °C/°F Actual outside temperature 3 65 °C/°F Actual boiler water temperature 5 50 °C/°F Actual cylinder temperature 5□ 45 °C/°F Solar – actual DHW temperature 6 70 °C/°F Actual value – collector sensor P Burner hours run (after maintenance, reset with e to "0") 263572 h PPP Burner starts (after maintenance, reset with e to "0") 030529 PPPP Fuel consumption 030417 Weather–compensated control unit 5692 619 GB Press the following keys: 4. d to select heating circuit with mixer M2. 1. a "1r" flashes. 2. d to select heating circuit without mixer A1 or 6. a/b for the required operating condition. 3. a "2r" flashes. 7. d 5. c End scan. Subject to the actual equipment level for heating circuits A1 and M2, the following operating conditions can be scanned: Display screen Explanation User no. Encoded user no. in the LON system Holiday mode If a holiday program has been entered. Departure day Date 67 Service scans Scanning operating conditions and sensors (cont.) Display screen Return day Outside temperature, ... °C Boiler water temperature, ... °C Flow temperature, ... °C Standard room temperature, ... °C Room temperature, ... °C Ext. set room temp, ... °C DHW temperature, ... °C Solar DHW temp., ... °C Collector temperature, ... °C Mixed flow temp., ... °C Burner, ...h Burner starts, ... Explanation Date Actual value Actual value Actual value (only for mixer circuit M2) Set value Actual value For external hook-up Actual DHW temperature Actual value Actual value Actual value, only with low loss header Actual hours run Hours run and burner starts (reset after maintenance e to "0"). 5692 619 GB Solar energy, ... kW/h Time Date Burner OFF/ON Int. pump OFF/ON Output 20 Int. output OFF/ON If an internal extension is installed Heating circuit pump OFF/ON If an external extension or extension kit for one heating circuit with mixer is installed Cylinder pump ON/OFF If an external extension is installed DHW circulation pump OFF/ If an external extension is installed ON Central fault message OFF/ If an external extension is installed ON Mixer open/closed If an extension kit for a heating circuit with mixer is installed Various languages The respective languages can be selected as permanent display language with d. 68 Troubleshooting Fault display Fault display structure A Fault display B Fault symbol C Fault number D Fault code The red fault indicator flashes for every fault. A fault in the burner control unit causes the display to show "E". Constant temperature control units In case of faults, the fault code and fault symbol will be displayed at the programming unit Weather–compensated control units 5692 619 GB The display flashes "Fault" if a fault message is issued Plain text fault displays: & Burner control unit & Outside temperature sensor & Flow sensor & Boiler sensor & Mixed flow sensor & DHW cylinder sensor & Flue gas sensor & DHW outlet sensor 69 Troubleshooting Fault display (cont.) & & Room temperature sensor Fault - user Checking and acknowledging faults Note If an acknowledged fault is not removed, the fault message will be re-displayed after 24 h. Constant temperature control units Press the following keys: 2. d all fault messages are acknowledged simultaneously, the fault display will be cancelled and the red fault indicator continues to flash. 3. d all fault messages are acknowledged simultaneously, the fault display will be cancelled and the red fault indicator continues to flash. 1. a/b for further fault codes. Weather–compensated control units Press the following keys: 1. c for the current fault. 2. a/b for further fault messages. Calling up acknowledged fault messages Press the following keys: for approx. 3 s. 5692 619 GB 1. d 2. a/b for the acknowledged fault. 70 Troubleshooting Calling up fault codes from the fault memory (fault history) The 10 most recent faults are saved and may be scanned. The faults are ordered according to date, thus the most recent fault is fault number 1. 1. G + d simultaneously for approx. 2 s 2. a/b for individual fault codes. 3. Note All saved fault codes can be deleted with e. 4. d Terminate the scan. 5692 619 GB Fault codes Fault Const. code in the display 0F X Weath.- System charcomp. acteristics Cause X Control mode 10 X X 18 X X 20 X X 28 X X Controls as if the outside temperature was 0 °C Controls as if the outside temperature was 0 °C Regulated without flow temperature sensor (low loss header) Regulated without flow temperature sensor (low loss header) Maintenance Carry out maintenance. After the maintenance, set code "24:0". Outside tem- Check the outside perature temperature sensensor sor (see page 79) shorted out Outside tem- Check the outside perature temperature sensensor lead sor (see page 79) broken System flow Check the low temperature loss header sensensor sor (see page 80) shorted out System flow temperature sensor lead broken Remedy Check the low loss header sensor (see page 80) 71 Troubleshooting Fault codes (cont.) Const. Fault code in the display 30 X Weath.- System charcomp. acteristics Cause Remedy X Burner blocked 38 X Burner blocked 40 X Mixer closes Check the boiler water temperature sensor (see page 80) Check the boiler water temperature sensor (see page 80) Check flow temperature sensor 48 X Mixer closes Boiler water temperature sensor shorted out Boiler water temperature sensor lead broken Mixer circuit M2 flow temperature sensor shorted out Mixer circuit M2 flow temperature sensor lead broken Cylinder primary temperature sensor shorted out Outlet temperature sensor shorted out Cylinder primary temperature sensor lead broken Draw off temperature sensor short circuit 50 X X No DHW heating 51 X X No DHW heating 58 X X No DHW heating 59 X X No DHW heating 72 Check flow temperature sensor Check sensors (see page 80) Check sensors (see page 80) Check sensors (see page 80) Check sensors (see page 80) 5692 619 GB X Troubleshooting Fault codes (cont.) Const. Fault code in the display 92 X Weath.