VIESMANN
for heating engineers
Vitodens 333
Type WS3A
Compact gas fired condensing boiler
4.2 to 13 kW natural gas version
6.6 to 26 kW natural gas and LPG version
For applicability, see the last page
VITODENS 333
5692 619 GB
8/2005
Please keep safe
Safety instructions
Safety instructions
Please follow these safety instructions closely to prevent accidents and
material losses.
Safety instructions explained
Danger
This symbol warns against the
risk of injury.
!
Please note
This symbol warns against the
risk of material losses and
environmental pollution.
Note
Details identified by the word "Note"
contain additional information.
Target group
These instructions are exclusively
designed for qualified personnel.
& Work on gas equipment must only
be carried out by a qualified gas fitter.
& Work on electrical equipment must
only be carried out by a qualified
electrician.
& The system must be commissioned
by the system installer or a qualified
person authorised by the installer.
&
the Code of Practice of relevant
trade associations,
& all current safety regulations as
defined by DIN, EN, DVGW, TRGI,
TRF, VDE and all locally applicable
standards.
If you smell gas
Danger
Escaping gas can lead to
explosions which may result in
serious injury.
& Never smoke. Prevent naked
flames and sparks. Never
switch lights or electrical
appliances ON or OFF.
& Close the gas shut‐off valve.
& Open windows and doors.
& Remove all people from the
danger zone.
& Notify your gas or electricity
supplier from outside the
building.
& Shut off the electricity supply
to the building from a safe
place (outside the building).
Regulations
2
Danger
Flue gas can lead to life‐threatening poisoning.
& Shut down the heating system.
& Ventilate the boiler room.
& Close all doors leading to the
living space.
5692 619 GB
If you smell flue gas
Observe the following when working
on this system
& all legal instructions regarding the
prevention of accidents,
& all legal instructions regarding
environmental protection,
Safety instructions
Safety instructions (cont.)
Working on the system
&
When using gas as fuel, also close
the main gas shut‐off valve and
safeguard against unauthorised
reopening.
& Isolate the system from the power
supply and check that it is no longer
'live', e.g. by removing a separate
fuse or by means of a mains isolator.
& Safeguard the system against
unauthorised reconnection.
Please note
Electronic modules can be
damaged by electro‐static discharges.
Touch earthed objects, such as
heating or water pipes, to discharge static loads.
!
Please note
Repairing components which
fulfil a safety function can compromise the safe operation of
your heating system.
Replace faulty components
only with original Viessmann
spare parts.
Ancillary components, spare and
wearing parts
!
Please note
Spare and wearing parts which
have not been tested together
with the heating system can
compromise its function. Installing non‐authorised components and non‐approved
modifications/conversion can
compromise safety and may
invalidate our warranty.
For replacements, use only original spare parts from
Viessmann or those which are
approved by Viessmann.
5692 619 GB
!
Repair work
3
Index
Index
Initial start-up, inspection, maintenance
Steps – initial start-up, inspection and maintenance ....................................
Further details regarding the individual steps ..............................................
5
7
Coding
Code 1........................................................................................................ 39
Code 2........................................................................................................ 41
Resetting codes to the delivered condition .................................................. 60
Service scans
Service level summary ................................................................................
Temperatures, boiler coding card and brief scans .......................................
Checking outputs (relay test) ......................................................................
Scanning operating conditions and sensors ................................................
61
62
65
67
Troubleshooting
Fault display ...............................................................................................
Calling up fault codes from the fault memory (fault history) ..........................
Fault codes.................................................................................................
Repairs ......................................................................................................
69
71
71
79
Function description
Constant temperature control unit ...............................................................
Weather–compensated control unit .............................................................
Extensions for external connections ............................................................
Control functions ........................................................................................
Remote control DIP switch ..........................................................................
90
92
95
99
105
Designs
Connection and wiring diagram – internal connections ................................ 106
Connection and wiring diagram – external connections ............................... 108
Parts lists .................................................................................................. 110
Commissioning/service reports ............................................................... 117
Certificates
Declaration of conformity ............................................................................ 119
Manufacturer's certificate according to the 1st BImSchV [Germany]............. 120
Keyword index .......................................................................................... 121
4
5692 619 GB
Specification ............................................................................................. 118
Initial start-up, inspection, maintenance
Steps – initial start-up, inspection and maintenance
For further information regarding individual steps, see the pages indicated.
!
•
•
•
•
•
•
•
Commissioning steps
!
•
Inspection steps
5692 619 GB
•
•
•
•
•
•
Page
!
•
1. Filling the heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
2. Venting the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
3. Venting the heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
4. Filling the siphon with water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
5. Checking all connections on the primary and DHW
side for leaks
6. Checking the power supply connection
•
•
•
Maintenance steps
•
•
•
•
•
•
•
7. Setting the time and date (if required) – only for
weather-compensated control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
8. Language selection (if required) - only for weathercompensated control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
9. Pivot down the control unit for commissioning and
maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
10. Checking the gas type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
11. Gas type conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
12. Function sequence and possible faults . . . . . . . . . . . . . . . . . . . . . . . 12
13. Checking the static and supply pressure . . . . . . . . . . . . . . . . . . . . 13
14. Setting the max. output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
15. Checking the balanced flue system soundness
(annular gap check) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
•
•
16. Removing the burner and checking the burner
gasket (replace gasket every two years) . . . . . . . . . . . . . . . . . . . . . . 17
•
•
•
•
17. Checking the burner gauze assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
•
•
19. Cleaning the combustion chamber/heating
surfaces and fitting the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
18. Checking and adjusting the ignition and ionisation
electrodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5
Initial start-up, inspection, maintenance
Steps – initial start-up, inspection and . . . (cont.)
!
Commissioning steps
!
•
•
Inspection steps
Page
!
•
20. Checking the condensate drain and cleaning the
siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
•
•
21. Checking the neutralising system (if installed)
•
•
23. Cleaning the DHW cylinder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
22. Testing the anode earth current with an anode
tester . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
24. Checking and replacing the magnesium anode (if
required) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
•
•
•
25. Returning the DHW cylinder to use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
•
•
•
•
•
•
•
•
•
•
27. Checking the function of all safety valves
•
•
•
•
•
•
•
•
•
30. Flue gas emissions test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
26. Checking the diaphragm expansion vessel and
system pressure
28. Checking the tightness of electrical connections
29. Checking all gas equipment for soundness at
operating pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
31. Checking the ionisation current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
32. Checking the LPG external safety valve (if
required)
•
•
33. Matching the control unit to the heating system . . . . . . 27
•
35. Connecting the control unit to the LON system
(only for weather-compensated control units) . . . . . . . . . . 35
•
36. Implementing a user check (in conjunction with
the LON system with a weather-compensated
control unit) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
•
37. Instructing the system user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
34. Adjusting the heating curves (only for control
units for weather-compensated operation) . . . . . . . . . . . . . . . . . 32
•
6
Maintenance steps
38. Scanning and resetting the "maintenance" display
38
5692 619 GB
Initial start-up, inspection, maintenance
Further details regarding the individual steps
Filling the heating system
!
Please note
Unsuitable fill water increases the level of deposits and corrosion and
may lead to boiler damage.
& Thoroughly flush the entire heating system prior to filling with water.
& Only use fill water of potable quality.
& Fill water with a water hardness in excess of 3.58 mmol/l must be softened, e.g. with the small softening system for heating water (see the
Vitoset pricelist).
& An anti-freeze additive suitable for heating systems can be mixed with
the fill water.
1. Check the inlet pressure of the diaphragm expansion vessel.
2. Close the gas shut-off valve.
3. Fill the heating system at the fill
valve in the heating return (on the
connection set or on site). Minimum
system pressure > 0.8 bar).
Note
If the control unit has not been
switched ON prior to filling the system, then the servomotor of the
changeover valve will still be in its
centre position, and the system will
be completely filled.
4. If the control unit had already been
switched ON before filling began:
Start the control unit and activate
the fill program via coding "2F:2".
Note
To call up coding level 1 and for
setting the coding address, see
page 39.
For function and details of the fill
program, see page 100.
Whilst the fill program runs, the display shows "bF" (Vitotronic 100) or
"Filling" (Vitotronic 200).
5. Close the boiler fill & drain valve.
5692 619 GB
6. Set code "2F:0".
7
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Venting the boiler
1. Close the shut-off valves on the primary side.
2. Connect the drain hose on valve
A with a drain outlet.
3. Open valve A and fill valve in the
heating return and vent at mains
pressure, until no sound of escaping air can be heard.
4. Close valve A and fill valve in the
heating return and open the primary shut-off valves.
Venting the heating system
1. Close the gas shut-off valve and
switch ON the control unit.
2. Activate the venting program via
code "2F:1".
Note
To call up coding level 1 and for
setting the coding address, see
page 39.
For the function and sequence of
the venting program, see page 100.
Whilst the venting program runs,
the display shows "EL"
(Vitotronic 100) or "Venting"
(Vitotronic 200).
5692 619 GB
3. Check the system pressure.
8
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Filling the siphon with water
1. Remove the retaining clip and
siphon A.
2. Fill the siphon with water.
3. Fit the siphon A and secure with
the retaining clip.
Setting the time and date (if required) – only for weathercompensated control units
Note
During commissioning, or after a prolonged time out of use, it may be necessary
to reset the time and date, if the time flashes in the display.
Press the following keys:
3. a/b for the current date.
1. a/b for the current time.
4. d
2. d
to confirm.
to confirm; "Date" is displayed.
Language selection (if required) - only for weather-compensated control units
Press the following keys:
3. c Press again.
1. c "Select a heating circuit" will
be displayed.
4. b for the required language.
5. d to confirm.
5692 619 GB
2. d to confirm; wait approx. 4 s.
9
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Pivot down the control unit for commissioning and maintenance work
A Control unit
B Closures
C Flap
D Retaining frame
1. Open flap C.
3. Release the side screws and pivot
control unit A down with its retaining frame D.
5692 619 GB
2. Release side closures B and pivot
control unit A forward.
10
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Checking the gas type
Note
In the delivered condition, the Vitodens 333 is set up for natural gas E.
The boiler can be operated in the Wobbe index range 12.0 to 16.1 kWh/m 3 (43.2
to 58.0 MJ/m 3 ).
1. Determine the gas type and Wobbe
index (Wo) by asking your local
mains gas or LPG supplier.
2. Compare the gas category (type)
and group with the details on the
burner label.
4. When converting to LPG (only
26 kW)
Adjust coding address "1E:1" (see
page 39).
5. Record the gas type in the service
report on page 117.
3. The burner must be converted
according to the details provided
by the mains gas or the LPG supplier to match the fuel provided, if
these details do not match.
Conversion kit installation
instructions.
Wobbe index range after conversion:
& Natural gas LL
10.0 to 13.1 kWh/m 3 (36.0 to
47.2 MJ/m 3 )
& LPG P (only 26 kW)
21.4 to 22.5 kWh/m 3 (76.9 to
81.0 MJ/m 3 )
Gas type conversion
5692 619 GB
Gas restrictor installation
instructions
11
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Gas restrictor allocation
Rated output
Gas restrictor, internal 7
Gas
& Natural gas E
& Natural gas LL
& LPG P
kW
mm
mm
mm
13
26
4.8
5.3
—
5.95
6.73
4.4
Function sequence and possible faults
Display screen
No
Measures
Increase set
value and ensure
heat is drawn off
No
after approx. 51 s
fault F5/F9
Check fan cables
and plugs
No
after approx. 51 s
fault E6/F5
Check fan cables
and plugs, check
fan
No
Fault F4
Check ignition
module (control
voltage 230 V
across plugs
"X2.1" and
"X2.2")
Control unit issues heat demand
Yes
Fan starts
Yes
Differential pressure sensor enables start
(0.75 V across
terminals "X8.5
"and "X8.6")
Yes
5692 619 GB
Ignition
12
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Yes
Gas combination
valve opens
No
Fault F4
Check the gas
combination valve
(control voltage
230 V); check the
gas supply pressure
No
Fault F4
Check ionisation
current, check
electrode adjustment and gas
pipe for airlocks.
Stops below set
boiler water temperature and restarts immediately
Check flue gas
system soundness (flue gas recirculation),
check gas flow
pressure
Yes
Ionisation current builds
(higher than
2 µA)
Symbol A
Yes
Burner starts
No
For further details regarding faults, see page 69.
Checking the static and supply pressure
Danger
CO build-up as a result of incorrect burner setting can have serious
health implications.
Carry out a CO test prior to, and after, work on gas equipment.
5692 619 GB
Operation with LPG (only 26 kW)
Flush the LPG tank twice during commissioning/replacement. Thoroughly vent
the tank and gas lines after flushing.
13
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
4. Record the static pressure and
record it in the service report on
page 117.
Set value: max. 57.5 mbar
5. Start up the boiler.
Note
During commissioning, the boiler
can enter a fault state because of
airlocks in the gas pipe. After
approx. 5 s press "E" to reset the
burner.
6. Check the supply (flow) pressure.
1. Close the gas shut-off valve.
2. Release screw A inside test nipple "PE" on the gas combination
valve, but do not remove it; then
connect the pressure gauge.
3. Open the gas shut-off valve.
Set value:
& Natural gas: 20 mbar
& LPG (only 26 kW): 50 mbar
Note
Use suitable test equipment, with a
resolution of at least 0.1 mbar, to
measure the supply pressure.
7. Record the actual value in the service report on page 117.
Take the action shown in the table.
Supply (flow)
pressure for natural gas
below 17.4 mbar
5692 619 GB
17.4 to 57.5 mbar
in excess of
57.5 mbar
Supply (flow)
Measures
pressure for
LPG (only 26 kW)
below 42.5 mbar
Never start up. Notify your mains gas
or LPG supplier.
42.5 to 57.5 mbar Start up the boiler.
in excess of
Install a separate gas governor down57.5 mbar
stream of the system and regulate the
inlet pressure to 20 mbar for natural
gas or 50 mbar for LPG. Notify your
mains gas or LPG supplier.
14
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
8. Shut down the boiler, close the gas
shut-off valve, remove the pressure
gauge and close test nipple A
with the screw.
