FORM 100.50-NOM6 (1207) TABLE 7-1 – DEFINITIONS (CONTINUED) MENU ITEM DEFINITION ERV UNOCCUPIED FAN ENABLE THIS PARAMETER ALLOWS THE EXHAUST FAN TO OPERATE ANYTIME THE SUPPLY FAN IS ON. THIS FEATURE IS REQUIRED WHEN AN ENERGY RECOVERY VENTILATOR IS INSTALLED. THIS FEATURE IS CURRENTLY NOT USED ON THESE UNITS. EXHAUST DAMPER POSITION FOR EXHAUST TO TURN OFF WHEN MODULATING DAMPER EXHAUST IS BEING USED THIS IS THE POSITION OF THE EXHAUST DAMPER TO TURN OFF THE EXHAUST FAN EXHAUST DAMPER POSITION FOR EXHAUST TO TURN ON WHEN MODULATING DAMPER EXHAUST IS BEING USED THIS IS THE POSITION OF THE EXHAUST DAMPER TO TURN ON THE EXHAUST FAN EXHAUST FAN OUTPUT THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE UNIT CONTROLLER TO THE EXHAUST FAN, OFF OR ON EXHAUST DAMPER / VFD OUTPUT STATUS THIS GIVES THE STATUS OF THE ANALOG UNIT CONTROLLER OUTPUT TO THE EXHAUST DAMPER OR EXHAUST FAN VFD IN % EXHAUST VFD INSTALLED THIS PARAMETER IDENTIFIES TO THE UNIT CONTROLLER THAT AN EXHAUST FAN VFD IS INSTALLED. THE PARAMETER MUST BE TURNED ON TO ENABLE THIS FEATURE FAN (G) THERMOSTAT INPUT THIS GIVES THE STATUS OF THE BINARY INPUT TO THE G TERMINAL OF THE UNIT CONTROLLER, OFF OR ON FAN ASD TIMER THIS IS THE STATUS OF THE SUPPLY FAN OFF DELAY IN SECONDS FAN OFF DELAY TIMER FOR COOL THIS GIVES THE STATUS OF THE COOLING TIME OFF DELAY IN SECONDS FAN OFF DELAY TIMER FOR HEAT THIS GIVES THE STATUS OF THE COOLING TIME OFF DELAY IN SECONDS FAN ON DELAY TIMER FOR COOL THIS GIVES THE STATUS OF THE COOLING TIME ON DELAY IN SECONDS FAN ON DELAY TIMER FOR HEAT THIS GIVES THE STATUS OF THE COOLING TIME ON DELAY IN SECONDS FREEZE THERMOSTAT SWITCH THIS IS THE BINARY INPUT FROM THE HYDRONIC HEAT FREEZE STAT TO THE UNIT CONTROLLER. OFF = FAULTED, ON = NORMAL OPERATION GAS VALVE #1 THIS IS THE STATUS OF THE BINARY INPUT FROM THE GAS VALVE FOR HEAT SECTION 1 TO THE UNIT CONTROLLER OFF / ON GAS VALVE #2 THIS IS THE STATUS OF THE BINARY INPUT FROM THE GAS VALVE FOR HEAT SECTION 2 TO THE UNIT CONTROLLER OFF / ON GAS VALVE #3 THIS IS THE STATUS OF THE BINARY INPUT FROM THE GAS VALVE FOR HEAT SECTION 3 TO THE UNIT CONTROLLER OFF / ON HEAT 1 (W1) THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL W1 - FIRST STAGE HEATING HEAT 1 ASCD TIMER THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR HEAT SECTION 1 IN SECONDS. Continued on next page JOHNSON CONTROLS 145 7