Programming Switching diff on HCs (2454) Switching diff off min HCs (2455) Switching diff off max HCs (2456) Switching diff on DHW (2460) Switching diff off min DHW (2461) Switching diff off max DHW (2462) To avoid unnecessary switch off during transient effects the switch off difference adapts dynamically depending on the temperature profile (see Fig. 21). Fig. 21: Switching differential Tc Switching diff off Switching diff off max HCs/DHW (2456/2462) Switching diff off min HCs/DHW (2456/2462) Switching diff on HCs/DHW duration Tc (Current temperature) t Pressure switch shutdown (2500) 8.16 Cascade Lead strategy (3510) This function checks the static water pressure with the aid of the connected water pressure switch. Depending on the set option (start prevention or lockout position) with shutdown either a start prevention or lockout position occurs with the corresponding diagnostics. A closed water pressure switch releases the commissioning on the burner control and the actuation of the pumps. With open pressure switch a start prevention or lockout position is triggered. The pump actuation is also locked for protection against dry running. If the water pressure increases again and the switch closes again , with a start prevention these are automatically again cancelled and the pump actuation is again released. Considering the specified output range the heat generation is switched on and off according to the set lead strategy. To switch off the effect of the output range, the limits must be set to 0% and 100% and the lead strategy to late on, late off. - Late on, early off: additional boiler is switched on as late as possible (output range max) and back off as early as possible (output range max). I.e. boiler in operation as little as possible, or short running times for additional boiler. - Late on, late off: additional boiler is switched on as late as possible (output range max) and back off as late as possible (output range min). I.e. as few as possible on and off processes for the boiler. - Early on, late off: additional boiler is switched on as early as possible (output range min) and back off as late as possible (output range min). I.e. boiler in operation as much as possible, or as long as possible running times for additional boiler. Release integral source seq (3530) A value generated from temperature and time. The following boiler will be switched on in case of exceeding the set limit. . Reset integral source seq (3531) The following boiler will be switched off in case of exceeding the setpoint 396532 07.11 Paramount three 30-115 kW 89