Download Carrier 38GLS...G Installation manual
Transcript
38GLS...G Installation instructions supplement ENGLISH Head pressure controller: wiring diagram Pressure sensor Interface relay Dual speed fan motor Live power supply FM FC Neutral power supply FM = Fan motor FC = Fan capacitor Head pressure controller and HIP remote manual reset Configuration The head pressure control “HPC” is made of three parts: Pressure setting High speed pressure set at 2323 kPa (23.2 bar; 337 psig). Low speed pressure set at 1896 kPa (18.9 bar; 275 psig). • Dual speed fan motor. • Interface relay. • Pressure sensor, complete with 500 mm wiring. The high pressure switch “HIP” has been selected at automatic reset. If “HIP” trips, cycle the power supply OFF and ON to reset the system, because the electrical box is equipped with relays that prevent the unit from starting, until the indoor control is switched OFF. When head pressure drops below 3000 kPa (30 bar; 420 psig) it is possible to restart the unit switching the indoor control ON. Operations mode Troubleshooting See paragraph “Troubleshooting”. Note: At start-up or in case of re-start after a pause of several hours at – 10°C, with low voltage supply (198V) high pressure switch HIP may trip off the unit. In this case, the remote reset by indoor control (infrared) can be done for unit restarting. High speed: If the condensing pressure is above the high pressure limit, the fan operates at high speed. Low speed: If the condensing pressure is below the low pressure limit, the fan operates at low speed. Hard start: At each compressor starting the fan motor high speed is reached by the pressure sensor operation. GB - 15