9. Open the gas shut-off valve and
start the boiler.
Danger
Gas escaping from the test
nipple leads to a risk of
explosion.
Check test nipple A for
soundness.
Setting the max. output
Note
The maximum output can be limited for heating operation. You can limit the
output via the modulation range.
1. Start up the boiler.
2. Press K + F simultaneously:
"100" flashes (corresponds to 100%
of rated output)
and "A" is displayed.
On weather-compensated control
units, the display
additionally shows
"Max. output".
a/b
for the required
value in % of rated
output as max.
output.
d
to confirm.
3. Record the setting for max. output
on the additional type plate supplied with the "technical documentation". Affix the type plate next to
the type plate on top of the boiler.
5692 619 GB
Checking the balanced flue system soundness (annular gap
check)
For balanced flue systems tested together with the wall mounted gas fired boiler, some authorities waive the requirement for a soundness test (pressure test)
during commissioning by the flue gas inspector.
15
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
We recommend that your heating engineer carries out a simple leak test during
the commissioning of your system. For this it would be sufficient to check the
CO 2 concentration in the combustion air at the annular gap of the balanced flue
pipe.
The flue pipe is deemed to be sound if
the CO 2 concentration in the combustion air is no higher than 0.2 % or the
O 2 concentration is at least 20.6 %.
If actual CO2 values are higher or O 2
values are lower, then pressure check
the flue pipe at a static pressure of
200 Pa.
5692 619 GB
A Combustion air aperture (ventilation air)
16
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Removing the burner and checking the burner gasket
(replace gasket every two years)
A
B
C
D
E
Nuts
Differential pressure sensor
Burner gasket
Gas supply pipe
Gas train
1. Switch OFF the control unit ON/
OFF switch and the power supply.
5692 619 GB
2. Close the gas shut-off valve and
safeguard against reopening.
3. Pull off electrical cables from fan
motor H, differential pressure sensor B, gas valve E, ionisation
electrode F, ignition unit K and
earth stud G.
F
G
H
K
Ionisation electrode
Earth stud
Fan motor
Ignition device
4. Release gas supply pipe fitting D.
5. Release four nuts A and remove
the burner.
!
Please note
Prevent damage to the wire
mesh.
Never rest the burner on the
gauze assembly.
17
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
6. Check the burner gasket C for
damage.
Generally replace the burner gasket every 2 years.
Checking the burner gauze assembly
A Torx screws
B Burner gauze
C Burner gauze gasket
D Ionisation electrode
E Ignition electrodes
1. Remove electrodes D and E.
4. Insert a new burner gauze assembly with a new gasket and secure it
with six Torx screws.
2. Release the six Torx screws A
and remove the burner gauze
assembly B.
3. Remove the old burner gauze gasket C.
18
Note
Torque: 3.5 Nm
5692 619 GB
Replace the burner gauze assembly if the wire mesh is damaged.
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Checking and adjusting the ignition and ionisation electrodes
A Ignition electrodes
B Ionisation electrode
C Gasket
1. Check electrodes A and B for
wear and contamination.
3. Check clearances. If the gaps are
not as specified or the electrodes
are damaged, replace and align the
electrodes together with new gaskets C. Tighten the electrode fixing screws with 2 Nm.
2. Clean the electrodes with a small
brush (not with a wire brush) or
emery paper.
Please note
Never damage the
wire mesh.
5692 619 GB
!
19
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Cleaning the combustion chamber/heating surfaces and fitting the burner
2. Apply a solvent/potassium-free
cleaning agent if residues remain:
& Remove soot deposits with alkaline cleaning agents with additional surfactants (e.g.
Fauch 600).
& Remove coatings and surface
discolouration (yellow-brown)
with slightly acidic, chloride-free
cleaning agents based on phosphoric acid (e.g. Antox 75 E).
& Thoroughly flush with water.
1. If required, clean the combustion
chamber and heating surfaces A
with a brush or flush with water.
!
Please note
Scratches on parts which
are in contact with flue
gases can lead to corrosion.
Only use plastic brushes
and NOT wire brushes.
Note
Fauch 600 and Antox 75 E are supplied by
Hebro Chemie GmbH
Rostocker Straße 40
D 41199 Mönchengladbach
3. Install the burner and torque nuts
diagonally with 4 Nm.
4. Secure the gas supply pipe with a
new gasket.
5. Check the gas connections for
soundness.
Danger
Escaping gas leads to a risk
of explosions.
Check all fittings for soundness.
5692 619 GB
6. Connect the electrical cables/leads
to each corresponding component.
20
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Checking the condensate drain and cleaning the siphon
1. Check that the condensate can
freely drain at siphon A.
2. Remove the retaining clip and the
siphon.
3. Clean the siphon.
4. Fit the siphon and secure with the
retaining clip.
Testing the anode earth current with an anode tester
Note
We recommend that the magnesium anode function is checked annually. This
function test can be carried out without interrupting operation by measuring the
earth current with an anode tester.
1. Remove cover A.
2. Pull earth cable B from push-on
tab C.
5692 619 GB
3. Connect the tester (up to 5 mA) in
series between push-on tab C
and earth cable B.
& The anode is OK if the indicated
current is > 0.3 mA.
& Visually inspect the anode if the
current measures < 0.3 mA or if
there is no current at all (see
page 22).
A Cover
B Earth cable
C Push-on tab
21
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Cleaning the DHW cylinder
Note
DIN 1988 requires a visual inspection and (if necessary) cleaning every two
years after the cylinder has been taken into use and thereafter according to
requirements.
4. Remove loose deposits with a high
pressure cleaner.
!
Please note
Only use plastic utensils for
cleaning the inside of the
cylinder.
5. Use a chemical cleaning agent to
remove hard deposits that cannot
be removed by a high pressure
cleaner.
1. Drain the DHW cylinder.
2. Remove flange lid A.
3. Disconnect the cylinder from the
pipework to prevent contaminants
entering the pipe system.
!
Please note
Never use hydrochloric
cleaning agents.
6. Thoroughly flush the DHW cylinder
after cleaning.
Checking and replacing the magnesium anode (if required)
5692 619 GB
Check the magnesium anode. We recommend you change the magnesium
anode if it has been reduced down to 10 to 15 mm Ø.
22
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Returning the DHW cylinder to use
A Flange lid
B Gasket
C Earth cable
D Push-on tab
1. Reconnect the DHW cylinder to the
pipework.
3. Fit the flange lid and tighten the
screws with a maximum torque of
25 Nm.
2. Insert new gasket B underneath
the flange lid A.
4. Push earth cable C onto push-on
tab D.
5. Fill the cylinder with potable water.
Checking all gas equipment for soundness at operating pressure
5692 619 GB
Danger
Escaping gas leads to a risk of
explosions.
Check gas equipment for
soundness.
23
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Flue gas emissions test
The Vitodens 333 is set up in the factory for natural gas E and can, with the aid
of a conversion kit, be converted to natural gas LL or LPG P (only 26 kW).
During commissioning or maintenance, check the CO 2 level at the flue outlet.
Note
The MatriX burner of the Vitodens 333 is preset for the entire gas group. Therefore, the burner requires no further setting or adjustment.
Subject to the Wobbe index, the CO 2 content fluctuates between
& 6.6 to 10.0% for natural gas E
& 7.0 to 10.0% for natural gas LL
& 8.5 to 10.5% for LPG P (only 26 kW)
Compare the actual CO 2 value with the above CO 2 value ranges for the individual gas groups (check the gas group with your mains gas or LPG supplier).
If the actual CO 2 value deviates by more than 1% for natural gas or 0.5% for
LPG (only 26 kW), proceed as follows:
& Check that the correct gas restrictor has been installed.
& Check the balanced flue system for soundness, see page 16.
Maintain limits to EN 483 and EN 297 (CO content < 1000 ppm).
2. Open the gas shut-off valve, start
the boiler and create a heat
demand.
1. Connect a flue gas analyser at the
flue gas port A on the flue outlet.
24
4. Check the CO 2 content. If the value
lies outside the above range, take
the measures listed on page 24.
5692 619 GB
3. Select the lower rated output.
Constant temperature control
unit:
Press K + d simultaneously:
"1" is shown.
Weather–compensated control
unit:
Press K + d simultaneously:
"Relay test" and
then "Base load" is
shown.
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
5. Record the actual value on
page 117 of the commissioning/
service report.
7. Check the CO 2 content. If the value
lies outside the above range, take
the measures listed on page 24.
6. Select the upper rated output.
Constant temperature control
unit:
Press K + d simultaneously:
"1" is shown.
Press a:
"2" is shown.
Weather–compensated control
unit:
Press K + d simultaneously:
"Relay test" is
shown.
Press a:
"Full load" is
shown.
8. After testing, press d.
5692 619 GB
9. Record the actual value on
page 117 of the commissioning/
service report.
25
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Checking the ionisation current
2. Adjusting the upper output:
Constant temperature control
unit:
Press K + d simultaneously:
"1" is shown.
Press a:
"2" is shown.
Weather–compensated control
unit:
Press K + d simultaneously:
"Relay test" is
shown in the display.
Press a:
"Full load" is
shown in the display.
A Adaptor line (accessories)
1. Connect the test instrument
according to the adjacent diagram.
3. Ionisation current when the flame is
first established: min. 2 µA
Steps to take if the ionisation current < 2 µA:
& Check the electrode gap, see
page 19.
& Check the control unit power supply.
5692 619 GB
4. Press d.
Operation with the upper rated output is terminated.
26
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
5. Record the actual value in the service report on page 117.
Matching the control unit to the heating system
Note
The control unit must be matched to the system equipment. Various system
components are recognised automatically by the control unit and the relevant
codes adjusted automatically.
& For the selection of an appropriate design, see the following diagrams.
& For coding steps, see page 39.
System version 1
5692 619 GB
One heating circuit without mixer A1
! Outside temperature sensor (only
for control units for weather-compensated operation)
or
lH Vitotrol 100 (only for constant
temperature control units)
27
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Required coding
Operation with LPG
1E:1
System version 2
One heating circuit with mixer M2 and a low loss header
!
?
sÖ
lH
aVG
Outside temperature sensor
Flow temperature sensor
Heating circuit pump
Power supply (extension kit)
KM BUS
A
B
C
Low loss header
Extension kit for a heating circuit
with mixer
Maximum temperature thermostat (underfloor heating)
1E:1
00:4
5692 619 GB
Required coding
Operation with LPG
System with only one heating circuit with mixer and DHW heating
28
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
System version 3
One heating circuit without mixer A1 and one heating circuit with mixer M2
!
?
sÖ
lH
aVG
Outside temperature sensor
Flow temperature sensor
Heating circuit pump
Power supply (extension kit)
KM BUS
A
B
Maximum temperature thermostat (underfloor heating)
Extension kit for a heating circuit
with mixer
Note
The flow rate of the heating circuit without mixer must be at least 30% greater
than the flow rate of the heating circuit with mixer.
1E:1
5692 619 GB
Required coding
Operation with LPG
29
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
System version 4
One heating circuit without mixer A1, one heating circuit with mixer M2
and system separation
!
?
sÖ
lH
aVG
Outside temperature sensor
Flow temperature sensor
Heating circuit pump
Power supply (extension kit)
KM BUS
B
C
Extension kit for a heating circuit
with mixer
Maximum temperature thermostat (underfloor heating)
Heat exchanger for system
separation
1E:1
5692 619 GB
Required coding
Operation with LPG
A
30
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
System version 5
One heating circuit with mixer M2 (with extension kit), one heating circuit
with mixer (with the Vitotronic 050) and low loss header
!
?
sÖ
lH
aVG
A
Outside temperature sensor
Flow temperature sensor
Heating circuit pump
Power supply (extension kit)
KM BUS
Low loss header
B
C
D
Extension kit for a heating circuit
with mixer
Vitotronic 050
Maximum temperature thermostat (underfloor heating)
1E:1
00:4
5692 619 GB
Required coding
Operation with LPG
System with only one heating circuit with mixer and DHW heating
31
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Adjusting the heating curves (only for control units for
weather-compensated operation)
The heating curves illustrate the relationship between the outside temperature and the boiler water or the
flow temperature.
To put it simply: The lower the outside
temperature, the higher the boiler
water or flow temperature.
The room temperature, again,
depends on the boiler water or the
flow temperature.
A Heating curve slope for underfloor
heating systems
B Heating curve slope for low temperature heating systems
(according to the Energy Savings
Order [Germany])
5692 619 GB
Settings in the delivered condition:
& Slope = 1.4
& Level = 0
32
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Changing slope and level
1. Change the slope with coding
address "d3" in code 1 (see
page 39).
Setting range 2 to 35 (equals slope
0.2 to 3.5).
2. Change the level in coding address
"d4" in code 1 (see page 39).
Setting range -13 to +40 K.
5692 619 GB
A Changing the slope
B Changing the level (vertical parallel offset of the heating curve)
33
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Adjusting the set room temperature
Standard room temperature
Press the following keys:
1. a "1r" flashes.
2. d to select heating circuit A1
(heating circuit without mixer)
or
3. a "2r" flashes.
4. d to select heating circuit M2
(heating circuit with mixer)
Example 1: Adjustment of the standard room temperature from 20 °C to
26 °C
5692 619 GB
A Boiler water temperature or flow
temperature in °C
B Outside temperature in °C
C Set room temperature in °C
D Heating circuit pump "OFF"
E Heating circuit pump "ON"
5. Adjust the set day temperature with
rotary selector "ts".
The value will be automatically
accepted after approx. 2 s.
Accordingly, the heating curve is
adjusted along the set room temperature axis, which results in
modified start-up/shutdown characteristics of the heating circuit
pumps if heating circuit pump logic
is active.
34
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Reduced room temperature
Press the following keys:
1. a
"1r" flashes.
2. d
to select heating circuit A1
(heating circuit without
mixer)
or
3. a
"2r" flashes.
4. d
to select heating circuit M2
(heating circuit with mixer)
5. E
Calling up the set night
temperature.
