Download Baxi 80 HE Technical data
Transcript
30 7.0 Site Requirements 50 28 7.9 &8 26 NOTE: Please read this section in conjunction with the instructions supplied in the kit. The table opposite supplements information in the kit literature. 0 24 22 0/2 10 20 70Ø Exhaust (metres) X 18 Plume Displacement Kit 1. This kit is recommended for installations where the condensate plume emitted from the flue may cause a nuisance or affect the surroundings. 2. The flue consists of two main parts. The concentric part, most of which is fitted inside and the 70Ø part which is entirely outside the building. 16 14 3. Full fitting details are supplied with the kit. The table and illustration opposite show the maximum permissible lengths of each part of the flue (Fig 17a). 12 10 4. The required length of one part of the flue affects the maximum permissible length of the other. For example, when fitting a 100/2 HE the table shows that if 14 metres of 70Ø are required outside, up to 2 metres of concentric flue can be used. 8 6 4 5. This is determined by finding the 14 metre mark on the left hand part of the graph, and tracing across to the sloping line marked ‘100/2 HE’. Then trace vertically down to the bottom part of the graph - this gives a concentric maximum of 2 metres. 2 0 0 1 2 3 4 Concentric 70/110 Flue (metres) Y Fig. 17a 6. Further worked examples are shown in the literature supplied with the kit. IMPORTANT: If fitting a Plume Displacement Flue Kit, the air inlet must be a minimum of 100mm from any opening windows or doors (see Section 7.9). 70Ø Exhaust X Plume Displacement Kit Y Air Inlet Concentric 70/110 Flue (MUST be installed horizontally) Fig. 17b © Baxi Heating UK Ltd 2006 Opening Window or Door 100mm MIN. Fig. 17c 21