Download Airwell YUDA060 Setup guide

Transcript
Fixed Speed
DK DN
q Cooling and heating mode
q Cooling capacity: from 37.5 to 83 kW
q Heating capacity: from 36.5 to 83.8 kW
q Refrigerant: R407C
G
ON/OFF DUCTED HIGH STATIC PRESSURE
O
OD
QUALITY
PEED
FIXED S O
I
Made
in
France
P R I C E R AT
R407C FLUID
[ PRODUCT ADVANTAGES ]
Weather resistant casing with external
panels coated with powder-based
epoxy paint colour RAL 7040.
Indoor centrifugal fan units for duct
network connection.
High static pressure available.
Multi-position architecture for horizontal or vertical mounting (acc. to
models).
Compact, top discharge outdoor fan
units.
Scroll compressor with crankcase
heater.
Electrical, refrigeration and thermal
protection devices.
Phase controller.
External HP and LP pressure taps.
Frame and air filter supplied.
MAIN OPTIONS
Low ambient temperature control to ensure
cooling operation down to -10°C outdoor
temperature (All-season).
MAIN ACCESSORIES
Synthetic air filter.
Electric heater.
Programmable controller RCW2 to control
up to 15 units with independent set points
and programming.
OPERATING LIMIT FOR STANDARD UNIT
Cooling mode
Minimum indoor air temperature
21°C DB/15°C WB
Maximum indoor air temperature
32°C DB/23°C WB
Minimum outdoor air temperature/with all-season kit
Maximum outdoor air temperature
15°C DB/-10°C
46°C DB
Heating mode
Maximum indoor air temperature
52
27°C DB
Minimum outdoor air temperature
-10°C
Maximum outdoor air temperature
24°C DB/18°C WB