Download AMD LV-651 User's Specifications
Transcript
Programming Menu • Softstart UK 3 Secondary Start/Stop See the Primary Start/Stop parameters for parameter details. 3A – Start Mode-2 Options: Description: Constant Current (default) Adaptive Control Selects the soft start mode. 3B – Current Limit-2 Range: Description: 100% - 600% FLC Default: 350% Sets the current limit for constant current and current ramp soft starting, as a percentage of motor full load current. 3C – Initial Current-2 Range: Description: 100% - 600% Default: 350% Sets the initial start current level for current ramp starting, as a percentage of motor full load current. Set so that the motor begins to accelerate immediately after a start is initiated. If current ramp starting is not required, set the initial current equal to the current limit. 3D – Start Ramp Time-2 Range: Description: 1 - 180 (seconds) Default: 10 seconds Sets the total start time for an Adaptive Control start or the ramp time for current ramp starting (from the initial current to the current limit). 3E – Kickstart Level-2 Range: Description: 100% - 700% FLC Sets the level of the kickstart current. Default: 500% 3F – Kickstart Time-2 Range: Description: 0 - 2000 (milliseconds) Sets the kickstart duration. Default: 0000 milliseconds A setting of 0 disables kickstart. 3G – Excess Start Time-2 Range: Description: 0:00 - 4:00 (minutes:seconds) Set as required. Default: 20 seconds Default: 0 second 3H – Stop Mode-2 Options: Description: Coast To Stop (default) TVR Soft Stop Adaptive Control Brake Selects the stop mode. 3I – Stop Time-2 Range: Description: 0:00 - 4:00 (minutes:seconds) Sets the stop time. 3J – Adaptive Start Profile-2 Options: Description: Early Acceleration Constant Acceleration (default) Late Acceleration Selects which profile the LV-DS will use for an Adaptive Control soft start. 3K – Adaptive Stop Profile-2 Options: Description: Early Deceleration Constant Deceleration (default) Late Deceleration Selects which profile the LV-DS will use for an Adaptive Control soft stop. 3L – Adaptive Control Gain-2 Range: Description: 38/64 1% - 200% Default: 75% Adjusts the performance of Adaptive Control. This setting affects both starting and stopping control. 710-15797-00A – LV-DS User Manual