- System charcomp. acteristics Cause Remedy X Control mode Check sensor 93 X X Control mode 94 X X Control mode 9A X X Control mode 9b X X Control mode 9C X X Control mode 9F X X Control mode X Control operation as per the delivered condition Burner blocked Collector temperature sensor shorted out Solar: Sensor S3 shorted out Solar: Cylinder primary temperature sensor shorted out Collector temperature sensor lead broken Solar: Sensor S3 lead broken Solar: Cylinder primary temperature sensor lead broken Solar control unit fault message Faulty programming unit 5692 619 GB A7 b0 X X b1 X X Control operation as per the delivered condition Flue gas temperature sensor short circuit Communication error programming unit Check sensor Check sensor Check sensor Check sensor Check sensor See solar control unit service instructions Replace programming unit Check flue gas temperature sensor Check connections and replace the programming unit if required 73 Troubleshooting Const. Fault code in the display b4 X Weath.- System charcomp. acteristics Cause Remedy X Internal fault Replace control unit b5 X X Internal fault Replace control unit b7 X X b8 X X bA X bC X bd X bE X bF X 74 Controls as if the outside temperature was 0 °C Control operation as per the delivered condition Burner blocked Boiler coding Plug in boiler codcard fault ing card or replace, if faulty Burner Flue gas Check flue gas blocked temperature temperature sensensor break sor Mixer "Close" Communica- Check the extention fault – sion kit connecextension kit tions and coding; for heating start the extencircuit M2 sion kit Control mode Communica- Check connections, cable/lead without remote tion fault and coding adcontrol Vitotrol remote control, dress "A0" heating circuit A1 Control mode Communica- Check connections, cable/lead without remote tion fault and coding adVitotrol recontrol mote control, dress "A0" heating circuit M2 Check remote Control mode Vitotrol remote control control DIP switch setting (see incorrectly page 105) encoded Replace the LON Control mode Incorrect communication LON commodule munication module 5692 619 GB Fault codes (cont.) Troubleshooting Fault codes (cont.) Const. Fault code in the display C2 X Weath.- System charcomp. acteristics Cause X Control mode C5 X Control mode, max. pump speed X Control mode, max. pump speed Check the connections and settings of coding address "54" Check the coding address "30" settings; check the DIP switch settings in the pump wiring chamber: Switch 1: OFF, Switch 2: ON Communica- Check the coding address "E5" settion fault external vari- tings; check the DIP switch setable speed tings in the pump heating cirwiring chamber: cuit pump, Switch 1: OFF, heating Switch 2: ON circuit M2 Communica- Check the coding address "E5" settion fault external vari- tings; check the DIP switch setable speed tings in the pump heating cirwiring chamber: cuit pump, Switch 1: ON, heating Switch 2: OFF circuit A1 Communica- Check connections, Vitocom 100 tion fault Vitocom 100 and coding address "95" (KM BUS) Communica- Check connections and coding tion fault – address "2E" ext. extension X C6 X X Control mode, max. pump speed Cd X X Control mode CE X X Control mode Communication fault solar control unit Communication error – variable speed internal pump 5692 619 GB C7 Remedy 75 Troubleshooting Fault codes (cont.) Const. Fault code in the display CF Weath.- System charcomp. acteristics Cause Remedy X Control mode Replace the LON communication module dA X Control mode without room influence db X Control mode without room influence dd X Control mode without room influence Communication fault LON communication module Room temperature sensor, heating circuit A1 shorted out Room temperature sensor, heating circuit M2 shorted out Room temperature sensor, heating circuit A1 lead broken dE X Control mode without room influence X X Burner blocked E5 X X Burner blocked Check the room temperature sensor – heating circuit M2 Check the room temperature sensor, heating circuit A1 and the remote control DIP switch setting (see page 105) Check the room Room temtemperature senperature sensor, heat- sor, heating circuit M2 and the ing circuit M2 lead bro- remote control DIP switch setting ken (see page 105) Fault – sup- Replace control unit ply voltage 24 V Flame ampli- Replace the confier fault trol unit. 5692 619 GB E4 Check the room temperature sensor – heating circuit A1 76 Troubleshooting 5692 619 GB Fault codes (cont.) Const. Fault code in the display E6 X Weath.- System charcomp. acteristics Cause Remedy X Burner fault Flue gas/ ventilation system blocked F0 X X Internal fault F1 X X Burner blocked Burner fault Check the flue gas/ventilation system and differential pressure sensor; press "E" Replace control unit Check flue gas path/route, press "E" F2 X X Burner fault F3 X X Burner fault F4 X X Burner fault F7 X X Burner blocked Flue gas temperature limiter has responded The temperature limiter has responded Check the heating system fill level, the circulation pump, the temperature limiter and interconnecting cables/leads; ventilate the system; press "E" Flame signal Check the ionisais already tion electrode and present at interconnecting burner start leads; press "E" No flame sig- Check the ionisanal. tion electrode, ignition, ignition module, interconnecting cables and leads, gas pressure, gas combination valve and the ionisation current; press "E" Check differential Differential pressure sensor pressure sensor faulty and lead 77 Troubleshooting Const. Fault code in the display F8 X Weath.