Download ClimateMaster OE Series Unit installation

Transcript
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Genesis Large (GL) Series
R e v. : 1 3 A p r i l , 2 0 0 9 B
Table 4B: GLV Electrical Data
All GLV Units
Standard GLV Unit
Compressor
Fan
Motor
FLA
Min
Circuit
Amp
Model
Voltage
Code
Voltage
Min/
Max
Voltage
Blower
Option
GLV080
H
208-230/60/3
197/253
A, B, C
1
20.7
156
5.0
25.7
30.9
50
1.1
26.8
32.0
50
GLV080
H
208-230/60/3
197/253
E
1
20.7
156
6.2
26.9
32.1
50
1.1
28.0
33.2
50
GLV080
F
460/60/3
414/506
A, B, C
1
10.0
75
2.4
12.4
14.9
20
0.6
12.9
15.4
25
QTY
RLA
LRA
Total
Unit
FLA
GLV unit with ClimaDry Reheat
Min
Circuit
Amp
Max
Fuse/
HACR
Reheat
Pump
FLA
Total
Unit
FLA
Max
Fuse/
HACR
GLV080
F
460/60/3
414/506
E
1
10.0
75
3.1
13.1
15.6
25
0.6
13.7
16.2
25
GLV080
N
575/60/3
518/633
A, B, C
1
8.2
54
1.9
10.1
12.1
20
0.4
10.5
12.6
20
GLV080
N
575/60/3
518/633
E
1
8.2
54
2.3
10.5
12.5
20
0.4
10.9
13.0
20
GLV100
H
208-230/60/3
197/253
A, B
1
32.1
195
5.8
37.9
45.9
70
2.0
39.1
47.1
70
GLV100
H
208-230/60/3
197/253
E
1
32.1
195
6.2
38.3
46.3
70
2.0
40.3
48.3
80
GLV100
F
460/60/3
414/506
A, B
1
16.4
95
2.4
18.8
22.9
35
1.0
19.8
23.9
40
GLV100
F
460/60/3
414/506
E
1
16.4
95
3.1
19.5
23.6
40
1.0
20.5
24.6
40
GLV100
N
575/60/3
518/633
A, B
1
12.0
80
1.9
13.9
16.9
25
0.8
14.7
17.7
25
GLV100
N
575/60/3
518/633
E
1
12.0
80
2.3
14.3
17.3
25
0.8
15.1
18.1
30
GLV120
H
208-230/60/3
197/253
A, B, C
1
33.6
225
6.2
39.8
48.2
80
2.0
41.8
50.2
80
GLV120
H
208-230/60/3
197/253
E
1
33.6
225
8.4
42.0
50.4
80
2.0
44.4
52.8
80
GLV120
F
460/60/3
414/506
A, B, C
1
17.3
114
3.1
20.4
24.5
40
1.0
21.4
25.7
40
GLV120
F
460/60/3
414/506
E
1
17.3
114
4.2
21.5
25.8
40
1.0
22.5
26.8
40
GLV120
N
575/60/3
518/633
A, B, C
1
13.5
80
2.3
15.8
19.2
30
0.8
16.6
20.0
30
GLV120
N
575/60/3
518/633
E
1
13.5
80
3.4
16.9
20.3
30
0.8
17.7
21.1
30
GLV160
H
208-230/60/3
197/253
A, B, C
2
20.7
156
8.4
49.8
55.0
70
2.0
52.2
57.3
70
GLV160
F
460/60/3
414/506
A, B, C
2
10.0
74
4.2
24.2
26.7
35
1.0
25.2
27.7
35
GLV160
N
575/60/3
518/633
A, B, C
2
8.2
54
3.4
19.8
21.9
30
0.8
20.6
22.6
30
GLV200
H
208-230/60/3
197/253
A, B
2
32.1
195
5.0
74.2
75.8
110
2.0
76.2
84.2
110
GLV200
H
208-230/60/3
197/253
E
2
32.1
195
6.2
76.6
84.6
110
2.0
78.6
86.6
110
GLV200
F
460/60/3
414/506
A, B
2
16.4
95
2.4
37.6
41.7
50
1.0
38.6
42.7
50
GLV200
F
460/60/3
414/506
E
2
16.4
95
3.1
39.0
43.1
50
1.0
40.0
44.1
60
GLV200
N
575/60/3
518/633
A, B
2
12.0
80
1.9
27.8
30.8
40
0.8
28.6
31.6
40
GLV200
N
575/60/3
518/633
E
2
12.0
80
2.3
28.6
31.6
40
0.8
29.4
32.4
40
GLV240
H
208-230/60/3
197/253
A, B, C
2
33.6
225
6.2
79.6
88.0
110
4.5
84.1
92.5
125
GLV240
H
208-230/60/3
197/253
E
2
33.6
225
8.4
84.0
92.4
125
4.5
89.3
97.7
125
GLV240
F
460/60/3
414/506
A, B, C
2
17.3
114
3.1
40.8
45.1
60
2.3
43.0
47.4
60
GLV240
F
460/60/3
414/506
E
2
17.3
114
4.2
43.0
47.3
60
2.3
45.3
49.6
60
GLV240
N
575/60/3
518/633
A, B, C
2
13.5
80
2.3
31.6
35.0
45
1.8
33.4
36.8
50
GLV240
N
575/60/3
518/633
E
2
13.5
80
3.4
33.8
37.2
50
1..8
35.6
39.0
50
GLV300
H
208-230/60/3
197/253
A, C
2
47.1
245
8.4
111.0
122.8
150
4.5
116.3
128.1
175
GLV300
F
460/60/3
414/506
A, C
2
19.6
125
4.2
47.6
52.5
70
2.3
49.8
54.8
70
GLV300
N
575/60/3
518/633
A, C
2
15.8
100
3.4
38.4
42.4
50
1.8
40.2
44.2
50
HACR circuit breaker in USA only
All fuses Class RK-5
Note: Compressor RLA & LRA values are per compressor
Compressor RLA & LRA values are per compressor.
* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ClimaDry require a four wire power supply with neutral.
Reheat pump is rated 265 vac and are wired between one hot leg and neutral.
c l i m a t e m a s t e r. c o m
25