Example 2: Adjustment of the reduced
room temperature from 5 °C to 14 °C
A Boiler water temperature or flow
temperature in °C
B Outside temperature in °C
C Set room temperature in °C
D Heating circuit pump "OFF"
E Heating circuit pump "ON"
6. a/b Change the value.
7. d
Confirm the value.
Connecting the control unit to the LON system (only for
weather-compensated control units)
The LON communication module (accessories) must be plugged in.
Installation instructions
LON communication module
Note
The data transfer via the LON system can take 2 to 3 min.
Setting up LON user numbers
In a LON system, the same number
cannot be allocated twice.
5692 619 GB
Adjust the user number via coding
address "77" (see the following table).
35
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Updating the LON user list
Note
Only possible if all users are connected and the control unit is programmed to
be fault manager (code "79:1").
Press the following keys:
1. L + d simultaneously for
approx. 2 s
User check initiated (see
page 37).
2. e
The user list is updated
after approx. 2 min.
The user check is completed.
Single boiler system with Vitotronic 050 and Vitocom 300
Note
In each heating system, only one Vitotronic may be programmed as fault manager.
Boiler control
unit
Vitotronic 050
Vitotronic 050
Vitocom
User no. 1
Code "77: 1"
Control unit is
fault manager
Set code "79: 1"
Send time via
LON
Code "7b: 1"
Transmit outside
temperature via
LON
Set code "97: 2"
Fault monitoring
LON user code
"9C:20"
User no. 10
Set code "77: 10"
Control unit is not
fault manager
Code "79: 0"
Time received via
LON
Set code "81: 3"
The outside temperature is received via LON
Set code "97: 1"
Fault monitoring
LON user code
"9C:20"
User no. 11
Set code "77: 11"
Control unit is not
fault manager
Code "79: 0"
Time received via
LON
Set code "81: 3"
The outside temperature is received
via LON
Set code "97: 1"
Fault monitoring
LON user code
"9C:20"
User no. 99
36
Control unit is
fault manager
Time received
via LON
—
5692 619 GB
—
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Implementing a user check (in conjunction with the LON system with a weather-compensated control unit)
Communication with the system devices connected to the fault manager is
tested with a user check.
Preconditions:
& The control unit must be programmed as fault manager (code "79:1").
& The LON user number must be programmed in all control units (see page 35).
& The fault manager LON user list must be up to date (see page 35).
3. d
A Consecutive number in the user
list
B User number
Press the following keys:
1. L + d simultaneously for
approx. 2 s
The user check has been
initiated.
2. a/b
Activating a check.
"Check" flashes until its
completion. The display
and all key illuminations
for the selected user
flash for approx. 60 s.
& "Check OK" is displayed during communication between both
devices.
& "Check not OK" is displayed if there is no
communication
between both devices;
check the LON connection.
4. Repeat points 2 and 3 to check
further users.
for the required user.
5. L + d simultaneously for
approx. 1 s
The user check is completed.
5692 619 GB
Instructing the system user
The system installer must hand the operating instructions to the system user
and instruct him/her in the operation of the system.
37
Initial start-up, inspection, maintenance
Further details regarding the individual steps (cont.)
Scanning and resetting the "maintenance" display
The red fault indicator flashes when the limits set via coding addresses "21" and
"23" have been reached. As regards the programming unit display:
& For a constant temperature control unit:
The defaulted hours run or the defaulted interval with clock symbol "u" (subject to setting)
& For a weather-compensated control unit:
"Maintenance"
Note
Set code "24:1" and then code "24:0" if maintenance is carried out before maintenance is displayed; the set maintenance parameters for hours run and intervals are then reset to 0.
Press the following keys:
1. c
3. d
The maintenance scan is
active.
2. a/b Scan maintenance messages.
The maintenance display
will be cleared (for a
weather-compensated
control unit: "Acknowledge:
Yes" re-confirm with d).
The red fault display continues to flash.
Note
An acknowledged maintenance message can be redisplayed by pressing
d (approx. 3 s).
1. Reset code "24:1" to "24:0".
The red fault indicator extinguishes.
Note
A new maintenance message will
be displayed 7 days later, if coding
address "24" is not reset.
38
2. Reset the burner hours run, burner
starts and consumption, if required
Press the following keys:
c
Scanning is active (see
page 67).
a/b for the selected value.
e
the selected value will be
set to "0".
a/b for further scans.
d
Scanning is completed.
5692 619 GB
After maintenance has been carried out
Coding
Code 1
Calling up code 1
Note
& On weather-compensated control
units, codes are displayed as plain
text.
& Codes which are irrelevant (due to
the system equipment level or the
setting of other codes) will not be
displayed.
& For heating systems with one heating circuit without mixer and one
heating circuit with mixer, initially
the possible coding addresses "A0"
to "d4" are scrolled for the heating
circuit without mixer A1 and then
those for the heating circuit with
mixer M2.
Press the following keys:
1. K + L simultaneously for
approx. 2s.
2. a/b
for the required coding
address; the address
flashes.
3. d
to confirm.
4. a/b
for the selected value.
5. d
to confirm; the display
briefly shows "accepted"
(weather-compensated
control unit); the address
flashes again.
6. a/b
for the selection of further
addresses.
7. K + L simultaneously for
approx. 1 s to terminate
code 1.
Summary
Coding
Coding in the delivered condition
System designs
00:2
System version 1:
1 heating circuit without
mixer A1, with DHW
heating
Possible change
00:4
5692 619 GB
00:6
System version 2, 5:
1 heating circuit with
mixer M2, with DHW
heating
System version 3, 4:
1 heating circuit without
mixer A1 and 1 heating
circuit with mixer M2, with
DHW heating
39
Coding
Code 1 (cont.)
Coding in the delivered condition
Max. boiler temp.
06:...
Maximum limit of the
boiler water temperature, defaulted in °C by
the boiler coding card
Gas type
1E:0
Operation with natural
gas
Venting/filling
2F:0
Program enabled
Possible change
06:20
to
06:127
Maximum limit of the boiler water temperature
within the ranges defaulted by the boiler
1E:1
Operation with LPG
2F:1
Ventilation program disabled
Filling program enabled
2F:2
User no.
77:1
LON user number (only
for weather-compensated control units)
77:2
to
77:99
LON user number, adjustable from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - 98 = Vitotronic 050
99 = Vitocom
Summer econ. A1/M2
A5:5
With heating circuit
logic function (only for
weather-compensated
control units)
Min. flow temp. A1/M2
C5:20
Electronic minimum
limit of the flow temperature 20 °C (only for
weather-compensated
control units)
Max. flow temp. A1/M2
C6:75
Electronic maximum
limit of the flow temperature 75 °C (only for
weather-compensated
control units)
40
A5:0
Without heating circuit
pump logic function
C5:1
to
C5:127
Minimum limit adjustable
from 1 to 127 °C
C6:10
to
C6:127
Maximum limit adjustable
from 10 to 127 °C
5692 619 GB
Note
Allocate each number
once only.
Coding
Code 1 (cont.)
Coding in the delivered condition
Slope A1/M2
d3:14
Heating curve slope =
1.4 (only for weathercompensated control
units)
Level A1/M2
d4:0
Heating curve slope = 0
(only for weather-compensated control units)
Possible change
d3:2
to
d3:35
Heating curve slope adjustable from 0.2 to 3.5
(see page 32)
d4:–13
to
d4:40
Heating curve level adjustable from –13 to 40
(see page 32)
Code 2
Calling up code 2
Note
& On weather-compensated control
units, codes are displayed as plain
text.
& Codes, which are irrelevant (due to
the system equipment level or the
setting of other codes) will not be
displayed.
4. d
to confirm; the value
flashes.
5. a/b
for the selected value.
6. d
to confirm; the display
briefly shows
"accepted" (for
weather-compensated
control units); the
address flashes again.
7. a/b
for the selection of
further addresses.
Press the following keys:
1. L + G simultaneously for
approx. 2s.
2. d
to confirm.
3. a/b
for the required coding
address; the address
flashes.
8. L + G simultaneously for
approx. 1 s to terminate
code 2.
5692 619 GB
Overall summary
The coding addresses are grouped according to the following function areas.
The respective function area is shown on the display.
41
Coding
Code 2 (cont.)
The areas are scanned in the following sequence with a/b:
Function area
System design
Boiler/burner
DHW
General
Heating circuit A1 (heating circuit without
mixer)
Heating circuit M2 (heating circuit with
mixer)
Coding addresses
00
06 to 54
56 to 73
76 to 9F
A0 to Fb
A0 to Fb
Note
For heating systems with one heating circuit without mixer and one heating circuit with mixer, initially the possible coding addresses "A0" to "Fb" are scrolled
for the heating circuit without mixer A1 and then those for the heating circuit
with mixer M2.
Coding
Possible change
00:4
00:6
Boiler/burner
06:...
Maximum limit of the
boiler water temperature, defaulted in °C by
the boiler coding card
1E:0
Operation with natural
gas
21:0
No burner maintenance
indication
42
06:20
to
06:127
1E:1
21:1
to
21:9999
System version 2, 5:
1 heating circuit with
mixer M2, with DHW
heating
System version 3, 4:
1 heating circuit without
mixer A1 and 1 heating
circuit with mixer M2, with
DHW heating
Maximum limit of the boiler water temperature
within the ranges defaulted by the boiler
Operation with LPG
The number of hours to
run before the burner
should be serviced is adjustable from 1 to 9999 h
5692 619 GB
Coding in the delivered condition
System designs
00:2
System version 1:
1 heating circuit without
mixer A1, with DHW
heating
Coding
Code 2 (cont.)
Coding in the delivered condition
23:0
No time interval for
burner maintenance
24:0
No "Maintenance" display
25:0
i: No outside temperature sensor or fault
monitoring recognised
(only for constant temperature control units)
No burner interval ignition
Without external extension
Program disabled
28:0
2E:0
2F:0
30:1
Internal variable speed
circulation pump (automatic adjustment)
31:...
Set speed of the internal circulation pump
when operated as boiler
circuit pump in %, defaulted by the boiler
coding card
Influence of the signal
"External blocking" on
the circulation pumps:
All pumps in control
function
28:1
2E:1
2F:1
2F:2
30:0
31:0
to
31:100
32:1
to
32:15
The burner will be forcestarted for 30 s after 5 h
With external extension
(automatic recognition)
Ventilation program enabled
Filling program enabled
Internal circulation pump
without variable speed
(e.g. temporarily for service)
Set speed adjustable
from 0 to 100 %
Influence of the signal
"External blocking" on
the circulation pumps:
see the following table
5692 619 GB
32:0
Possible change
23:1
Interval adjustable from 1
to
to 24 months
23:24
24:1
"Maintenance" display
(the address is automatically set and must be
manually reset after a
service has been carried
out)
25:1
Outside temperature sensor and fault monitoring
recognised
43
Coding
Code 2 (cont.)
Internal circulation pump
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Control funct.
Control funct.
Control funct.
Control funct.
Control funct.
Control funct.
Control funct.
Control funct.
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Heating circuit
pump
Heating circuit
without mixer
Control funct.
Control funct.
Control funct.
Control funct.
OFF
OFF
OFF
OFF
Control funct.
Control funct.
Control funct.
Control funct.
OFF
OFF
OFF
OFF
Coding in the delivered condition
Boiler/burner
34:0
Influence of the signal
"External demand" on
the circulation pumps:
All pumps in control
function
Coding
Internal circulation pump
0
1
2
3
4
5
6
Control funct.
Control funct.
Control funct.
Control funct.
Control funct.
Control funct.
Control funct.
44
Heating circuit
pump
Heating circuit
with mixer
Control funct.
Control funct.
OFF
OFF
Control funct.
Control funct.
OFF
OFF
Control funct.
Control funct.
OFF
OFF
Control funct.
Control funct.
OFF
OFF
Cylinder primary pump
Control funct.
OFF
Control funct.
OFF
Control funct.
OFF
Control funct.
OFF
Control funct.
OFF
Control funct.
OFF
Control funct.
OFF
Control funct.
OFF
Possible change
34:1
to
34:23
Heating circuit
pump
Heating circuit
without mixer
Control funct.
Control funct.
Control funct.
Control funct.
OFF
OFF
OFF
Influence of the signal
"External demand" on the
circulation pumps: see
the following table
Heating circuit
pump
Heating circuit
with mixer
Control funct.
Control funct.
OFF
OFF
Control funct.
Control funct.
OFF
Cylinder primary pump
Control funct.
OFF
Control funct.
OFF
Control funct.
OFF
Control funct.
5692 619 GB
Coding
Coding
Code 2 (cont.)
Coding
Internal circulation pump
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
Control funct.
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
Heating circuit
pump
Heating circuit
without mixer
OFF
Control funct.
Control funct.
Control funct.
Control funct.
OFF
OFF
OFF
OFF
Control funct.
Control funct.
Control funct.
Control funct.
OFF
OFF
OFF
OFF
Coding in the delivered condition
Boiler/burner
52:0
Without flow temperature sensor for low loss
header
54:0
Without solar control
unit
Heating circuit
pump
Heating circuit
with mixer
OFF
Control funct.
Control funct.
OFF
OFF
Control funct.
Control funct.
OFF
OFF
Control funct.
Control funct.
OFF
OFF
Control funct.
Control funct.
OFF
OFF
Cylinder primary pump
OFF
Control funct.
OFF
Control funct.
OFF
Control funct.
OFF
Control funct.
OFF
Control funct.
OFF
Control funct.
OFF
Control funct.
OFF
Control funct.
OFF
Possible change
52:1
54:1
5692 619 GB
54:2
With flow temperature
sensor for low loss header (automatic recognition)
With Vitosolic 100 (automatic recognition)
With Vitosolic 200 (automatic recognition)
45
Coding
Code 2 (cont.)
Coding in the delivered condition
Domestic hot water
56:0
Set DHW temperature
adjustable from 10 to
60 °C
Possible change
56:1
Set DHW temperature
adjustable from 10 to
above 60 °C
Note
Maximum value subject
to boiler coding card
Observe the max. permissible DHW temperature
Without auxiliary function for DHW heating
58:10
to
58:60
63:0
No default interval for
auxiliary function for
DHW heating (only for
constant temperature
control units)
63:1
65:...