- System charcomp. acteristics Cause Remedy X Burner fault The fuel valve closes too late F9 X X Burner fault Fan speed too low during burner start FA X X Burner fault Fan not at standstill Fd X X Burner blocked Fault burner control unit FE X X FF X X Strong interBurner blocked or in a ference (EMC) field fault state nearby or faulty main PCB Burner Strong interblocked or in a ference (EMC) field fault state nearby or internal fault Check the gas combination valve and both control paths; press "E" Check the fan, fan connecting cables, fan power supply and control; press "E" Check fan, fan connecting cables and fan control; press "E" Check the ignition electrodes and connecting cables/leads; check whether there are strong fields of interference (EMC) near the equipment; press "E". Replace the control unit if the fault persists. Start the boiler again. Replace the control unit if the equipment will not restart. 78 Start the boiler again. Replace the control unit if the equipment will not restart. 5692 619 GB Fault codes (cont.) Troubleshooting Repairs Checking the outside temperature sensor (weather-compensated control unit) 1. Pull plug "X3" off the control unit. 2. Test the resistance of the outside temperature sensor across terminals "X3.1" and "X3.2" on the disconnected plug and compare it with the curve. 3. Where actual values strongly deviate from the curve values, disconnect the wires at the sensor and repeat test directly at the sensor. 5692 619 GB 4. Subject to result, replace the lead or the outside temperature sensor. 79 Troubleshooting Repairs (cont.) Check the boiler temperature sensor, cylinder primary temperature sensor or flow temperature sensor for the low loss header 5692 619 GB A Boiler water temperature sensor 80 Troubleshooting Repairs (cont.) 1. & Boiler water temperature sensor Pull the leads off the boiler temperature sensor and check the resistance. & Cylinder primary temperature sensor Pull the plug % from the cable harness on the control unit and measure the resistance. & Flow temperature sensor Pull plug "X3" off the control unit and measure the resistance across terminals "X3.4" and "X3.5". 2. Check the sensor resistance and compare the actual values with the curve. 3. Replace the sensor in cases of severe deviation. Danger The boiler water temperature sensor is immersed in the heating water (risk of scalding). Drain the boiler before replacing the sensor. 5692 619 GB % Plug for the cylinder primary temperature sensor 81 Troubleshooting Repairs (cont.) Check the outlet temperature sensor 1. Pull the leads off the outlet temperature sensor A. 2. Check the sensor resistance and compare it with the curve. 3. Replace the sensor in cases of severe deviation. Danger The outlet temperature sensor is immersed in the DHW (risk of scalding). Drain the secondary side of the boiler before replacing the sensor. The flue gas temperature sensor locks out the boiler when the permissible flue gas temperature is exceeded. Reset the interlock after the flue gas system has cooled down by pressing the reset button "E". 82 5692 619 GB Checking the flue gas temperature sensor Troubleshooting Repairs (cont.) 1. Pull the leads off the flue gas temperature sensor A. 2. Check the sensor resistance and compare it with the curve. 3. Replace the sensor in cases of severe deviation. Checking the plate-type heat exchanger 5692 619 GB Drain the primary and secondary side of the boiler. During removal, small amounts of water may trickle out and escape from the removed plate-type heat exchanger. 83 Troubleshooting Repairs (cont.) 1. Shut off and drain the boiler on the primary and the secondary side. 2. Release the side closures and pivot the control unit forward. 3. Remove the siphon. 4. Release the compression fittings A, screws B and pull out the plate-type heat exchanger C. 5. Check the primary and secondary connections for contamination and scaling; if necessary, replace the plate-type heat exchanger. A Compression fittings B Screws C Plate-type heat exchanger 6. Lubricate the new gaskets/seals. Install in reverse order with new gaskets. Checking the temperature limiter 5692 619 GB If the burner control unit cannot be reset after a fault shutdown, although the boiler water temperature is below approx. 75 °C, check the temperature limiter. 84 Troubleshooting Repairs (cont.) 1. Pull the leads off the temperature limiter. 2. Check the continuity of the temperature limiter with a multimeter. 3. Remove the faulty temperature limiter. 4. Coat the replacement temperature limiter with heat conducting paste and install. 5. After commissioning, press reset button "E" on the control unit. Checking and replacing the differential pressure sensor 5692 619 GB In case of fault messages concerning the differential pressure sensor, check the sensor for: & Correct installation & Electrical connection & Correct position of the O-rings inside the adaptor & Plugs in test nipples Replace the sensor if fault messages persist. 85 Troubleshooting Repairs (cont.) Checking O-rings: A O-rings B Sensor C Plug-in connection D Adaptor 1. Pull off electrical plug C. 4. Insert the sensor with connection nipples into the gas combination valve adaptor and push in until it clicks into place. 2. Remove sensor B by pulling it upwards. 5. Reconnect the electrical plug-in connector on the sensor. 5692 619 GB 3. Ensure that both O-rings A are properly seated inside the adaptor retainers D. 86 Troubleshooting Repairs (cont.) Checking the fuse 3. Remove the cover. 2. Release the side closures and pivot the control unit down. 4. Check the fuse F1 (see connection and wiring diagram). 5692 619 GB 1. Switch OFF the power. 87 Troubleshooting Repairs (cont.) Extension kit for heating circuit with mixer Checking the rotational direction of the mixer motor Changing the rotational direction of the mixer motor (if required) 1. 1. Switch the ON/OFF switch A at the extension kit first OFF and then ON again. The device will carry out the following self-test: & Mixer "Close" (150 s) & Pump "ON" (10 s) & Mixer "Open" (10 s) & Mixer "Close" (10 s) Standard control mode then recommences. Danger An electric shock can be life-threatening. When opening the equipment, switch OFF the ON/ OFF switch and mains voltage, for example at the fuse or the mains isolator. 2. Remove the lower and upper housing cover of the extension kit. Extension kit installation instructions 3. 