Download ClimateMaster OE Series Unit installation
Transcript
THE SMART SOLUTION FOR ENERGY EFFICIENCY Genesis Large (GL) Series R e v. : 1 3 A p r i l , 2 0 0 9 B Table 4B: GLV Electrical Data All GLV Units Standard GLV Unit Compressor Fan Motor FLA Min Circuit Amp Model Voltage Code Voltage Min/ Max Voltage Blower Option GLV080 H 208-230/60/3 197/253 A, B, C 1 20.7 156 5.0 25.7 30.9 50 1.1 26.8 32.0 50 GLV080 H 208-230/60/3 197/253 E 1 20.7 156 6.2 26.9 32.1 50 1.1 28.0 33.2 50 GLV080 F 460/60/3 414/506 A, B, C 1 10.0 75 2.4 12.4 14.9 20 0.6 12.9 15.4 25 QTY RLA LRA Total Unit FLA GLV unit with ClimaDry Reheat Min Circuit Amp Max Fuse/ HACR Reheat Pump FLA Total Unit FLA Max Fuse/ HACR GLV080 F 460/60/3 414/506 E 1 10.0 75 3.1 13.1 15.6 25 0.6 13.7 16.2 25 GLV080 N 575/60/3 518/633 A, B, C 1 8.2 54 1.9 10.1 12.1 20 0.4 10.5 12.6 20 GLV080 N 575/60/3 518/633 E 1 8.2 54 2.3 10.5 12.5 20 0.4 10.9 13.0 20 GLV100 H 208-230/60/3 197/253 A, B 1 32.1 195 5.8 37.9 45.9 70 2.0 39.1 47.1 70 GLV100 H 208-230/60/3 197/253 E 1 32.1 195 6.2 38.3 46.3 70 2.0 40.3 48.3 80 GLV100 F 460/60/3 414/506 A, B 1 16.4 95 2.4 18.8 22.9 35 1.0 19.8 23.9 40 GLV100 F 460/60/3 414/506 E 1 16.4 95 3.1 19.5 23.6 40 1.0 20.5 24.6 40 GLV100 N 575/60/3 518/633 A, B 1 12.0 80 1.9 13.9 16.9 25 0.8 14.7 17.7 25 GLV100 N 575/60/3 518/633 E 1 12.0 80 2.3 14.3 17.3 25 0.8 15.1 18.1 30 GLV120 H 208-230/60/3 197/253 A, B, C 1 33.6 225 6.2 39.8 48.2 80 2.0 41.8 50.2 80 GLV120 H 208-230/60/3 197/253 E 1 33.6 225 8.4 42.0 50.4 80 2.0 44.4 52.8 80 GLV120 F 460/60/3 414/506 A, B, C 1 17.3 114 3.1 20.4 24.5 40 1.0 21.4 25.7 40 GLV120 F 460/60/3 414/506 E 1 17.3 114 4.2 21.5 25.8 40 1.0 22.5 26.8 40 GLV120 N 575/60/3 518/633 A, B, C 1 13.5 80 2.3 15.8 19.2 30 0.8 16.6 20.0 30 GLV120 N 575/60/3 518/633 E 1 13.5 80 3.4 16.9 20.3 30 0.8 17.7 21.1 30 GLV160 H 208-230/60/3 197/253 A, B, C 2 20.7 156 8.4 49.8 55.0 70 2.0 52.2 57.3 70 GLV160 F 460/60/3 414/506 A, B, C 2 10.0 74 4.2 24.2 26.7 35 1.0 25.2 27.7 35 GLV160 N 575/60/3 518/633 A, B, C 2 8.2 54 3.4 19.8 21.9 30 0.8 20.6 22.6 30 GLV200 H 208-230/60/3 197/253 A, B 2 32.1 195 5.0 74.2 75.8 110 2.0 76.2 84.2 110 GLV200 H 208-230/60/3 197/253 E 2 32.1 195 6.2 76.6 84.6 110 2.0 78.6 86.6 110 GLV200 F 460/60/3 414/506 A, B 2 16.4 95 2.4 37.6 41.7 50 1.0 38.6 42.7 50 GLV200 F 460/60/3 414/506 E 2 16.4 95 3.1 39.0 43.1 50 1.0 40.0 44.1 60 GLV200 N 575/60/3 518/633 A, B 2 12.0 80 1.9 27.8 30.8 40 0.8 28.6 31.6 40 GLV200 N 575/60/3 518/633 E 2 12.0 80 2.3 28.6 31.6 40 0.8 29.4 32.4 40 GLV240 H 208-230/60/3 197/253 A, B, C 2 33.6 225 6.2 79.6 88.0 110 4.5 84.1 92.5 125 GLV240 H 208-230/60/3 197/253 E 2 33.6 225 8.4 84.0 92.4 125 4.5 89.3 97.7 125 GLV240 F 460/60/3 414/506 A, B, C 2 17.3 114 3.1 40.8 45.1 60 2.3 43.0 47.4 60 GLV240 F 460/60/3 414/506 E 2 17.3 114 4.2 43.0 47.3 60 2.3 45.3 49.6 60 GLV240 N 575/60/3 518/633 A, B, C 2 13.5 80 2.3 31.6 35.0 45 1.8 33.4 36.8 50 GLV240 N 575/60/3 518/633 E 2 13.5 80 3.4 33.8 37.2 50 1..8 35.6 39.0 50 GLV300 H 208-230/60/3 197/253 A, C 2 47.1 245 8.4 111.0 122.8 150 4.5 116.3 128.1 175 GLV300 F 460/60/3 414/506 A, C 2 19.6 125 4.2 47.6 52.5 70 2.3 49.8 54.8 70 GLV300 N 575/60/3 518/633 A, C 2 15.8 100 3.4 38.4 42.4 50 1.8 40.2 44.2 50 HACR circuit breaker in USA only All fuses Class RK-5 Note: Compressor RLA & LRA values are per compressor Compressor RLA & LRA values are per compressor. * NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ClimaDry require a four wire power supply with neutral. Reheat pump is rated 265 vac and are wired between one hot leg and neutral. c l i m a t e m a s t e r. c o m 25