Information regarding
the type of diverter
valve; do not adjust.
67:40
With the Vitosolic:
third set DHW temperature 40 °C
6C:100
6F:...
46
Set speed of the internal cylinder primary
pump 100 %
Maximum output for
DHW heating in %; defaulted by the boiler
coding card
63:2
to
63:14
63:15
65:0
65:1
65:2
65:3
67:0
67:1
to
67:60
6C:0
to
6C:100
6F:0
to
6F:100
Input of a second set
DHW value, adjustable
from 10 to 60 °C (observe
the coding addresses
"56" and "63")
Auxiliary function for
DHW heating, 1 x daily
Every 2 days to every 14
days
2 x daily
Without diverter valve
Viessmann diverter valve
Wilo diverter valve
Grunfos diverter valve
Without third set DHW
temperature
Third set DHW temperature adjustable from 1 to
60 °C (subject to the setting of coding address
"56")
Set speed adjustable
from 0 to 100 %
Max. output during DHW
heating adjustable from
min. output to 100 %
5692 619 GB
58:0
Coding
Code 2 (cont.)
Coding in the delivered condition
71:0
DHW circulation pump:
"ON" subject to DHW
time program (for the
Vitotrol 300, separate
switching times are
possible) (only for
weather-compensated
control units)
72:0
DHW circulation pump:
"ON" in accordance
with the DHW time program (only for weathercompensated control
units)
73:0
DHW circulation pump:
"ON" in accordance
with the DHW time program (only for weathercompensated control
units)
General
76:0
Without LON communication module (only for
weather-compensated
control units)
77:1
LON user number (only
for weather-compensated control units)
Possible change
71:1
"OFF" during DHW heating to the first set value
71:2
"ON" during DHW heating to the first set value
72:1
72:2
73:1
to
73:6
73:7
"OFF" during DHW heating to the second set
value
"ON" during DHW heating to the second set
value
During the time program
1x/h "ON" for 5 min
up to 6x/h "ON" for 5 min
Permanently "ON"
76:1
With LON communication
module (automatic recognition)
77:2
to
77:99
LON user number, adjustable from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - 98 = Vitotronic 050
99 = Vitocom
Note
Allocate each number
once only.
5692 619 GB
79:0
The control unit is not
the fault manager (only
for weather-compensated control units)
79:1
Control unit is fault manager
47
Coding
Code 2 (cont.)
Coding in the delivered condition
7b:1
Without LON communication module (only for
weather-compensated
control units)
7F:1
Detached house (only
for weather-compensated control units)
Possible change
7b:0
Do not send time via LON
7F:0
80:1
A fault message is dis80:0
played, providing a fault 80:2
is active for at least 5 s to
80:199
81:1
Automatic summer/winter time changeover
81:0
81:2
88:0
81:3
88:1
90:1
to
90:199
Fast (low values) or slow
(high values) matching of
the flow temperature,
subject to set value when
the outside temperature
changes;
1 step = 10 min
5692 619 GB
8A:175
90:128
Temperature displayed
in °C (Celsius)
Do not adjust
Time constant for calculating the adjusted outside temperature 21.3 h
Apartment block
As option, separate adjustment of holiday program and time program
for DHW heating
Immediate fault message
The minimum fault duration before a fault message is issued is
adjustable from 10 s to
995 s; 1 step = 5 s
Manual summer/winter
time changeover
Use of the radio clock receiver (automatic recognition)
Accept time via LON
Temperature displayed in
°F (Fahrenheit)
48
Coding
Code 2 (cont.)
5692 619 GB
Coding in the delivered condition
Possible change
91:0
No external heating pro- 91:1
The external heating program changeover via
gram changeover affects
external extension (only
the heating circuit without
for weather-compenmixer
sated control units)
91:2
The external heating program changeover affects
the heating circuit with
mixer
91:3
The external heating program changeover affects
the heating circuit without
mixer and the heating circuit with mixer
95:0
Without Vitocom 100
95:1
With Vitocom 100 comcommunication intermunication interface
face
(automatic recognition)
97:1
The outside temperature
97:0
The outside temperais accepted by the LON
ture of the sensor conBUS
nected to the control
unit is utilised internally 97:2
The outside temperature
(only for weather-comof the sensor connected
pensated control units)
to the control unit will be
utilised internally and is
transmitted via the LON
BUS to any connected
Vitotronic 050.
System number adjusta98:1
98:1
Viessmann system
ble from 1 to 5
number (in conjunction to
98:5
with monitoring of several systems via
Vitocom 300)
Minimum set boiler water
9b:1
9b:0
Minimum set boiler
temperature adjustable
to
water temperature for
from 1 to 127 °C
9b:127
external demand
49
Coding
Code 2 (cont.)
Possible change
9C:0
No monitoring
9C:5
The time is adjustable
to
from 5 to 60 min
9C:60
9F:0
to
9F:40
Differential temperature
adjustable from 0 to 40 K
A0:1
With Vitotrol 200 (automatic recognition)
With Vitotrol 300 (automatic recognition)
A0:2
5692 619 GB
Coding in the delivered condition
9C:20
Monitoring LON users.
If a user fails to respond, the values defaulted inside the
control unit will be used
after 20 min. Only then
will a fault message be
issued (only for weather-compensated control
units)
9F:8
Differential temperature
8 K; only in conjunction
with the mixer circuit
(only for weather-compensated control units)
Heating circuit A1/M2
A0:0
Without remote control
(only for weather-compensated control units)
50
Coding
Code 2 (cont.)
Coding in the delivered condition
A3:2
Outside temperature
below 1 °C: Heating circuit pump "ON"
Outside temperature
above 3 °C: Heating circuit pump "OFF"
5692 619 GB
!
Parameters
Address A3:...
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
1
2
to
15
Possible change
A3:–9
Heating circuit pump
to
"ON/OFF" (see the folA3:15
lowing table)
Please note
When selecting a
value below 1 °C
there is a risk of
pipes outside the
thermal envelope
of the house
being damaged
by frost.
The standby
mode, in particular, should be
taken into consideration, e.g.
during holidays.
Heating circuit pump
"ON"
-10 °C
-9 °C
-8 °C
-7 °C
-6 °C
-5 °C
-4 °C
-3 °C
-2 °C
-1 °C
0 °C
1 °C
to
14 °C
"OFF"
-8 °C
-7 °C
-6 °C
-5 °C
-4 °C
-3 °C
-2 °C
-1 °C
0 °C
1 °C
2 °C
3 °C
16 °C
51
Coding
Code 2 (cont.)
Coding in the delivered condition
Heating circuit A1/M2
A4:0
With frost protection
(only for weather-compensated control units)
Possible change
A4:1
No frost protection; this
setting is only possible if
code "A3:-9" has been
selected.
Note
Observe the note for
code "A3".
A5:5
With heating circuit
pump logic function
(economy circuit): Heating circuit pump "OFF"
when the outside temperature (AT) is 1 K
higher than set room
temperature (RT Set )
AT > RTSet + 1 K (only
for weather-compensated control units)
A5:1
to
A5:15
Without heating circuit
pump logic function
With heating circuit pump
logic function: Heating
circuit pump "OFF" (see
the following table)
With heating circuit pump logic function: Heating
circuit pump "OFF"
AT > RTSet + 5 K
AT > RTSet + 4 K
AT > RTSet + 3 K
AT > RTSet + 2 K
AT > RTSet + 1 K
AT > RTSet
AT > RTSet -v1 K
AT > RTSet - 9 K
5692 619 GB
Parameter address
A5:...
1
2
3
4
5
6
7
to
15
A5:0
52
Coding
Code 2 (cont.)
Coding in the delivered condition
Heating circuit A1/M2
A6:36
Extended economy
function disabled (only
for weather-compensated control units)
Possible change
A6:5
to
A6:35
A7:0
Without mixer economy A7:1
function (only for weather-compensated control
units)
A8:1
Heating circuit with
mixer M2 creates a demand for the internal
circulation pump (only
for weather-compensated control units)
5692 619 GB
A8:0
Extended economy function enabled, i.e. the
burner and heating circuit
pump will be switched
OFF and the mixer will be
closed at a variable
value, which is adjustable
between 5 and 35 °C plus
1 °C. This value is based
on the adjusted outside
temperature, comprising
the actual outside temperature and a time constant, which takes the
cooling down of an average building into consideration.
With mixer economy
function (extended heating circuit pump logic):
Heating circuit pump also
"OFF":
If a mixer has been
closed for longer than
20 min.
Heating pump "ON":
& If the mixer changes to
control mode
& After cylinder heating
(for 20 min)
& If there is a risk of frost
Heating circuit M2 creates no demand for the
internal circulation pump
53
Coding
Code 2 (cont.)
Possible change
A9:0
Without pump idle period
A9:1
With pump idle period,
to
adjustable from 1 to 15
A9:15
b0:1
b0:2
b0:3
b2:8
b5:0
54
With remote control unit
and for the heating circuit, heating with room
temperature hook-up
must be encoded:
Room influence factor 8
(only for weather-compensated control units;
change the coding only
for the heating circuit
with mixer M2)
With remote control: No
room temperature-dependent heating circuit
pump logic function
(only for weather-compensated control units;
change the coding only
for the heating circuit
with mixer M2)
b2:0
b2:1
to
b2:64
b5:1
to
b5:8
Heating mode: weathercompensated
Reduced mode: with
room temperature hookup
Heating mode: with room
temperature hook-up
Reduced mode: weathercompensated
Heating mode/reduced
mode: with room temperature hook-up
Without room influence
Room influence factor
adjustable from 1 to 64
Heating circuit pump
logic function, see the following table:
5692 619 GB
Coding in the delivered condition
A9:7
With pump idle period:
Heating circuit pump
"OFF" when the set
value changes through
a change in operating
mode or through a
change in the set room
temperature (only for
weather-compensated
control units)
b0:0
With remote control:
Heating mode/reduced
mode: weather-compensated (only for
weather-compensated
control units; change
the coding only for the
heating circuit with
mixer M2)
Coding
Code 2 (cont.)
Parameter address b5:...
1
2
3
4
5
6
7
8
With heating circuit pump logic function:
Heating circuit pump "OFF" Heating circuit pump "ON"
RTActual > RT Set + 5 K
RTActual < RT Set + 4 K
RTActual > RT Set + 4 K
RTActual < RT Set + 3 K
RTActual < RT Set + 2 K
RTActual > RT Set + 3 K
RTActual < RT Set + 1 K
RTActual > RT Set + 2 K
RTActual < RT Set
RTActual > RT Set + 1 K
RTActual > RT Set
RTActual < RT Set - 1 K
RTActual < RT Set - 2 K
RTActual > RT Set - 1 K
RTActual < RT Set - 3 K
RTActual > RT Set - 2 K
Possible change
C5:1
to
C5:127
Minimum limit adjustable
from 1 to 127 °C
C6:10
to
C6:127
Maximum limit adjustable
from 10 to 127 °C
d3:2
to
d3:35
Heating curve slope adjustable from 0.2 to 3.5
(see page 32)
d4:–13
to
d4:40
d5:1
Heating curve level adjustable from –13 to 40
(see page 32)
The external heating program changeover
changes the heating program to "Constant central
heating with standard
room temperature"
5692 619 GB
Coding in the delivered condition
Heating circuit A1/M2
C5:20
Electronic minimum
limit of the flow temperature 20 °C (only for
weather-compensated
control units)
C6:74
Electronic maximum
limit of the flow temperature 74 °C (only for
weather-compensated
control units)
d3:14
Heating curve slope =
1.4 (only for weathercompensated control
units)
d4:0
Heating curve slope = 0
(only for weather-compensated control units)
d5:0
The external heating
program changeover
changes the heating
program to "Constant
operation with reduced
room temperature"
(only for weather-compensated control units)
55
Coding
Code 2 (cont.)
Possible change
E1:0
Set day temperature adjustable from 3 to 23 °C
E1:2
Set day temperature adjustable from 17 to 37 °C
E2:0
to
E2:49
E2:51
to
E2:99
E5:1
Display correction –5 K
to
display correction -0.1 K
Display correction +0.1 K
to
display correction +4.9 K
With external variable
speed heating circuit
pump (automatic recognition)
E6:0
to
E6:100
Maximum speed adjustable from 0 to 100 %
E7:0
to
E7:100
Minimum speed adjustable from 0 to 100 % of
max. speed
E8:0
Speed subject to the setting in coding address
"E7"
5692 619 GB
Coding in the delivered condition
E1:1
With remote control:
The set day temperature is adjustable at the
remote control unit from
10 to 30 °C (only for
weather-compensated
control units)
E2:50
With remote control: No
display correction for
the actual room temperature (only for
weather-compensated
control units)
E5:0
Without variable speed
external heating circuit
pump (only for weathercompensated control
units)
E6:100
Maximum speed of the
external variable speed
heating circuit pump:
100 % of the speed in
standard mode (only for
weather-compensated
control units)
E7:30
Minimum speed of the
external variable speed
heating circuit pump:
30 % of the maximum
speed (only for weather-compensated control
units)
E8:1
Minimum speed in operation with reduced
room temperature subject to the setting of
coding address "E9"
(only for weather-compensated control units)
56
Coding
Code 2 (cont.)
Coding in the delivered condition
E9:45
Speed of the external
variable speed heating
circuit pump: 45 % of
the maximum speed in
reduced temperature
mode (only for weathercompensated control
units)
F2:8
Time limit for party
mode 8 h or external
heating program changeover via the keyboard
(only for weather-compensated control units)
Possible change
E9:0
Speed adjustable from 0
to
to 100 % of maximum
E9:100
speed during operation
with reduced room temperature
F2:0
F2:1
to
F2:12
No time limit for party
mode * 1
Time limit adjustable from
1 to 12 h* 1
*1
F5:12
F6:25
5692 619 GB
F7:25
Run-on time of the internal circulation pump in
heating mode (only for
constant temperature
control units)
In the "DHW only" operating mode, the internal
circulation pump is permanently ON (only for
weather-compensated
control units)
F5:0
In the "Standby" operating mode, the internal
circulation pump is permanently ON (only for
constant temperature
control units)
F7:0
F5:1
to
F5:20
F6:0
F6:1
to
F6:24
F7:1
to
F7:24
No run-on time of the internal circulation pump
Run-on time of the internal circulation pump adjustable from 1 to 20 min
In the "DHW only" operating mode, the internal circulation pump is
permanently OFF
In the "DHW only" operating mode, the internal circulation pump will be
started 1 to 24 times per
day for 10 min respectively.