2. Observe the rotational direction of the mixer motor during its self-test. Then set the mixer manually to "Open" again. Note The flow temperature sensor must now capture a higher temperature. If the temperature falls, either the motor is turning in the wrong direction or the mixer set is incorrectly fitted. 5692 619 GB Mixer installation instructions A ON/OFF switch B Rotational direction switch Change the rotational direction switch: 88 Troubleshooting Repairs (cont.) & Switch position I for central heating return from the left (delivered condition). & Switch position II for central heating return from the right. Checking the Vitotronic 050 (accessories) 5692 619 GB The Vitotronic 050 is connected with the control unit via the LON connecting cable. To test the connection, implement a user check at the boiler control unit (see page 37). 89 Function description Constant temperature control unit Controls and display elements A B C D Pressure gauge Fault display (red) ON indicator (green) Reset button E Control panel: O Set boiler water temperature F Set DHW temperature O+F Emissions test function K Standby mode: L DHW only G Heating and DHW / No function b/a Setting values d Confirmation c Information e Standard setting (Reset) F ON/OFF switch The set boiler water temperature will be maintained in the "Heating and DHW" program when a demand is raised by the room thermostat. The boiler water temperature will be maintained at the default frost protection temperature when there is no demand. 90 The boiler water temperature will be limited: & to 74 °C by the thermostat inside the burner control unit. & to 82 °C by the electronic temperature limiter inside the burner control unit (during DHW heating to 87 °C). & to 100 °C by the temperature limiter in the safety chain (interlocks the burner control unit). 5692 619 GB Heating mode Function description Constant temperature control unit (cont.) Heating the DHW storage cylinder from cold The heating circuit pump is switched ON and the three-way diverter valve will be changed over, if the cylinder primary temperature sensor captures a temperature lower than the set temperature. & At a boiler water temperature ≥ set DHW temperature, the cylinder primary pump will be switched ON. & At a boiler water temperature ≤ set DHW temperature, the burner will be switched ON and, after the required boiler water temperature has been reached, the cylinder primary pump will be switched ON. The cylinder is then heated up to the set DHW temperature. Heating stops when the set temperature has been reached at the cylinder primary temperature sensor and at the outlet temperature sensor. After heating, the cylinder primary pump and the three-way diverter valve remain ON for a further 30 s. Reheating when DHW is drawn off The DHW is regulated to the set temperature via the cylinder primary temperature sensor. The cylinder continues to be heated up after the draw-off process has ended, until the set DHW temperature has been reached at the cylinder primary temperature sensor. The cylinder primary pump and the three-way diverter valve remain ON for a further 30 s. 5692 619 GB When DHW is drawn off, cold water enters at the bottom of the cylinder. The heating circulation pump is switched ON and the three-way diverter valve is changed over, if the cylinder primary temperature sensor captures a temperature lower than the set temperature. & At a boiler water temperature ≥ set DHW temperature, the cylinder primary pump will be switched ON. & At a boiler water temperature ≤ set DHW temperature, the burner will be switched ON and, after the required boiler water temperature has been reached, the cylinder primary pump will be switched ON. 91 Function description Weather–compensated control unit Controls and display elements Pressure gauge Fault display (red) ON indicator (green) Reset button E Control panel: A Time program, central heating B Time program DHW heating/DHW circulation pump (if connected to the control unit) H Holiday mode D Date/time E Reduced room temperature F Set DHW temperature O+F Emissions test function K Standby mode: L DHW only G Heating and DHW M Party mode N Economy mode b/a Setting values d Confirmation c Information e Standard setting (Reset) F Rotary selector for the standard room temperature G ON/OFF switch 5692 619 GB A B C D 92 Function description Weather–compensated control unit (cont.) Heating mode The control unit determines a set boiler water temperature subject to the outside temperature or room temperature (if a room temperature-dependent remote control is connected) and the slope/level of the heating curve. The determined set boiler water temperature is transferred to the burner control unit. From the set and actual boiler water temperatures, the burner control unit calculates the modulation level and regulates the burner accordingly. The boiler water temperature will be limited: & to 74 °C by the thermostat inside the burner control unit. & to 82 °C by the electronic temperature limiter inside the burner control unit (during DHW heating to 87 °C). & to 100 °C by the temperature limiter in the safety chain (interlocks the burner control unit). Heating the DHW storage cylinder from cold The heating circuit pump is switched ON and the three-way diverter valve will be changed over, if the cylinder primary temperature sensor captures a temperature lower than the set temperature. & At a boiler water temperature ≥ set DHW temperature, the cylinder primary pump will be switched ON. & At a boiler water temperature ≤ set DHW temperature, the burner will be switched ON and, after the required boiler water temperature has been reached, the cylinder primary pump will be switched ON. The cylinder is then heated up to the set DHW temperature. Heating stops when the set temperature has been reached at the cylinder primary temperature sensor and at the outlet temperature sensor. After heating, the cylinder primary pump and the three-way diverter valve remain ON for a further 30 s. Reheating when DHW is drawn off 5692 619 GB When DHW is drawn off, cold water enters at the bottom of the cylinder. 