Download Saftronics GP5 Series Specifications
Transcript
efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor Chapter 6: Programming Features § Terminal Function at 2-Wire Sequence Selection (Setting: 0) Figure 41 Terminal Function at 2-Wire Sequence Selection § Terminal Function at 3-Wire Sequence Selection (Setting: 1) Figure 42 Terminal Function at 2-Wire Sequence Selection § LOCAL/REMOTE Selection (Setting: 5) Selects operation reference by the Digital Operator or by the control circuit terminal. LOCAL/REMOTE selection is available only during stop. § Open : Run according to the setting of Operation mode selection (n022). Closed : Run by frequency reference and RUN command from the Digital Operator. (Example) Open : Set n002 to 3. Run by frequency reference from control circuit Terminals FV, FI and RUN command from control circuit Terminals S1, S2. Closed : Run by frequency reference and RUN command from the Digital Operator. Serial Communication/Control Circuit Terminal Selection (Setting: 6) Selects operation reference by serial communication or by the control circuit terminal. This selection is available only during stop. Firmware – S2011 and S3012 Revision: 1 (9/98) Open : Run according to the setting of Operation mode selection (n022). Closed : Run by frequency reference and RUN command from serial communication. (Example) Open : Set n002 to 3. Run by frequency reference from control circuit Terminals FV, FI and RUN command from control circuit Terminals S1, S2. Closed : Run by frequency reference and RUN command from serial communication. 51 © Saftronics, Inc.