In "Standby mode", the
internal circulation pump
is permanently OFF
In the "Standby" mode,
the internal circulation
pump in operating mode
will be started 1 to 24
times per day for 10 min
respectively.
mode ends automatically in the "Heating and DHW" program, when the system
changes over to operation with standard room temperature.
*1 Party
57
Coding
Code 2 (cont.)
Possible change
F8:+10
Temperature limit adjusto
table from
F8:–60
+10 to -60 °C
F8:–61
Function disabled
F9:+10
to
F9:–60
Temperature limit adjustable from
+10 to -60 °C
FA:0
to
FA:50
Temperature rise adjustable from 0 to 50%
Fb:0
to
Fb:150
Duration adjustable from
0 to 300 min;
1 step ≙ 2 min)
5692 619 GB
Coding in the delivered condition
F8:–5
Temperature limit for
terminating the reduced
mode -5 ºC, see example on page 103.
Observe the setting of
coding address "A3".
(only for weather-compensated control units)
F9:–14
Temperature limit for
raising the reduced set
room temp. -14 ºC, see
example on page 103
(only for weather-compensated control units)
FA:20
Raising the set boiler
water temperature or
the set flow temperature
when changing from operation with reduced
room temperature to operation with standard
room temperature by
20 %. See example on
page 104 (only for
weather-compensated
control units).
Fb:30
Duration for raising the
set boiler water temperature or the set flow
temperature (see coding address "FA")
60 min. See example on
page 104 (only for
weather-compensated
control units).
58
Coding
Code 2 (cont.)
Coding in the delivered condition
Heating circuit M2
F1:0
Screed drying function
disabled (only for
weather-compensated
control units)
Possible change
F1:1
to
F1:5
Screed drying function
adjustable in accordance
with five optional temperature/time profiles
(see page 101)
Note
Observe the screed supplier's instructions.
5692 619 GB
F1:6
to
F1:15
Observe DIN 4725–2.
The report to be provided
by the heating contractor
must contain the following heat-up details:
& Heat-up data with
respective flow temperatures
& Max. flow temperature
achieved
& Operating condition
and outside temperature during handover
The function continues
after a power failure or
after the control unit has
been switched OFF.
Heating program "Heating and DHW" will be
started after the screed
function has been terminated or if the address is
manually set to 0.
Constant flow temperature 20 °C
59
Coding
Resetting codes to the delivered condition
Press the following keys:
3. d
to confirm
or
1. L + G simultaneously for
approx. 2s
4. a/b
to select "Basic setting?
No".
"Basic settings? Yes" is
displayed.
5692 619 GB
2. e
60
Service scans
Service level summary
Function
Temperatures, boiler coding card, brief scans
Relay test
5692 619 GB
Max. output (heating
mode)
Operating conditions and
sensors
Maintenance scan
Key combination
K and G simultaneously
for approx. 2 s
K and d simultaneously
for approx. 2 s
K and F simultaneously
for approx. 2 s
Press c
Exit
Press d
Page
62
Press d
66
Press d
15
Press d
67
c (if "Maintenance"
Press d
flashes)
Adjusting the display con- d and a simultaneously; –
trast
the display darkens
d and b simultaneously; –
the display becomes lighter
Calling up acknowledged d for approx. 3 s
fault messages
Fault history
G and d simultaneously Press d
for approx. 2 s
User check (in conjuncL and d simultaneously Press L
tion with LON system)
for approx. 2 s
and d simultaneously
F and E
Emissions test function
Weather–compensated
or O and
"S"
control unit:
F simultaF and E simultaneously for
neously for approx. 2 s
Constant temperature con- approx. 1 s,
alternatively
trol unit:
will be seO and F simultalected autoneously for approx. 2 s
matically
after 30 min
Coding level 1
K and L simultaneously K and L
for approx. 2 s
simultaneously for
approx. 1 s
Coding level 2
L and G simultaneously L and G
for approx. 2 s
simultaneously for
approx. 1 s
38
–
–
70
71
37
–
39
41
61
Service scans
Service level summary (cont.)
Function
Resetting codes to the
delivered condition
Key combination
Exit
L and G simultaneously –
for approx. 2 s; press e
Page
60
Temperatures, boiler coding card and brief scans
Constant temperature control unit
Press the following keys:
2. a/b
for the required scan.
1. K + G simultaneously for
approx. 2 s
3. d
End scan.
0
1
E
3
A
62
0
Software
version
Solar control unit
0: w/o
solar control unit
0: w/o external demand
1: external
demand
0
0
System deSoftware version
Software
signs 1 to 6
Control unit
version
Display in
Programaccordance
ming unit
with the
system
equipment
level
Software version
Software
0
Burner control unit
version
External
extension
0: w/o external extension
0: w/o exExternal 0 to 10 V hook-up
ternal
Display in %
blocking
0: w/o external hook-up
1: external
blocking
0
Set boiler water temperature
0
Highest demand temperature
5692 619 GB
The following values can be scanned, subject to the actual equipment
level:
Display screen
Brief scan
Service scans
Temperatures, boiler coding card and brief . . . (cont.)
Display screen
Brief scan
4
0
5
b
C
c
0
0
0
0
d
0
Burner control unit type
Boiler type
0
Set cylinder temperature
0
Max. output in %
Boiler coding card (hexadecimal)
Boiler
Burner control unit
version
version
0
0
Variable
Software
speed
version
pump
variable
0 w/o
speed pump
1 Wilo
0: w/o vari2 Grundfos able speed
pump
5692 619 GB
Weather–compensated control unit
Press the following keys:
2. a/b
for the required scan.
1. K + G simultaneously for
approx. 2 s
3. d
Relay test ended.
The following values can be scanned, subject to the actual equipment
level:
Display screen
Explanation
Slope A1 – level A1
Slope M2 – level M2
Adj. outside temperature
The adjusted outside temperature can be reset
Actual outside temperature
to the actual outside temperature with e.
Set boiler temp.
Actual boiler temp.
Set DHW temp.
Actual DHW temp.
Actual DHW outlet temperature
Set DHW outlet temp.
Set flow temperature
Heating circuit with mixer
Actual flow temperature
Heating circuit with mixer
63
Service scans
Temperatures, boiler coding card and brief . . . (cont.)
Display screen
Set mixed flow temp.
Actual mixed flow temp.
Boiler coding card
Brief scan 1 to 8
Explanation
Low loss header
Low loss header
Display screen
Brief
scan
1
2
3
4
5
Software version
Burner control unit
0: w/o ex- 0: w/o
ternal de- external
blocking
mand
1: exter- 1: external
nal deblocking
mand
Number of LON
users
Equipment version
Number
of KM
BUS
users
Burner control unit
version
Maximum demand temperature
Software Software Software Software
version
version
version
version
LON
External
Solar
Mixer
module
extension
control
exten0: w/o
0: w/o exunit
sion
LON
ternal ex0: w/o
0: w/o
module
tension
solar
mixer
control
extenunit
sion
Type
Boiler type
Burner control unit
0
External 0 to 10 V hook-up
Display in %
0: w/o external hook-up
Check
digit
Max. output
Details in %
5692 619 GB
6
Software version
Control unit
System designs 01
to 06
Display in accordance with the system equipment level
0
Software
version
Programming unit
64
Service scans
Temperatures, boiler coding card and brief . . . (cont.)
Display screen
Brief
scan
Boiler
7
8
0
0
Internal circulation
pump
Variable
Software
speed
version
pump
variable
0: w/o
speed
1: Wilo
pump
2: Grun- 0: w/o
dfos
variable
speed
pump
Heating circuit A1
Heating circuit M2
(w/o mixer)
(with mixer)
Remote Software Remote
Software
control
version
control
version
0: w/o
Remote
0: w/o
Remote
1: Vitotr- control
1: Vitotr- control
ol 200 0: w/o reol 200 0: w/o re2: Vitotr- mote
2: Vitotr- mote conol 300 control
ol 300 trol
Heating circuit pump to connection extension
Variable Software Variable Software
speed
version
speed
version
pump
variable
pump
variable
0: w/o
speed
0: w/o
speed
1: Wilo
pump
1: Wilo
pump
2: Grun- 0: w/o vari2: Grun- 0: w/o
dfos
able speed
dfos
variable
pump
speed
pump
Checking outputs (relay test)
5692 619 GB
Constant temperature control units
Press the following keys:
2. a/b
Control relay outputs.
1. K + d simultaneously for
approx. 2 s
3. d
Relay test ended.
Subject to the actual equipment level, the following relay outputs can be
controlled:
Display screen
Explanation
1
Burner modulation base load
65
Service scans
Checking outputs (relay test) (cont.)
Display screen
2
3
4
5
6
10
11
12
13
14
Explanation
Burner modulation full load
Internal pump / output 20 "ON"
Heating mode diverter valve
Valve, centre position
DHW valve
Output sK Internal extension
Heating circuit pump A1 external extension
Cylinder primary pump external extension
DHW circulation pump external extension
Central fault message external extension
Weather–compensated control unit
Press the following keys:
2. a/b
Control relay outputs.
1. K + d simultaneously for
approx. 2 s
3. d
Relay test ended.
5692 619 GB
Subject to the actual equipment level, the following relay outputs can be
controlled:
Display screen
Explanation
Base load
Burner modulation lower output
Full load
Burner modulation upper output
Int. pump ON
Int. pump/output 20 "ON"
Heating valve
Diverter valve set to heating mode
Valve central pos.
Diverter valve in centre position (filling)
DHW valve
Diverter valve set to DHW mode
Heat. circ. pump M2 ON
Mixer extension
Close mixer
Mixer extension
Open mixer
Mixer extension
Output int.
Internal extension
Heat. circ. pump A1 ON
External extension
Cylinder primary pump ON
External extension
DHW circ. pump ON
External extension
Central fault message ON
External extension
66
Service scans
Scanning operating conditions and sensors
Constant temperature control units
Press the following keys:
1. c
2. a/b for the required operating
condition.
3. d
End scan.
Subject to the actual equipment level, the following operating conditions
can be scanned:
Display screen Explanation
1
15 °C/°F Actual outside temperature
3
65 °C/°F Actual boiler water temperature
5
50 °C/°F Actual cylinder temperature
5□ 45 °C/°F Solar – actual DHW temperature
6
70 °C/°F Actual value – collector sensor
P
Burner hours run (after maintenance, reset with e to "0")
263572 h
PPP
Burner starts (after maintenance, reset with e to "0")
030529
PPPP
Fuel consumption
030417
Weather–compensated control unit
5692 619 GB
Press the following keys:
4. d
to select heating circuit
with mixer M2.
1. a
"1r" flashes.
2. d
to select heating circuit
without mixer A1
or
6. a/b for the required operating
condition.
3. a
"2r" flashes.
7. d
5. c
End scan.
Subject to the actual equipment level for heating circuits A1 and M2, the
following operating conditions can be scanned:
Display screen
Explanation
User no.
Encoded user no. in the LON system
Holiday mode
If a holiday program has been entered.
Departure day
Date
67
Service scans
Scanning operating conditions and sensors (cont.)
Display screen
Return day
Outside temperature, ... °C
Boiler water temperature,
... °C
Flow temperature, ... °C
Standard
room temperature, ... °C
Room temperature, ... °C
Ext. set room temp, ... °C
DHW temperature, ... °C
Solar DHW temp., ... °C
Collector temperature, ... °C
Mixed flow temp., ... °C
Burner, ...h
Burner starts, ...
Explanation
Date
Actual value
Actual value
Actual value (only for mixer circuit M2)
Set value
Actual value
For external hook-up
Actual DHW temperature
Actual value
Actual value
Actual value, only with low loss header
Actual hours run
Hours run and burner starts (reset after maintenance e to "0").
5692 619 GB
Solar energy, ... kW/h
Time
Date
Burner OFF/ON
Int. pump OFF/ON
Output 20
Int. output OFF/ON
If an internal extension is installed
Heating circuit pump OFF/ON If an external extension or extension kit for one
heating circuit with mixer is installed
Cylinder pump ON/OFF
If an external extension is installed
DHW circulation pump OFF/
If an external extension is installed
ON
Central fault message OFF/
If an external extension is installed
ON
Mixer open/closed
If an extension kit for a heating circuit with mixer
is installed
Various languages
The respective languages can be selected as
permanent display language with d.
68
Troubleshooting
Fault display
Fault display structure
A Fault display
B Fault symbol
C Fault number
D Fault code
The red fault indicator flashes for every fault.
A fault in the burner control unit causes the display to show "E".
Constant temperature control units
In case of faults, the fault code and
fault symbol will be displayed at the
programming unit
Weather–compensated control units
5692 619 GB
The display flashes "Fault" if a fault
message is issued
Plain text fault displays:
& Burner control unit
& Outside temperature sensor
& Flow sensor
& Boiler sensor
& Mixed flow sensor
& DHW cylinder sensor
& Flue gas sensor
& DHW outlet sensor
69
Troubleshooting
Fault display (cont.)
&
&
Room temperature sensor
Fault - user
Checking and acknowledging faults
Note
If an acknowledged fault is not removed, the fault message will be re-displayed
after 24 h.
Constant temperature control units
Press the following keys:
2. d
all fault messages are
acknowledged simultaneously, the fault display
will be cancelled and the
red fault
indicator continues to
flash.
3. d
all fault messages are
acknowledged simultaneously, the fault display
will be cancelled and the
red fault
indicator continues to
flash.
1. a/b for further fault codes.
Weather–compensated control units
Press the following keys:
1. c
for the current fault.
2. a/b for further fault messages.
Calling up acknowledged fault messages
Press the following keys:
for approx. 3 s.