93 Function description Weather–compensated control unit (cont.) The DHW is regulated to the set temperature via the cylinder primary temperature sensor. The cylinder continues to be heated up after the draw-off process has ended, until the set DHW temperature has been reached at the cylinder primary temperature sensor. The cylinder primary pump and the three-way diverter valve remain ON for a further 30 s. 5692 619 GB The heating circulation pump is switched ON and the three-way diverter valve is changed over, if the cylinder primary temperature sensor captures a temperature lower than the set temperature. & At a boiler water temperature ≥ set DHW temperature, the cylinder primary pump will be switched ON. & At a boiler water temperature ≤ set DHW temperature, the burner will be switched ON and, after the required boiler water temperature has been reached, the cylinder primary pump will be switched ON. 94 Function description Extensions for external connections Internal extension H1 An external safety valve can be connected to gD. 5692 619 GB The internal extension H1 is integrated into the control unit casing. The cylinder primary pump is connected to relay output sK. 95 Function description Extensions for external connections (cont.) Internal extension H2 (accessories) An external extractor fan interlock can be connected to aBJ. 5692 619 GB The internal extension H2 is integrated into the control unit casing instead of the internal extension H1. The cylinder primary pump is connected to relay output sK. 96 Function description Extensions for external connections (cont.) External extension H1 (accessories) aVD & External blocking (terminals 2 - 3) & External demand (terminals 1 - 2) & External heating program changeover (terminal 1 - 2) The allocation of function "External heating program changeover" is set via coding address "91". aVF External set value 0 to 10 V aVG KM BUS 5692 619 GB The external extension is connected to the boiler control unit via the KM BUS. The following functions can be controlled or processed simultaneously via the extension: A Mains isolator (on site) sÖ Heating circuit pump for the heating circuit without mixer sK DHW circulation pump fÖ Power supply gÖ Central fault message 97 Function description Extensions for external connections (cont.) External extension H2 (accessories) aVD & External blocking (terminals 2 - 3) & External demand (terminals 1 - 2) & External heating program changeover (terminal 1 - 2) The allocation of function "External heating program changeover" is set via coding address "91". aVG KM BUS 5692 619 GB The external extension is connected to the boiler control unit via the KM BUS. The following functions can be controlled or processed simultaneously via the extension: A Mains isolator (on site) sK DHW circulation pump fÖ Power supply 98 Function description Control functions External heating program changeover The "Ext. heating program changeover" function is connected via the external extension input "aVD". Coding address "91" enables the selection of which heating circuits the heating program changeover should affect: The heating program changeover affects: No changeover Heating circuit without mixer (A1) Heating circuit with mixer (M2) Heating circuit without mixer and heating circuit with mixer Coding 91:0 91:1 91:2 91:3 With coding address "d5", you can select in which direction the changeover should be made for each heating circuit: The heating program changeover affects: Changeover in the direction of "Constant reduced" or "Constant standby" mode (respectively in accordance with the selected set value) Changeover towards "Constant heating mode" Coding d5:0 d5:1 The duration of the heating program changeover can be adjusted in coding address "F2". The heating program changeover affects: No heating program changeover Duration of the heating program changeover 1 to 12 hours Coding F2:0 F2:1 to F2:12 The heating program changeover remains active for as long as the contact remains closed, in any case at least as long as the duration selected in coding address "F2". 5692 619 GB External blocking The "External blocking" function is connected via the external extension input "aVD". The "External blocking" function stops the burner. In coding address "32" you can select the influence the signal "External blocking" should have on the connected circulation pumps. 99 Function description Control functions (cont.) External demand The "External demand" function is connected via the external extension input "aVD". In coding address "34" you can select the influence the signal "External demand" should have on the connected circulation pumps. In coding address "9b" you can select the minimum set boiler water temperature in case of external demand. Venting program During the venting program, the circulation pump will be alternately switched ON and OFF for 30 seconds respectively over a period of 20 minutes. For a certain period, the changeover valve is alternately set towards heating mode and DHW heating. The burner is switched OFF during the venting program. The venting program is activated via coding "2F:1". The program is automatically deactivated after 20 min, and the coding address "2F" is set to "0". Filling program In the delivered condition, the changeover valve is set in its centre position, enabling the system to be filled completely. After starting the control unit, the diverter valve no longer goes into its central position. Afterwards, the changeover valve can be moved via coding address "2F:2" into the centre position. In this position, the control unit can be switched OFF, and the the system can be filled completely. Filling with the control unit switched ON The burner shuts down if this function is enabled via coding address "2F". The program is automatically deactivated after 20 min, and the coding address "2F" is set to "0". 