Download Raypak 1005 Operating instructions

Transcript
Model
No.
Certified
Vent
Material
1005
1505
Vent Size
(in.)
Vertical Vent
Height1 (ft)
Min.
Max.
6
Category IV
(AL29-4C)
0
75
8
2005
Combustion Air
Intake Pipe
Material
Galvanized
Steel,
PVC,
ABS,
CPVC
Air Inlet
Max. Length* (ft)
6” Ø
8” Ø
45
100**
45
10” Ø
85**
1 Vent lengths are based on a lateral length of 2 ft. Refer to the latest edition of the NFGC for further details.
* Subtract 10 ft per elbow. Max. 4 elbows.
** Adapters supplied by others.
Table M: Category IV Vertical Venting
nal. The horizontal portions of the vent shall also be
supported for the design and weight of the material
employed to maintain clearances and to prevent physical damage or separation of joints.
NOTE: A vent adapter (field-supplied) may be required to connect the Category IV vent to the heater.
Termination
The vent terminal should be vertical and should terminate outside the building at least 2 ft above the highest
point of the roof that is within 10 ft. The vent cap
should have a minimum clearance of 4 ft horizontally
from and in no case above or below (unless a 4 ft horizontal distance is maintained) electric meters, gas
meters, regulators and relief equipment.
The distance of the vent terminal from adjacent public
walkways, adjacent buildings, open windows and
building openings must be consistent with the NFGC
(U.S.) or B149 (Canada). Gas vents supported only by
flashing and extended above the roof more than 5 ft
should be securely guyed or braced to withstand snow
and wind loads.
Fig. 23: Vertical Venting