5692 619 GB
1. d
2. a/b for the acknowledged fault.
70
Troubleshooting
Calling up fault codes from the fault memory (fault history)
The 10 most recent faults are saved
and may be scanned.
The faults are ordered according to
date, thus the most recent fault is fault
number 1.
1. G + d simultaneously for
approx. 2 s
2. a/b
for individual fault
codes.
3. Note
All saved fault codes can be
deleted with e.
4. d
Terminate the scan.
5692 619 GB
Fault codes
Fault
Const.
code in
the display
0F
X
Weath.- System charcomp.
acteristics
Cause
X
Control mode
10
X
X
18
X
X
20
X
X
28
X
X
Controls as if
the outside
temperature
was 0 °C
Controls as if
the outside
temperature
was 0 °C
Regulated
without flow
temperature
sensor (low
loss header)
Regulated
without flow
temperature
sensor (low
loss header)
Maintenance Carry out maintenance. After the
maintenance, set
code "24:0".
Outside tem- Check the outside
perature
temperature sensensor
sor (see page 79)
shorted out
Outside tem- Check the outside
perature
temperature sensensor lead
sor (see page 79)
broken
System flow Check the low
temperature loss header sensensor
sor (see page 80)
shorted out
System flow
temperature
sensor lead
broken
Remedy
Check the low
loss header sensor (see page 80)
71
Troubleshooting
Fault codes (cont.)
Const.
Fault
code in
the display
30
X
Weath.- System charcomp.
acteristics
Cause
Remedy
X
Burner
blocked
38
X
Burner
blocked
40
X
Mixer closes
Check the boiler
water temperature sensor (see
page 80)
Check the boiler
water temperature sensor (see
page 80)
Check flow temperature sensor
48
X
Mixer closes
Boiler water
temperature
sensor
shorted out
Boiler water
temperature
sensor lead
broken
Mixer circuit
M2 flow temperature
sensor
shorted out
Mixer circuit
M2 flow temperature
sensor lead
broken
Cylinder primary temperature
sensor
shorted out
Outlet temperature
sensor
shorted out
Cylinder primary temperature
sensor lead
broken
Draw off
temperature
sensor short
circuit
50
X
X
No DHW heating
51
X
X
No DHW heating
58
X
X
No DHW heating
59
X
X
No DHW heating
72
Check flow temperature sensor
Check sensors
(see page 80)
Check sensors
(see page 80)
Check sensors
(see page 80)
Check sensors
(see page 80)
5692 619 GB
X
Troubleshooting
Fault codes (cont.)
Const.
Fault
code in
the display
92
X
Weath.- System charcomp.
acteristics
Cause
Remedy
X
Control mode
Check sensor
93
X
X
Control mode
94
X
X
Control mode
9A
X
X
Control mode
9b
X
X
Control mode
9C
X
X
Control mode
9F
X
X
Control mode
X
Control operation as per the
delivered condition
Burner
blocked
Collector
temperature
sensor
shorted out
Solar: Sensor S3
shorted out
Solar: Cylinder primary
temperature
sensor
shorted out
Collector
temperature
sensor lead
broken
Solar: Sensor S3 lead
broken
Solar: Cylinder primary
temperature
sensor lead
broken
Solar control
unit fault
message
Faulty programming
unit
5692 619 GB
A7
b0
X
X
b1
X
X
Control operation as per the
delivered condition
Flue gas
temperature
sensor short
circuit
Communication error
programming unit
Check sensor
Check sensor
Check sensor
Check sensor
Check sensor
See solar control
unit service instructions
Replace programming unit
Check flue gas
temperature sensor
Check connections and replace
the programming
unit if required
73
Troubleshooting
Const.
Fault
code in
the display
b4
X
Weath.- System charcomp.
acteristics
Cause
Remedy
X
Internal fault
Replace control
unit
b5
X
X
Internal fault
Replace control
unit
b7
X
X
b8
X
X
bA
X
bC
X
bd
X
bE
X
bF
X
74
Controls as if
the outside
temperature
was 0 °C
Control operation as per the
delivered condition
Burner
blocked
Boiler coding Plug in boiler codcard fault
ing card or replace, if faulty
Burner
Flue gas
Check flue gas
blocked
temperature temperature sensensor break sor
Mixer "Close" Communica- Check the extention fault –
sion kit connecextension kit tions and coding;
for heating
start the extencircuit M2
sion kit
Control mode Communica- Check connections, cable/lead
without remote tion fault and coding adcontrol
Vitotrol remote control, dress "A0"
heating circuit A1
Control mode Communica- Check connections, cable/lead
without remote tion fault and coding adVitotrol recontrol
mote control, dress "A0"
heating circuit M2
Check remote
Control mode Vitotrol remote control control DIP switch
setting (see
incorrectly
page 105)
encoded
Replace the LON
Control mode Incorrect
communication
LON commodule
munication
module
5692 619 GB
Fault codes (cont.)
Troubleshooting
Fault codes (cont.)
Const.
Fault
code in
the display
C2
X
Weath.- System charcomp.
acteristics
Cause
X
Control mode
C5
X
Control mode,
max. pump
speed
X
Control mode,
max. pump
speed
Check the connections and settings of coding
address "54"
Check the coding
address "30" settings; check the
DIP switch settings in the pump
wiring chamber:
Switch 1: OFF,
Switch 2: ON
Communica- Check the coding
address "E5" settion fault external vari- tings; check the
DIP switch setable speed
tings in the pump
heating cirwiring chamber:
cuit pump,
Switch 1: OFF,
heating
Switch 2: ON
circuit M2
Communica- Check the coding
address "E5" settion fault external vari- tings; check the
DIP switch setable speed
tings in the pump
heating cirwiring chamber:
cuit pump,
Switch 1: ON,
heating
Switch 2: OFF
circuit A1
Communica- Check connections, Vitocom 100
tion fault
Vitocom 100 and coding address "95"
(KM BUS)
Communica- Check connections and coding
tion fault –
address "2E"
ext. extension
X
C6
X
X
Control mode,
max. pump
speed
Cd
X
X
Control mode
CE
X
X
Control mode
Communication fault solar control
unit
Communication error –
variable
speed internal pump
5692 619 GB
C7
Remedy
75
Troubleshooting
Fault codes (cont.)
Const.
Fault
code in
the display
CF
Weath.- System charcomp.
acteristics
Cause
Remedy
X
Control mode
Replace the LON
communication
module
dA
X
Control mode
without room
influence
db
X
Control mode
without room
influence
dd
X
Control mode
without room
influence
Communication fault LON communication
module
Room temperature
sensor, heating circuit A1
shorted out
Room temperature
sensor, heating circuit
M2 shorted
out
Room temperature
sensor, heating circuit A1
lead broken
dE
X
Control mode
without room
influence
X
X
Burner
blocked
E5
X
X
Burner
blocked
Check the room
temperature sensor – heating circuit M2
Check the room
temperature sensor, heating circuit A1 and the
remote control
DIP switch setting
(see page 105)
Check the room
Room temtemperature senperature
sensor, heat- sor, heating circuit M2 and the
ing circuit
M2 lead bro- remote control
DIP switch setting
ken
(see page 105)
Fault – sup- Replace control
unit
ply voltage
24 V
Flame ampli- Replace the confier fault
trol unit.
5692 619 GB
E4
Check the room
temperature sensor – heating circuit A1
76
Troubleshooting
5692 619 GB
Fault codes (cont.)
Const.
Fault
code in
the display
E6
X
Weath.- System charcomp.
acteristics
Cause
Remedy
X
Burner fault
Flue gas/
ventilation
system
blocked
F0
X
X
Internal fault
F1
X
X
Burner
blocked
Burner fault
Check the flue
gas/ventilation
system and differential pressure
sensor; press "E"
Replace control
unit
Check flue gas
path/route, press
"E"
F2
X
X
Burner fault
F3
X
X
Burner fault
F4
X
X
Burner fault
F7
X
X
Burner
blocked
Flue gas
temperature
limiter has
responded
The temperature limiter has
responded
Check the heating
system fill level,
the circulation
pump, the temperature limiter
and interconnecting cables/leads;
ventilate the system; press "E"
Flame signal Check the ionisais already
tion electrode and
present at
interconnecting
burner start
leads; press "E"
No flame sig- Check the ionisanal.
tion electrode,
ignition, ignition
module, interconnecting cables
and leads, gas
pressure, gas
combination valve
and the ionisation
current; press
"E"
Check differential
Differential
pressure sensor
pressure
sensor faulty and lead
77
Troubleshooting
Const.
Fault
code in
the display
F8
X
Weath.- System charcomp.
acteristics
Cause
Remedy
X
Burner fault
The fuel
valve closes
too late
F9
X
X
Burner fault
Fan speed
too low during burner
start
FA
X
X
Burner fault
Fan not at
standstill
Fd
X
X
Burner
blocked
Fault burner
control unit
FE
X
X
FF
X
X
Strong interBurner
blocked or in a ference
(EMC) field
fault state
nearby or
faulty main
PCB
Burner
Strong interblocked or in a ference
(EMC) field
fault state
nearby or internal fault
Check the gas
combination valve
and both control
paths; press "E"
Check the fan, fan
connecting
cables, fan power
supply and control; press "E"
Check fan, fan
connecting cables
and fan control;
press "E"
Check the ignition
electrodes and
connecting
cables/leads;
check whether
there are strong
fields of interference (EMC) near
the equipment;
press "E". Replace the control
unit if the fault
persists.
Start the boiler
again. Replace
the control unit if
the equipment will
not restart.
78
Start the boiler
again. Replace
the control unit if
the equipment will
not restart.
5692 619 GB
Fault codes (cont.)
Troubleshooting
Repairs
Checking the outside temperature sensor (weather-compensated control unit)
1. Pull plug "X3" off the control unit.
2. Test the resistance of the outside
temperature sensor across terminals "X3.1" and "X3.2" on the disconnected plug and compare it with
the curve.
3. Where actual values strongly deviate from the curve values, disconnect the wires at the sensor and
repeat test directly at the sensor.
5692 619 GB
4. Subject to result, replace the lead
or the outside temperature sensor.
79
Troubleshooting
Repairs (cont.)
Check the boiler temperature sensor, cylinder primary temperature sensor or flow temperature sensor for the low loss
header
5692 619 GB
A Boiler water temperature sensor
80
Troubleshooting
Repairs (cont.)
1.
&
Boiler water temperature sensor
Pull the leads off the boiler temperature sensor and check the
resistance.
& Cylinder primary temperature
sensor
Pull the plug % from the cable
harness on the control unit and
measure the resistance.
& Flow temperature sensor
Pull plug "X3" off the control unit
and measure the resistance
across terminals "X3.4" and
"X3.5".
2. Check the sensor resistance and
compare the actual values with the
curve.
3. Replace the sensor in cases of
severe deviation.
Danger
The boiler water temperature sensor is immersed in
the heating water (risk of
scalding).
Drain the boiler before
replacing the sensor.
5692 619 GB
% Plug for the cylinder primary temperature sensor
81
Troubleshooting
Repairs (cont.)
Check the outlet temperature sensor
1. Pull the leads off the outlet temperature sensor A.
2. Check the sensor resistance and
compare it with the curve.
3. Replace the sensor in cases of
severe deviation.
Danger
The outlet temperature sensor is immersed in the DHW
(risk of scalding).
Drain the secondary side of
the boiler before replacing
the sensor.
The flue gas temperature sensor locks out the boiler when the permissible flue
gas temperature is exceeded. Reset the interlock after the flue gas system has
cooled down by pressing the reset button "E".
82
5692 619 GB
Checking the flue gas temperature sensor
Troubleshooting
Repairs (cont.)
1. Pull the leads off the flue gas temperature sensor A.
2. Check the sensor resistance and
compare it with the curve.
3. Replace the sensor in cases of
severe deviation.
Checking the plate-type heat exchanger
5692 619 GB
Drain the primary and secondary side
of the boiler.
During removal, small amounts of
water may trickle out and escape from
the removed plate-type heat exchanger.
83
Troubleshooting
Repairs (cont.)
1. Shut off and drain the boiler on the
primary and the secondary side.
2. Release the side closures and
pivot the control unit forward.
3. Remove the siphon.
4. Release the compression fittings
A, screws B and pull out the
plate-type heat exchanger C.
5. Check the primary and secondary
connections for contamination and
scaling; if necessary, replace the
plate-type heat exchanger.
A Compression fittings
B Screws
C Plate-type heat exchanger
6. Lubricate the new gaskets/seals.
Install in reverse order with new
gaskets.
Checking the temperature limiter
5692 619 GB
If the burner control unit cannot be reset after a fault shutdown, although the
boiler water temperature is below approx. 75 °C, check the temperature limiter.
84
Troubleshooting
Repairs (cont.)
1. Pull the leads off the temperature
limiter.
2. Check the continuity of the temperature limiter with a multimeter.
3. Remove the faulty temperature limiter.
4. Coat the replacement temperature
limiter with heat conducting paste
and install.
5. After commissioning, press reset
button "E" on the control unit.
Checking and replacing the differential pressure sensor
5692 619 GB
In case of fault messages concerning the differential pressure sensor, check the
sensor for:
& Correct installation
& Electrical connection
& Correct position of the O-rings inside the adaptor
& Plugs in test nipples
Replace the sensor if fault messages persist.
85
Troubleshooting
Repairs (cont.)
Checking O-rings:
A O-rings
B Sensor
C Plug-in connection
D Adaptor
1. Pull off electrical plug C.
4. Insert the sensor with connection
nipples into the gas combination
valve adaptor and push in until it
clicks into place.
2. Remove sensor B by pulling it
upwards.
5. Reconnect the electrical plug-in
connector on the sensor.
5692 619 GB
3. Ensure that both O-rings A are
properly seated inside the adaptor
retainers D.
86
Troubleshooting
Repairs (cont.)
Checking the fuse
3. Remove the cover.
2. Release the side closures and
pivot the control unit down.
4. Check the fuse F1 (see connection
and wiring diagram).
5692 619 GB
1. Switch OFF the power.
87
Troubleshooting
Repairs (cont.)