5692 619 GB If the system is to be filled with the control unit switched ON, the changeover will be moved to its centre position via code "2F:2" and the pump will be started. 100 Function description Control functions (cont.) Screed function The screed function enables the drying of screed. For this, always observe the details specified by the screed manufacturer. You can select various temperature profiles. Temperature profile: Diagram 1 (DIN 4725 part 4) code "F1:1" Temperature profile: Diagram 2 (ZV parquet and flooring technology) code "F1:2" 5692 619 GB Temperature profile: Diagram 3 code "F1:3" 101 Function description Control functions (cont.) Temperature profile: Diagram 4 code "F1:4" Temperature profile: Diagram 5 code "F1:5" 5692 619 GB Temperature profile: Diagram 6 code "F1:6" (delivered condition) 102 Function description Control functions (cont.) Raising the reduced room temperature During operation with reduced room temperature, the reduced set room temperature can be automatically raised subject to outside temperature. The temperature is raised in accordance with the selected heating curve up to the set standard room temperature. The outside temperature limits for the start and end of the temperature raising can be adjusted via the coding addresses "F8" and "F9". Example using the settings in the delivered condition B Heating curve for operation with reduced room temperature 5692 619 GB A Heating curve for operation with standard room temperature 103 Function description Control functions (cont.) Reducing the heat-up time During the transition from operation with reduced room temperature into operation with standard room temperature, the boiler water or flow temperature will be raised in accordance with the selected heating curve. The boiler water or flow temperature can be automatically increased. The value and duration for the additional increase of the set boiler water temperature or flow temperature can be adjusted in the coding addresses "FA" and "Fb". A Start of operation with standard room temperature B Set boiler water or flow temperature in accordance with the selected heating curve 104 C Set boiler water or flow temperature in accordance with coding address "FA": 50 °C + 20 % = 60 °C D Duration of operation with raised boiler water or flow temperature in accordance with coding address "Fb": 60 min 5692 619 GB Example using the settings in the delivered condition Function description Remote control DIP switch The DIP switches are located on the PCB in the top part of the housing. Remote control The remote control affects the heating circuit without mixer A1 DIP switch setting The remote control affects the heating circuit with mixer M2 5692 619 GB When connecting a separate room temperature sensor, set DIP switch "3" to "ON". 105 Designs A1 X... § $ 106 Main PCB Electrical interfaces Boiler water temperature sensor Draw-off temperature sensor % aA aG dÖ Cylinder temperature sensor Ionisation electrode Flue gas temperature sensor Stepper motor for diverter valve 5692 619 GB Connection and wiring diagram – internal connections Designs Connection and wiring diagram – internal . . . (cont.) Thermocouple Ignition device a-ÖA Fan motor aNF Differential pressure sensor 5692 619 GB fJ gF 107 Designs A1 108 Main PCB A2 Power supply unit 5692 619 GB Connection and wiring diagram – external connections Designs Connection and wiring diagram – external . . . (cont.) Optolink Burner control unit Programming unit Coding card Connection adaptor Communication module LON Internal extension H1 or H2 ON/OFF switch Reset button Electrical interfaces Outside temperature sensor ? Flow temperature sensor - low loss header % Cylinder temperature sensor sÖ Internal circulation pump sK Primary pump dG Gas solenoid valve fÖ Power supply lH Power supply accessories and Vitotrol 100 a-Ö Fan motor aYA Gas governor aVG KM BUS 5692 619 GB A3 A4 A5 A6 A7 A8 A9 S1 S2 X... ! 109 Parts lists Parts lists 001 Heat exchanger connecting pipe with gaskets 002 Flow pipework 003 DHW connecting pipe 004 DHW connecting pipe 005 Cylinder connecting pipe 006 Return connecting pipe 007 Gas connection flange 008 Stratification storage cylinder 009 Siphon 010 Condensate hose 012 Heat exchanger 013 Cap plate (with item 014) 014 Profiled gasket 015 Clip nut 016 Mounting bracket closure 017 Boiler adaptor 018 Plug 019 Air inlet gasket Ø 125 020 Lip seal Ø 80 021 Boiler connection grommets 022 Connecting pipe - diaphragm expansion vessel 023 Diaphragm expansion vessel 024 Pressure gauge and fem. connection 025 Quick-acting air vent valve G ⅜" 026 Overflow valve 027 Safety valve 028 Air vent valve G ⅜" 029 Linear stepper motor 030 Non-return valve 031 Ball valve R ½" with handle 033 Flat packing 034 Set of plug connector retainers 035 Safety spring 036 Plate-type heat exchanger 110 037 Gasket set – plate-type heat exchanger 040 Grommets (set) 051 Burner (with items 050, 052 to 064) 052 Ignition unit 055 Burner gauze 056 Radial fan 057 Pressure transmitter 058 Gas train 059 Conversion kit for natural gas E (gas restrictor) 060 Conversion kit for natural gas LL (gas restrictor) 061 only for 26 kW: Conversion kit for LPG P (gas restrictor) 064 Burner gauze gasket 069 DHW connecting pipe 100 Control unit 101 Back cover 102 Locking clips (10 pieces) 103 Support 104 Pivot arm 105 Hinge pins (10 pieces) 106 Flap 107 Pressure gauge retainer 108 Clip (10 pieces) 109 Hinge (10 pieces) 110 Boiler coding card 111 Fuse 6.2 A s (10 pieces) 112 Programming unit for constant temperature operation 113 Programming unit for weathercompensated mode 122 LON communication module (accessories) 123 PCB adaptor – LON module (accessories) 5692 619 GB Spare parts information Quote the part and serial no. (see type plate) and the item no. of the required part (as per this parts list). Obtain standard parts from your local supplier. Parts lists Parts lists (cont.) 125 151 152 153 154 