Download APC UXICH 3000 Specifications
Transcript
ATTACH THE BEZEL TO THE UPS HARDWIRING INSTRUCTIONS • Wiring must be performed by a qualified electrician. • Adhere to all national and local electrical codes. • Install a utility circuit breaker for input wiring, (see tables below). 220/230/240 V MODELS Input Connections Output Connection (optional) Single-Phase: Wire to L1, N, and Three-Phase: Wire to L1, L2, L3, N, and System SURT8000 SURT10000 Wire to L1A, N1, and . . . Wiring Number of Phases Voltage Current Full Load (Nominal) External Input Circuit Breaker (Typical) Wire Size (Typical) Input 1 220/230/240 V 40 A 50 A / 2-pole 10mm2 Input 3+ Neutral 380/400/415 V 15 A / phase when online 40 A on L1 in bypass 50 A / 4-pole 10mm2 Output 1 220/230/240 V 40 A (not required) 10mm2 Input 1 220/230/240 V 50 A 63 A / 2-pole 16mm2 Input 3+ Neutral 380/400/415 V 18 A / phase when online 50 A on L1 in bypass 63 A / 4-pole 16mm2 Output 1 220/230/240 V 50 A (not required) 16mm2 2