Extension kit for heating circuit with mixer
Checking the rotational direction of
the mixer motor
Changing the rotational direction of
the mixer motor (if required)
1.
1.
Switch the ON/OFF switch A at
the extension kit first OFF and then
ON again. The device will carry out
the following self-test:
& Mixer "Close" (150 s)
& Pump "ON" (10 s)
& Mixer "Open" (10 s)
& Mixer "Close" (10 s)
Standard control mode then recommences.
Danger
An electric shock can be
life-threatening.
When opening the equipment, switch OFF the ON/
OFF switch and mains voltage, for example at the fuse
or the mains isolator.
2. Remove the lower and upper housing cover of the extension kit.
Extension kit installation
instructions
3.
2. Observe the rotational direction of
the mixer motor during its self-test.
Then set the mixer manually to
"Open" again.
Note
The flow temperature sensor must
now capture a higher temperature.
If the temperature falls, either the
motor is turning in the wrong direction or the mixer set is incorrectly
fitted.
5692 619 GB
Mixer installation instructions
A ON/OFF switch
B Rotational direction switch
Change the rotational direction
switch:
88
Troubleshooting
Repairs (cont.)
&
Switch position I for central heating
return from the left (delivered condition).
&
Switch position II for central heating
return from the right.
Checking the Vitotronic 050 (accessories)
5692 619 GB
The Vitotronic 050 is connected with the control unit via the LON connecting
cable. To test the connection, implement a user check at the boiler control unit
(see page 37).
89
Function description
Constant temperature control unit
Controls and display elements
A
B
C
D
Pressure gauge
Fault display (red)
ON indicator (green)
Reset button
E Control panel:
O
Set boiler water temperature
F
Set DHW temperature
O+F Emissions test function
K
Standby mode:
L
DHW only
G
Heating and DHW
/
No function
b/a
Setting values
d
Confirmation
c
Information
e
Standard setting (Reset)
F ON/OFF switch
The set boiler water temperature will
be maintained in the "Heating and
DHW" program when a demand is
raised by the room thermostat.
The boiler water temperature will be
maintained at the default frost protection temperature when there is no
demand.
90
The boiler water temperature will be
limited:
& to 74 °C by the thermostat inside the
burner control unit.
& to 82 °C by the electronic temperature limiter inside the burner control
unit (during DHW heating to 87 °C).
& to 100 °C by the temperature limiter
in the safety chain (interlocks the
burner control unit).
5692 619 GB
Heating mode
Function description
Constant temperature control unit (cont.)
Heating the DHW storage cylinder from cold
The heating circuit pump is switched
ON and the three-way diverter valve
will be changed over, if the cylinder
primary temperature sensor captures
a temperature lower than the set temperature.
& At a boiler water temperature ≥ set
DHW temperature, the cylinder primary pump will be switched ON.
& At a boiler water temperature ≤ set
DHW temperature, the burner will
be switched ON and, after the
required boiler water temperature
has been reached, the cylinder primary pump will be switched ON.
The cylinder is then heated up to the
set DHW temperature. Heating stops
when the set temperature has been
reached at the cylinder primary temperature sensor and at the outlet temperature sensor.
After heating, the cylinder primary
pump and the three-way diverter
valve remain ON for a further 30 s.
Reheating when DHW is drawn off
The DHW is regulated to the set temperature via the cylinder primary temperature sensor.
The cylinder continues to be heated
up after the draw-off process has
ended, until the set DHW temperature
has been reached at the cylinder primary temperature sensor.
The cylinder primary pump and the
three-way diverter valve remain ON
for a further 30 s.
5692 619 GB
When DHW is drawn off, cold water
enters at the bottom of the cylinder.
The heating circulation pump is
switched ON and the three-way diverter valve is changed over, if the cylinder primary temperature sensor
captures a temperature lower than the
set temperature.
& At a boiler water temperature ≥ set
DHW temperature, the cylinder primary pump will be switched ON.
& At a boiler water temperature ≤ set
DHW temperature, the burner will
be switched ON and, after the
required boiler water temperature
has been reached, the cylinder primary pump will be switched ON.
91
Function description
Weather–compensated control unit
Controls and display elements
Pressure gauge
Fault display (red)
ON indicator (green)
Reset button
E Control panel:
A
Time program, central
heating
B
Time program DHW
heating/DHW circulation
pump (if connected to
the control unit)
H
Holiday mode
D
Date/time
E
Reduced room temperature
F
Set DHW temperature
O+F Emissions test function
K
Standby mode:
L
DHW only
G
Heating and DHW
M
Party mode
N
Economy mode
b/a
Setting values
d
Confirmation
c
Information
e
Standard setting (Reset)
F Rotary selector for the standard
room temperature
G ON/OFF switch
5692 619 GB
A
B
C
D
92
Function description
Weather–compensated control unit (cont.)
Heating mode
The control unit determines a set boiler water temperature subject to the
outside temperature or room temperature (if a room temperature-dependent
remote control is connected) and the
slope/level of the heating curve. The
determined set boiler water temperature is transferred to the burner control unit.
From the set and actual boiler water
temperatures, the burner control unit
calculates the modulation level and
regulates the burner accordingly.
The boiler water temperature will be
limited:
& to 74 °C by the thermostat inside the
burner control unit.
& to 82 °C by the electronic temperature limiter inside the burner control
unit (during DHW heating to 87 °C).
& to 100 °C by the temperature limiter
in the safety chain (interlocks the
burner control unit).
Heating the DHW storage cylinder from cold
The heating circuit pump is switched
ON and the three-way diverter valve
will be changed over, if the cylinder
primary temperature sensor captures
a temperature lower than the set temperature.
& At a boiler water temperature ≥ set
DHW temperature, the cylinder primary pump will be switched ON.
& At a boiler water temperature ≤ set
DHW temperature, the burner will
be switched ON and, after the
required boiler water temperature
has been reached, the cylinder primary pump will be switched ON.
The cylinder is then heated up to the
set DHW temperature. Heating stops
when the set temperature has been
reached at the cylinder primary temperature sensor and at the outlet temperature sensor.
After heating, the cylinder primary
pump and the three-way diverter
valve remain ON for a further 30 s.
Reheating when DHW is drawn off
5692 619 GB
When DHW is drawn off, cold water
enters at the bottom of the cylinder.
93
Function description
Weather–compensated control unit (cont.)
The DHW is regulated to the set temperature via the cylinder primary temperature sensor.
The cylinder continues to be heated
up after the draw-off process has
ended, until the set DHW temperature
has been reached at the cylinder primary temperature sensor.
The cylinder primary pump and the
three-way diverter valve remain ON
for a further 30 s.
5692 619 GB
The heating circulation pump is
switched ON and the three-way diverter valve is changed over, if the cylinder primary temperature sensor
captures a temperature lower than the
set temperature.
& At a boiler water temperature ≥ set
DHW temperature, the cylinder primary pump will be switched ON.
& At a boiler water temperature ≤ set
DHW temperature, the burner will
be switched ON and, after the
required boiler water temperature
has been reached, the cylinder primary pump will be switched ON.
94
Function description
Extensions for external connections
Internal extension H1
An external safety valve can be connected to gD.
5692 619 GB
The internal extension H1 is integrated into the control unit casing.
The cylinder primary pump is connected to relay output sK.
95
Function description
Extensions for external connections (cont.)
Internal extension H2 (accessories)
An external extractor fan interlock can
be connected to aBJ.
5692 619 GB
The internal extension H2 is integrated into the control unit casing
instead of the internal extension H1.
The cylinder primary pump is connected to relay output sK.
96
Function description
Extensions for external connections (cont.)
External extension H1 (accessories)
aVD
&
External blocking
(terminals 2 - 3)
& External demand
(terminals 1 - 2)
& External heating program
changeover (terminal 1 - 2)
The allocation of function
"External heating program
changeover" is set via coding
address "91".
aVF External set value 0 to 10 V
aVG KM BUS
5692 619 GB
The external extension is connected
to the boiler control unit via the KM
BUS. The following functions can be
controlled or processed simultaneously via the extension:
A Mains isolator (on site)
sÖ Heating circuit pump for the
heating circuit without mixer
sK DHW circulation pump
fÖ Power supply
gÖ Central fault message
97
Function description
Extensions for external connections (cont.)
External extension H2 (accessories)
aVD
&
External blocking
(terminals 2 - 3)
& External demand
(terminals 1 - 2)
& External heating program
changeover (terminal 1 - 2)
The allocation of function
"External heating program
changeover" is set via coding
address "91".
aVG KM BUS
5692 619 GB
The external extension is connected
to the boiler control unit via the KM
BUS. The following functions can be
controlled or processed simultaneously via the extension:
A Mains isolator (on site)
sK DHW circulation pump
fÖ Power supply
98
Function description
Control functions
External heating program changeover
The "Ext. heating program changeover" function is connected via the external
extension input "aVD". Coding address "91" enables the selection of which heating circuits the heating program changeover should affect:
The heating program changeover affects:
No changeover
Heating circuit without mixer (A1)
Heating circuit with mixer (M2)
Heating circuit without mixer and heating circuit with mixer
Coding
91:0
91:1
91:2
91:3
With coding address "d5", you can select in which direction the changeover
should be made for each heating circuit:
The heating program changeover affects:
Changeover in the direction of "Constant reduced" or "Constant standby" mode (respectively in accordance with the selected set value)
Changeover towards "Constant heating mode"
Coding
d5:0
d5:1
The duration of the heating program changeover can be adjusted in coding
address "F2".
The heating program changeover affects:
No heating program changeover
Duration of the heating program changeover 1 to 12 hours
Coding
F2:0
F2:1 to
F2:12
The heating program changeover remains active for as long as the contact
remains closed, in any case at least as long as the duration selected in coding
address "F2".
5692 619 GB
External blocking
The "External blocking" function is
connected via the external extension
input "aVD".
The "External blocking" function stops
the burner.
In coding address "32" you can select
the influence the signal "External
blocking" should have on the connected circulation pumps.
99
Function description
Control functions (cont.)
External demand
The "External demand" function is
connected via the external extension
input "aVD".
In coding address "34" you can select
the influence the signal "External
demand" should have on the connected circulation pumps.
In coding address "9b" you can select
the minimum set boiler water temperature in case of external demand.
Venting program
During the venting program, the circulation pump will be alternately
switched ON and OFF for 30 seconds
respectively over a period of
20 minutes.
For a certain period, the changeover
valve is alternately set towards heating mode and DHW heating.
The burner is switched OFF during
the venting program.
The venting program is activated via
coding "2F:1". The program is automatically deactivated after 20 min,
and the coding address "2F" is set to
"0".
Filling program
In the delivered condition, the changeover valve is set in its centre position, enabling the system to be filled
completely. After starting the control
unit, the diverter valve no longer goes
into its central position.
Afterwards, the changeover valve can
be moved via coding address "2F:2"
into the centre position. In this position, the control unit can be switched
OFF, and the the system can be filled
completely.
Filling with the control unit switched ON
The burner shuts down if this function
is enabled via coding address "2F".
The program is automatically deactivated after 20 min, and the coding
address "2F" is set to "0".
5692 619 GB
If the system is to be filled with the
control unit switched ON, the changeover will be moved to its centre position via code "2F:2" and the pump will
be started.
100
Function description
Control functions (cont.)
Screed function
The screed function enables the drying of screed. For this, always
observe the details specified by the
screed manufacturer.
You can select various temperature
profiles.
Temperature profile: Diagram 1 (DIN 4725 part 4) code "F1:1"
Temperature profile: Diagram 2 (ZV parquet and flooring technology) code
"F1:2"
5692 619 GB
Temperature profile: Diagram 3 code "F1:3"
101
Function description
Control functions (cont.)
Temperature profile: Diagram 4 code "F1:4"
Temperature profile: Diagram 5 code "F1:5"
5692 619 GB
Temperature profile: Diagram 6 code "F1:6" (delivered condition)
102
Function description
Control functions (cont.)
Raising the reduced room temperature
During operation with reduced room
temperature, the reduced set room
temperature can be automatically
raised subject to outside temperature.
The temperature is raised in accordance with the selected heating curve
up to the set standard room temperature.
The outside temperature limits for the
start and end of the temperature raising can be adjusted via the coding
addresses "F8" and "F9".
Example using the settings in the delivered condition
B Heating curve for operation with
reduced room temperature
5692 619 GB
A Heating curve for operation with
standard room temperature
103
Function description
Control functions (cont.)
Reducing the heat-up time
During the transition from operation
with reduced room temperature into
operation with standard room temperature, the boiler water or flow temperature will be raised in accordance
with the selected heating curve. The
boiler water or flow temperature can
be automatically increased.
The value and duration for the additional increase of the set boiler water
temperature or flow temperature can
be adjusted in the coding addresses
"FA" and "Fb".
A Start of operation with standard
room temperature
B Set boiler water or flow temperature in accordance with the
selected heating curve
104
C Set boiler water or flow temperature in accordance with coding
address "FA":
50 °C + 20 % = 60 °C
D Duration of operation with raised
boiler water or flow temperature in
accordance with coding address
"Fb":
60 min
5692 619 GB
Example using the settings in the delivered condition
Function description
Remote control DIP switch
The DIP switches are located on the PCB in the top part of the housing.
Remote control
The remote control affects the heating
circuit without mixer A1
DIP switch setting
The remote control affects the heating
circuit with mixer M2
5692 619 GB
When connecting a separate room
temperature sensor, set DIP switch "3"
to "ON".
105
Designs
A1
X...
§
$
106
Main PCB
Electrical interfaces
Boiler water temperature sensor
Draw-off temperature sensor
%
aA
aG
dÖ
Cylinder temperature sensor
Ionisation electrode
Flue gas temperature sensor
Stepper motor for diverter
valve
5692 619 GB
Connection and wiring diagram – internal connections
Designs
Connection and wiring diagram – internal . . . (cont.)
Thermocouple
Ignition device
a-ÖA Fan motor
aNF Differential pressure sensor
5692 619 GB
fJ
gF
107
Designs
A1
108
Main PCB
A2
Power supply unit
5692 619 GB
Connection and wiring diagram – external connections
Designs
Connection and wiring diagram – external . . . (cont.)