155 200 201 202 203 204 205 206 300 301 352 354 355 Fuse holder Outside temperature sensor Cylinder temperature sensor Flue gas temperature sensor Thermocouple Temperature sensor Side panels Top front panel Back top panel Front top panel Front bottom panel Tie-bar Adjustable foot Circulation pump motor Circulation pump motor Gasket Anode flange with gasket Thermal insulation – flange Wearing parts 050 Burner gasket 053 Ignition electrode with gasket 054 Ionisation electrode with gasket 353 Magnesium anode Ø = 26 × 280/ 250 116 117 118 119 120 126 127 128 207 208 209 350 351 400 401 403 404 A Heat conducting paste Burner maintenance set Set of small burner parts Pressure sensor adaptor Ionisation current test lead adaptor Cable harness X8/X9 Cable harness 100/35/54 (auxiliary earth) Stepper motor connecting cable Cable harness ionisation/KM BUS (internal) Internal ionisation lead Mating plug Cable fixing Anti-splash protection Fixing elements Touch-up paint stick, Vitowhite Touch-up spray paint, Vitowhite Seal washer Strain relief Operating instructions for constant temperature operation Operating instructions for weather-compensated operation Installation instructions Service instructions Type plate 5692 619 GB Parts not shown 032 Gasket set – plug-in connector 038 Special grease 039 062 063 065 115 111 Parts lists 5692 619 GB Parts lists (cont.) 112 Parts lists 5692 619 GB Parts lists (cont.) 113 Parts lists 5692 619 GB Parts lists (cont.) 114 Parts lists 5692 619 GB Parts lists (cont.) 115 Parts lists 5692 619 GB Parts lists (cont.) 116 Commissioning/service reports Commissioning/service reports Setting and test values Set value Static pressure Date: By: mbar Supply pressure (flow pressure) = for natural gas E mbar = for natural gas LL mbar = for LPG mbar Initial start-up Maintenance/service max. 57.5 mbar 17.457.5 mbar 17.457.5 mbar 42.557.5 mbar Tick gas type Carbon dioxide content CO 2 & at the lower rated output % vol. & at the upper rated out% vol. put Oxygen content O 2 & at the lower rated output % vol. & at the upper rated out% vol. put Carbon monoxide content CO & at the lower rated output ppm & at the upper rated outppm put µA min. 2 µA 5692 619 GB Ionisation current 117 Specification Specification Rated voltage Rated frequency Rated current Protection class Protection 230 V~ 50 Hz~ 6 A~ I IP X 4 D to EN 60529 Permissible ambient temperature & during operation 0 to +40 °C & during storage and transport Electronic temperature limiter setting: Temperature limiter setting Line fuse (mains) Power consumption & Circulation pump & Burner & Control unit 82 °C 100 °C (fixed) max. 16 A max. 115 W max. 60 W max. 10 VA -20 to +65 °C Product characteristics (to EnEV [Germany]) Rated output range kW Efficiency µ at & 100 % of rated output % & 30% of rated output % % Standby heat loss qB,70* 2 Power consumption * 2 at & 100 % of rated output W & 30 % of rated output W *1 The 4.2 to 13 6.6 to 26 96.0 107.4 0.8 96.3 107.4 0.7 207 69 207 69 supply values are only for reference (e.g. in the gas contract application) or to estimate the supplementary volumetric settings. Because of factory settings, the gas pressure must not be altered from these values. Reference: 15°C, 1013 mbar. *2 Max. limit to EnEV [Germany] 118 5692 619 GB Gas fired boiler, category 13 kW: I 2ELL, category 26 kW: II 2ELL3P Rated output TV/T R 50/30 °C kW 4.2 to 13 6.6 to 26 Rated output range for central heating kW 3.9 to 12.3 6.3 to 24.7 for DHW heating kW 3.9 to 16.7 — 1 Connection values * Relative to the max. load with: with H uB Natural gas E 9.45 kWh/m 3 m 3 /h 1.77 2.65 34.02 MJ/m 3 l/min 2.05 3.08 Natural gas LL 8.13 kWh/m 3 m 3 /h l/min 29.25 MJ/m 3 LPG 12.79 kWh/kg m 3 /h — 1.94 46.04 MJ/kg Product ID _-0085 Certificates Declaration of conformity Declaration of conformity for the Vitodens 333 We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, confirm as sole responsible body that the product Vitodens 333 complies with the following standards: DIN 4702–6 DIN 4753 EN 483 EN 625 EN 677 EN 50 165 EN 60 335 EN 61 000-3-2 EN 61 000-3-3 In accordance with the following Directives, this product is designated with _0085: 90/396/EEC 89/336/EEC 73/ 23/EEC 92/ 42/EEC 97/23/EC EC Declaration of conformity by an authorised body according to EMVG article 10.2 Certificate number: E9 02 08 1730. This product meets the requirements of the Efficiency Directive (92/42/EEC) for Condensing boilers. The product characteristics determined as system values for the Vitodens 333 as part of EC type testing according to the Efficiency Directive (see specification table) can be used for the energy assessment of heating and ventilation equipment to DIN V 4701–10. Allendorf 12.07.05 Viessmann Werke GmbH&Co KG 5692 619 GB pp. Manfred Sommer 119 Certificates Manufacturer's certificate according to the 1st BImSchV [Germany] We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, confirm that the Vitodens 333 product meets the NO x limits specified by the first BImSchV § 7 (2) [Germany]. Allendorf 12.07.05 Viessmann Werke GmbH&Co KG 5692 619 GB pp. Manfred Sommer 120 Keyword index Keyword index A Acknowledging a fault display . . . . . . . Adjusting the room temperature . . . . Anode replacement . . . . . . . . . . . . . . . . . . . . . . Anode testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 34 22 22 B Boiler temperature sensor . . . . . . . . . . . . Brief scans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Burner gauze assembly . . . . . . . . . . . . . . . . Burner removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 62 18 17 C Calling up fault messages . . . . . . . . . . . . . 71 Cleaning agent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Cleaning cylinders . . . . . . . . . . . . . . . . . . . . . . . 22 Cleaning the combustion chamber 20 Cleaning the heating surfaces . . . . . . . 20 Code 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Code 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Coding during commissioning . . . . . . . 