Download MicroNet InTagral Plus Specifications
Transcript
Current Ratings 24 VA at 24 Vac, pilot duty. Universal Inputs 10KW Thermistor w/ 11KW Shunt Resistor -40 to 250 °F (-40 to 121 °C) range. TS-5700-850 or equivalent. Voltage 0 to 5 Vdc. Current 0 to 20 mA requires an external 500 ohm shunt resistor. Digital Input Dry Contact. Detection of closed switch requires less than 300 ohm. Detection of open switch requires more than 1.5K ohm. Analog Outputs Current 0 to 20 mA. (Output load from 80 to 550 ohms). Software Capabilities • • • LONMARK-compatible. HVAC interoperability achieved through use of LONMARK HVAC profiles. Pre-packaged factory installed software customized for optimum unit operation. Communications LONWORKS Networks A LONWORKS communications network uses an FTT-10 Free Topology configuration. Controllers on a LONWORKS network can communicate with each other in a peer-to-peer fashion, and connect to the WorkPlace Tech Tool software platforms via the LON Jack on any LonMark controller or on any MN-Sx sensor. The wall sensor must be connected to the LON network. A LONWORKS network has acommunications speed of 78k baud, using unshielded,twisted-pair cabling. S-Link A Sensor Link (S-Link) communications wiring provides power and communication interface to the I/A Series MicroNet sensor (MN-SX series). It uses two-wire, unshielded cable and is not polarity sensitive. From some sensor models, the user can view and adjust application parameters. Maximum wire length allowed between a controller and the I/A Series MicroNet Sensor is 200 ft. (61 m). In a continuing effort toward product improvement the following PRODUCT INFORMATION IS SUBJECT TO CHANGE WITHOUT NOTICE 7/1/03 Part Number 011-200001-003