Optolink
Burner control unit
Programming unit
Coding card
Connection adaptor
Communication module LON
Internal extension H1 or H2
ON/OFF switch
Reset button
Electrical interfaces
Outside temperature sensor
?
Flow temperature sensor - low
loss header
% Cylinder temperature sensor
sÖ Internal circulation pump
sK Primary pump
dG Gas solenoid valve
fÖ Power supply
lH Power supply accessories and
Vitotrol 100
a-Ö Fan motor
aYA Gas governor
aVG KM BUS
5692 619 GB
A3
A4
A5
A6
A7
A8
A9
S1
S2
X...
!
109
Parts lists
Parts lists
001 Heat exchanger connecting pipe
with gaskets
002 Flow pipework
003 DHW connecting pipe
004 DHW connecting pipe
005 Cylinder connecting pipe
006 Return connecting pipe
007 Gas connection flange
008 Stratification storage cylinder
009 Siphon
010 Condensate hose
012 Heat exchanger
013 Cap plate (with item 014)
014 Profiled gasket
015 Clip nut
016 Mounting bracket closure
017 Boiler adaptor
018 Plug
019 Air inlet gasket Ø 125
020 Lip seal Ø 80
021 Boiler connection grommets
022 Connecting pipe - diaphragm
expansion vessel
023 Diaphragm expansion vessel
024 Pressure gauge and fem. connection
025 Quick-acting air vent valve G ⅜"
026 Overflow valve
027 Safety valve
028 Air vent valve G ⅜"
029 Linear stepper motor
030 Non-return valve
031 Ball valve R ½" with handle
033 Flat packing
034 Set of plug connector retainers
035 Safety spring
036 Plate-type heat exchanger
110
037 Gasket set – plate-type heat
exchanger
040 Grommets (set)
051 Burner (with items 050, 052 to
064)
052 Ignition unit
055 Burner gauze
056 Radial fan
057 Pressure transmitter
058 Gas train
059 Conversion kit for natural gas E
(gas restrictor)
060 Conversion kit for natural gas LL
(gas restrictor)
061 only for 26 kW: Conversion kit for
LPG P (gas restrictor)
064 Burner gauze gasket
069 DHW connecting pipe
100 Control unit
101 Back cover
102 Locking clips (10 pieces)
103 Support
104 Pivot arm
105 Hinge pins (10 pieces)
106 Flap
107 Pressure gauge retainer
108 Clip (10 pieces)
109 Hinge (10 pieces)
110 Boiler coding card
111 Fuse 6.2 A s (10 pieces)
112 Programming unit for constant
temperature operation
113 Programming unit for weathercompensated mode
122 LON communication module
(accessories)
123 PCB adaptor – LON module
(accessories)
5692 619 GB
Spare parts information
Quote the part and serial no. (see type plate) and the item no. of the required
part (as per this parts list).
Obtain standard parts from your local supplier.
Parts lists
Parts lists (cont.)
125
151
152
153
154
155
200
201
202
203
204
205
206
300
301
352
354
355
Fuse holder
Outside temperature sensor
Cylinder temperature sensor
Flue gas temperature sensor
Thermocouple
Temperature sensor
Side panels
Top front panel
Back top panel
Front top panel
Front bottom panel
Tie-bar
Adjustable foot
Circulation pump motor
Circulation pump motor
Gasket
Anode flange with gasket
Thermal insulation – flange
Wearing parts
050 Burner gasket
053 Ignition electrode with gasket
054 Ionisation electrode with gasket
353 Magnesium anode Ø = 26 × 280/
250
116
117
118
119
120
126
127
128
207
208
209
350
351
400
401
403
404
A
Heat conducting paste
Burner maintenance set
Set of small burner parts
Pressure sensor adaptor
Ionisation current test lead adaptor
Cable harness X8/X9
Cable harness 100/35/54 (auxiliary earth)
Stepper motor connecting cable
Cable harness ionisation/KM
BUS (internal)
Internal ionisation lead
Mating plug
Cable fixing
Anti-splash protection
Fixing elements
Touch-up paint stick, Vitowhite
Touch-up spray paint, Vitowhite
Seal washer
Strain relief
Operating instructions for constant temperature operation
Operating instructions for
weather-compensated operation
Installation instructions
Service instructions
Type plate
5692 619 GB
Parts not shown
032 Gasket set – plug-in connector
038 Special grease
039
062
063
065
115
111
Parts lists
5692 619 GB
Parts lists (cont.)
112
Parts lists
5692 619 GB
Parts lists (cont.)
113
Parts lists
5692 619 GB
Parts lists (cont.)
114
Parts lists
5692 619 GB
Parts lists (cont.)
115
Parts lists
5692 619 GB
Parts lists (cont.)
116
Commissioning/service reports
Commissioning/service reports
Setting and test values
Set value
Static pressure
Date:
By:
mbar
Supply pressure (flow
pressure)
= for natural gas E
mbar
= for natural gas LL
mbar
= for LPG
mbar
Initial
start-up
Maintenance/service
max.
57.5 mbar
17.457.5 mbar
17.457.5 mbar
42.557.5 mbar
Tick gas type
Carbon dioxide content
CO 2
& at the lower rated output % vol.
& at the upper rated out% vol.
put
Oxygen content O 2
& at the lower rated output % vol.
& at the upper rated out% vol.
put
Carbon monoxide content CO
& at the lower rated output ppm
& at the upper rated outppm
put
µA
min. 2 µA
5692 619 GB
Ionisation current
117
Specification
Specification
Rated voltage
Rated frequency
Rated current
Protection class
Protection
230 V~
50 Hz~
6 A~
I
IP X 4 D to
EN 60529
Permissible ambient temperature
& during operation
0 to +40 °C
&
during storage
and transport
Electronic temperature limiter setting:
Temperature limiter
setting
Line fuse (mains)
Power consumption
& Circulation pump
& Burner
& Control unit
82 °C
100 °C (fixed)
max. 16 A
max. 115 W
max. 60 W
max. 10 VA
-20 to +65 °C
Product characteristics (to EnEV [Germany])
Rated output range
kW
Efficiency µ at
& 100 % of rated output
%
& 30% of rated output
%
%
Standby heat loss qB,70* 2
Power consumption * 2 at
& 100 % of rated output
W
& 30 % of rated output
W
*1 The
4.2 to 13
6.6 to 26
96.0
107.4
0.8
96.3
107.4
0.7
207
69
207
69
supply values are only for reference (e.g. in the gas contract application) or to estimate the supplementary volumetric settings. Because of factory settings, the gas pressure must not be altered from these values. Reference: 15°C, 1013 mbar.
*2 Max. limit to EnEV [Germany]
118
5692 619 GB
Gas fired boiler, category 13 kW: I 2ELL, category 26 kW: II 2ELL3P
Rated output TV/T R 50/30 °C
kW
4.2 to 13
6.6 to 26
Rated output range
for central heating
kW
3.9 to 12.3
6.3 to 24.7
for DHW heating
kW
3.9 to 16.7
—
1
Connection values *
Relative to the max. load
with:
with H uB
Natural gas E
9.45 kWh/m 3 m 3 /h
1.77
2.65
34.02 MJ/m 3
l/min
2.05
3.08
Natural gas LL
8.13 kWh/m 3 m 3 /h
l/min
29.25 MJ/m 3
LPG
12.79 kWh/kg m 3 /h
—
1.94
46.04 MJ/kg
Product ID
_-0085
Certificates
Declaration of conformity
Declaration of conformity for the Vitodens 333
We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, confirm as sole
responsible body that the product Vitodens 333 complies with the following
standards:
DIN 4702–6
DIN 4753
EN 483
EN 625
EN 677
EN 50 165
EN 60 335
EN 61 000-3-2
EN 61 000-3-3
In accordance with the following Directives, this product is designated with _0085:
90/396/EEC
89/336/EEC
73/ 23/EEC
92/ 42/EEC
97/23/EC
EC Declaration of conformity by an authorised body according to EMVG article
10.2 Certificate number: E9 02 08 1730.
This product meets the requirements of the Efficiency Directive (92/42/EEC) for
Condensing boilers.
The product characteristics determined as system values for the Vitodens 333
as part of EC type testing according to the Efficiency Directive (see specification table) can be used for the energy assessment of heating and ventilation equipment to DIN V 4701–10.
Allendorf 12.07.05
Viessmann Werke GmbH&Co KG
5692 619 GB
pp. Manfred Sommer
119
Certificates
Manufacturer's certificate according to the 1st BImSchV [Germany]
We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, confirm that the
Vitodens 333 product meets the NO x limits specified by the
first BImSchV § 7 (2) [Germany].
Allendorf 12.07.05
Viessmann Werke GmbH&Co KG
5692 619 GB
pp. Manfred Sommer
120
Keyword index
Keyword index
A
Acknowledging a fault display . . . . . . .
Adjusting the room temperature . . . .
Anode replacement . . . . . . . . . . . . . . . . . . . . . .
Anode testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
70
34
22
22
B
Boiler temperature sensor . . . . . . . . . . . .
Brief scans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Burner gauze assembly . . . . . . . . . . . . . . . .
Burner removal . . . . . . . . . . . . . . . . . . . . . . . . . . . .
80
62
18
17
C
Calling up fault messages . . . . . . . . . . . . . 71
Cleaning agent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Cleaning cylinders . . . . . . . . . . . . . . . . . . . . . . . 22
Cleaning the combustion chamber 20
Cleaning the heating surfaces . . . . . . . 20
Code 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Code 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Coding during commissioning . . . . . . . 27
Condensate drain . . . . . . . . . . . . . . . . . . . . . . . . 21
Connection diagrams . . . . . . . . . . . . . . . . . . 106
Control unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90, 92
Cylinder primary temperature sensor .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
5692 619 GB
D
Diaphragm expansion vessel . . . . . . . . . . 7
Differential pressure sensor . . . . . . . . . . 85
Display elements . . . . . . . . . . . . . . . . . . . . 90, 92
E
Extension kit for heating circuit with
mixer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Extension
& external . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97, 98
& internal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95, 96
External blocking . . . . . . . . . . . . . . . . . . . . . . . . . 99
External demand. . . . . . . . . . . . . . . . . . . . . . . . . 100
F
Fault codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Fault display structure . . . . . . . . . . . . . . . . . . 69
Fault history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Fault memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Filling program. . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Filling the system . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Fitting the burner . . . . . . . . . . . . . . . . . . . . . . . . . 20
Flow temperature sensor . . . . . . . . . . . . . . 80
Flue gas temperature sensor . . . . . . . . 82
Function descriptions . . . . . . . . . . . . . . . . . . . 90
Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
G
Gas combination valve . . . . . . . . . . . . . . . . . 14
Gas supply pressure . . . . . . . . . . . . . . . . . . . . 14
Gas type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
H
Heating curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Heating curve level . . . . . . . . . . . . . . . . . . . . . . 33
Heating curve slope . . . . . . . . . . . . . . . . . . . . . 33
Heating program changeover . . . . . . . . 99
Heat-up time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Hiding a fault display . . . . . . . . . . . . . . . . . . . . 70
I
Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Ignition electrodes . . . . . . . . . . . . . . . . . . . . . . . 19
Initial start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Ionisation current . . . . . . . . . . . . . . . . . . . . . . . . . 26
Ionisation electrode. . . . . . . . . . . . . . . . . . . . . . 19
L
Language selection . . . . . . . . . . . . . . . . . . . . . . . . 9
LON communication module . . . . . . . . . 35
LON system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Lower rated output . . . . . . . . . . . . . . . . . . . . . . . 24
M
Manufacturer's declaration . . . . . . . . . . 120
121
Keyword index
Keyword index (cont.)
O
Outlet temperature sensor . . . . . . . . . . . . 82
Outside temperature sensor . . . . . . . . . 79
P
Parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Plate-type heat exchanger . . . . . . . . . . . . 83
Product characteristics . . . . . . . . . . . . . . . . 118
Protective anode
& Checking the anode . . . . . . . . . . . . . . . . . . . 21
R
Raising the reduced room
temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Reduced room temperature . . . . . . . . . . 35
Reducing the heat-up output . . . . . . . . 103
Reducing the heat-up time . . . . . . . . . . . 104
Relay test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Replacing the magnesium anode . . 22
Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Resetting codes . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
S
Safety chain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Scanning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Scanning operating conditions . . . . . . 67
Scanning sensors . . . . . . . . . . . . . . . . . . . . . . . . 67
Screed drying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Screed function . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Service level summary . . . . . . . . . . . . . . . . . 61
Setting the date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Setting the output. . . . . . . . . . . . . . . . . . . . . . . . . 15
Setting the time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Soundness test, balanced flue system
15
Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Standard room temperature . . . . . . . . . . 34
Static pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Supply pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . 13
System design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
System designs . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
System pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
System version . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
T
Temperature limiter . . . . . . . . . . . . . . . . . . . . . .
Temperature scans . . . . . . . . . . . . . . . . . . . . . .
Testing functions . . . . . . . . . . . . . . . . . . . . . . . . . .
Testing outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Testing the magnesium anode . . . . . .
84
62
65
65
22
U
Upper rated output . . . . . . . . . . . . . . . . . . . . . . . 25
V
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Venting program . . . . . . . . . . . . . . . . . . . . . . . . . 100
Vitotronic 050 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
5692 619 GB
W
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
122
123
5692 619 GB
124
Viessmann Limited
Hortonwood 30, Telford
Shropshire, TF1 7YP, GB
Telephone: +44 1952 675000
Fax: +44 1952 675040
E-mail: [email protected]
chlorine-free bleached paper
Printed on environmentally-friendly,
Viessmann Werke GmbH&Co KG
D-35107 Allendorf
Telefon: +49 6452 70-0
Telefax: +49 6452 70-2780
www.viessmann.de
5692 619 GB
Compact gas fired condensing boiler
Type WS3A
4.2 to 13 kW
from serial no.
7190 613 ...
6.6 to 26 kW
from serial no.
7190 614 ...
Subject to technical modifications.
Applicability