27 Condensate drain . . . . . . . . . . . . . . . . . . . . . . . . 21 Connection diagrams . . . . . . . . . . . . . . . . . . 106 Control unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90, 92 Cylinder primary temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80 5692 619 GB D Diaphragm expansion vessel . . . . . . . . . . 7 Differential pressure sensor . . . . . . . . . . 85 Display elements . . . . . . . . . . . . . . . . . . . . 90, 92 E Extension kit for heating circuit with mixer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 Extension & external . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97, 98 & internal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95, 96 External blocking . . . . . . . . . . . . . . . . . . . . . . . . . 99 External demand. . . . . . . . . . . . . . . . . . . . . . . . . 100 F Fault codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Fault display structure . . . . . . . . . . . . . . . . . . 69 Fault history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Fault memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Filling program. . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 Filling the system . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Fitting the burner . . . . . . . . . . . . . . . . . . . . . . . . . 20 Flow temperature sensor . . . . . . . . . . . . . . 80 Flue gas temperature sensor . . . . . . . . 82 Function descriptions . . . . . . . . . . . . . . . . . . . 90 Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 G Gas combination valve . . . . . . . . . . . . . . . . . 14 Gas supply pressure . . . . . . . . . . . . . . . . . . . . 14 Gas type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 H Heating curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Heating curve level . . . . . . . . . . . . . . . . . . . . . . 33 Heating curve slope . . . . . . . . . . . . . . . . . . . . . 33 Heating program changeover . . . . . . . . 99 Heat-up time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Hiding a fault display . . . . . . . . . . . . . . . . . . . . 70 I Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Ignition electrodes . . . . . . . . . . . . . . . . . . . . . . . 19 Initial start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Ionisation current . . . . . . . . . . . . . . . . . . . . . . . . . 26 Ionisation electrode. . . . . . . . . . . . . . . . . . . . . . 19 L Language selection . . . . . . . . . . . . . . . . . . . . . . . . 9 LON communication module . . . . . . . . . 35 LON system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Lower rated output . . . . . . . . . . . . . . . . . . . . . . . 24 M Manufacturer's declaration . . . . . . . . . . 120 121 Keyword index Keyword index (cont.) O Outlet temperature sensor . . . . . . . . . . . . 82 Outside temperature sensor . . . . . . . . . 79 P Parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 Plate-type heat exchanger . . . . . . . . . . . . 83 Product characteristics . . . . . . . . . . . . . . . . 118 Protective anode & Checking the anode . . . . . . . . . . . . . . . . . . . 21 R Raising the reduced room temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 Reduced room temperature . . . . . . . . . . 35 Reducing the heat-up output . . . . . . . . 103 Reducing the heat-up time . . . . . . . . . . . 104 Relay test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Replacing the magnesium anode . . 22 Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117 Resetting codes . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 S Safety chain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Scanning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Scanning operating conditions . . . . . . 67 Scanning sensors . . . . . . . . . . . . . . . . . . . . . . . . 67 Screed drying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 Screed function . . . . . . . . . . . . . . . . . . . . . . . . . . 101 Service level summary . . . . . . . . . . . . . . . . . 61 Setting the date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Setting the output. . . . . . . . . . . . . . . . . . . . . . . . . 15 Setting the time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Soundness test, balanced flue system 15 Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 Standard room temperature . . . . . . . . . . 34 Static pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Supply pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . 13 System design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 System designs . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 System pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 System version . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 T Temperature limiter . . . . . . . . . . . . . . . . . . . . . . Temperature scans . . . . . . . . . . . . . . . . . . . . . . Testing functions . . . . . . . . . . . . . . . . . . . . . . . . . . Testing outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . Testing the magnesium anode . . . . . . 84 62 65 65 22 U Upper rated output . . . . . . . . . . . . . . . . . . . . . . . 25 V Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Venting program . . . . . . . . . . . . . . . . . . . . . . . . . 100 Vitotronic 050 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 5692 619 GB W Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 122 123 5692 619 GB 124 Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Telephone: +44 1952 675000 Fax: +44 1952 675040 E-mail: [email protected] chlorine-free bleached paper Printed on environmentally-friendly, Viessmann Werke GmbH&Co KG D-35107 Allendorf Telefon: +49 6452 70-0 Telefax: +49 6452 70-2780 www.viessmann.de 5692 619 GB Compact gas fired condensing boiler Type WS3A 4.2 to 13 kW from serial no. 7190 613 ... 6.6 to 26 kW from serial no. 7190 614 ... Subject to technical modifications. Applicability