Download Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA Operating instructions
Transcript
To Begin Component Self-Test: ¥.t_ _I_ Blower access panel control. No component door switch operation taken when manually Failure _ closing iniury, i. Remove access 4. For approximately Caution to must be in electrical R lead from furnace door enclosure. nal on control until shock, control. (iumper) If TEST/TWIN longer than 2 sec, LED will quick-connect goes of£ Remover ONLY are jumpered a. LED will and ignore component b. Inducer motor component c. After is as follows: display combustion-air furnace, previous starts and reset switch. press Condensate button to gas occurs in buruer supply or im- DO NOT jumper check flame roll-out manual to reset Trap With trap must be PRIMED be primed of condensate i. test sequence inadequate condition If necessary, Condensate from test request. Component (flame rollout) reset switch switch. Water termi- jumper COM-24V terminals flash rapidly reset limit switch condition occur. The condensate and with a manual will open and shut offpower the COM-24V terminal (See Fig. 31.) NOTE: operating for continuity. Step 2--Prime 3/16-inch the LED Correct proper venting this switch. switch. 2 sec, short are equipped valve if an overheat Before to the TEST/TWIN terminals. power door. close blower on control can occnr. could result the thermostat 3. Manually 115-v or death. blower 2. Disconnect opens furnaces in burner box. This switch this switch for smwice purposes. to follow this warning personal These Remove or proper trap has 2 intemal by pouring draining chambers water into the inducer may not which can drain side trap. upper inducer housing drain connection cap. (See Fig. 55.) stares code 4 times. and continues to run until Step g of test sequence. 7 seconds the hot suri_ace igniter is energized for 15 sec., then of£ d. Blower motor operates on Continuous-FAN speed for I0 sec. e. Blower motor operates on HEAT speed for 10 sec. f. Blower motor operates on COOL speed for I0 sec. g. Inducer 5. Reconnect motor door switch, 6. Operate 7. Verify furuace room 8. Verify roolI1 and re-install furuace below stops. R lead to furuace per instruction shut down remove tape l'rom blower door. on outer door. by lowering thermostat setting temperature. that furuace restarts by raising thermostat setting above temperature. START-UP Step control, blower PROCEDURES \ 1--General i. Furnace must have a 115-v power supply properly connected and grounded. NOTE: polarity Proper polarity is incorrect, and furnace must be maintained control for 115-v wiring. LED status indicator If A99118 will flash rapidly Fig. 55--Inducer will not operate. 2. Thermostat wire connections at terminals R, W, G, and Y/Y2 nmst be made at 24-v terminal block on furnace control. 3. Natural gas selwice pressure must not exceed wc), and be no less than 0.16 psig (4.5-in. 4. Blower access panel must electrical circuit to furuace. be in place 2. Connect field-supplied ii2-in. housing drain connection. 0.5 psig (14-in. 3. Insert field-supplied wc). to complete Housing Drain Tube Cap ID robe to upper inducer funnel into robe. 4. Pour 1 quart of water into l'unnelimbe. Water should run through inducer housing, overfill condensate trap, and flow into open field drain. (See Fig. 56.) l15-v 5. Remove funnel and robe from inducer housing and replace drain connection cap and clamp. 39