Transcript
12 Motor Protection / 7SK80 Application ANSI No. IEC Protection functions 50, 50N I>, I>>, I>>>, IE>, IE>>, IE>>> Instantaneous and definite time-overcurrent protection (phase/neutral) 51, 51N Ip, IEp Inverse time-overcurrent protection (phase/neutral) 67N IEdir>, IEdir>>, IEp dir Directional overcurrent protection, ground (definite/inverse) 67Ns/50Ns IEE>, IEE>>, IEEp Directional/non-directional sensitive ground-fault detection Cold load pick-up (dynamic setting change) – 59N/64 VE, V0> Displacement voltage, zero-sequence voltage Breaker failure protection 50BF 46 I2> Phase-balance current protection (negative-sequence protection) 47 V2>, phase-sequence Unbalance-voltage protection and/or phase-sequence monitoring Starting time supervision 48 ϑ> 49 Thermal overload protection 51M Load jam protection 14 Locked rotor protection 66/86 Restart inhibit 37 I< Undercurrent monitoring Temperature monitoring via internal RTD inputs or external device (RTD-box), e.g. bearing temperature monitoring 38 27, 59 V<, V> Undervoltage/overvoltage protection 32 P<>, Q<> Forward-power, reverse-power protection 55 cos ϕ Power factor 81O/U f>, f< Overfrequency/underfrequency protection 81R df/dt Rate-of-frequency-change protection 12 Siemens SIP · 2008 12/11