Programming Menu
•
Softstart UK
3 Secondary Start/Stop
See the Primary Start/Stop parameters for parameter details.
3A – Start Mode-2
Options:
Description:
Constant Current (default)
Adaptive Control
Selects the soft start mode.
3B – Current Limit-2
Range:
Description:
100% - 600% FLC
Default: 350%
Sets the current limit for constant current and current ramp soft starting, as a
percentage of motor full load current.
3C – Initial Current-2
Range:
Description:
100% - 600%
Default: 350%
Sets the initial start current level for current ramp starting, as a percentage of motor
full load current. Set so that the motor begins to accelerate immediately after a start
is initiated.
If current ramp starting is not required, set the initial current equal to the current limit.
3D – Start Ramp Time-2
Range:
Description:
1 - 180 (seconds)
Default: 10 seconds
Sets the total start time for an Adaptive Control start or the ramp time for current ramp
starting (from the initial current to the current limit).
3E – Kickstart Level-2
Range:
Description:
100% - 700% FLC
Sets the level of the kickstart current.
Default:
500%
3F – Kickstart Time-2
Range:
Description:
0 - 2000 (milliseconds)
Sets the kickstart duration.
Default: 0000 milliseconds
A setting of 0 disables kickstart.
3G – Excess Start Time-2
Range:
Description:
0:00 - 4:00 (minutes:seconds)
Set as required.
Default:
20 seconds
Default:
0 second
3H – Stop Mode-2
Options:
Description:
Coast To Stop (default)
TVR Soft Stop
Adaptive Control
Brake
Selects the stop mode.
3I – Stop Time-2
Range:
Description:
0:00 - 4:00 (minutes:seconds)
Sets the stop time.
3J – Adaptive Start Profile-2
Options:
Description:
Early Acceleration
Constant Acceleration (default)
Late Acceleration
Selects which profile the LV-DS will use for an Adaptive Control soft start.
3K – Adaptive Stop Profile-2
Options:
Description:
Early Deceleration
Constant Deceleration (default)
Late Deceleration
Selects which profile the LV-DS will use for an Adaptive Control soft stop.
3L – Adaptive Control Gain-2
Range:
Description:
38/64
1% - 200%
Default: 75%
Adjusts the performance of Adaptive Control. This setting affects both starting and
stopping control.
710-15797-00A – LV-DS User Manual