Download BT 1050 Technical information
Transcript
10.7 Input technical data Switch box Maximum voltage Maximum current 32 Vdc (no load, open circuit) 3 mAdc (short circuit) Lockout (link) Maximum voltage Maximum pulldown voltage Maximum current 32 Vdc (no load, open circuit) 0.25 Vdc 1.5 mAdc ve 10.8 Output technical data Relay(s) ac motor load A rc Pilot duty load Electrical life (operations) Mechanical life (operations) RS485 2 x single pole changeover relays (SPCO) 250 Vac 3 amp @ 250 Vac 1 amp @ 250 Vac ¼ HP (2.9 amp) @ 250 Vac 1 /10 HP (3 amp) @ 120 Vac C300 (2.5 amp) - control circuit/coils 3 x 105 or greater depending on load 30 x 106 hi Contacts Voltage ratings (maximum) Resistive load Inductive load Physical layer Protocol Isolation Receiver unit load Output rate RS485 4-wire full or 2-wire half duplex Modbus RTU format 60 Vac/dc (256 devices - maximum) Up to 10 frames / second 10.9 Infrared Physical layer IrDA Baud Range Working angle 38400 10 cm 15° Exempt from EN 60825-12: 2007 Safety of laser products- does not exceed the accessible emission limits (AEL) of class 1 Eye safety information 42 IM-P405-39 AB Issue 1