Transcript
Mounting the ECL Comfort controller For easy access, you should mount the ECL Comfort controller near the system. Select one of the three following methods: • Mounting on a wall • Mounting on a DIN rail • Mounting in a panel Screws and rawlplugs are not supplied. Mounting on a wall Socket for mounting on wall: Order code No. 087B1149. Mount the terminal box on a wall with a smooth surface. Establish the electrical connections and position the controller in the box. Secure the controller with the fixing screw. Mounting on a DIN rail Mounting kit: Order code No. 087B1145. A mounting kit is necessary to mount the box with the controller on a DIN rail. Mounting in a panel Connector set: Order code No. 087B1148. The panel plate thickness must not exceed 3 mm. Prepare a cut-out with the dimensions 93 x 139 mm. Pull off the right side of the lid by means of a screwdriver. Insert the controller into the panel cut-out and fix it with the two locks which are placed diagonally in two corners of the controller. 11b Installation Installation 11a