Section 1—Installation & Configuration Trunk and Drop Cabling with Taps Bulletin No. VVDED397044US R12/00 December 2000 • For each drop cable, provide a service loop to allow the connector to be connected and disconnected at the network node device without any strain on the cable. A service loop of 6 in. (152 mm) minimum radius is adequate for most installations. • Install cable ties or clamps on each trunk cable segment as required for strain relief, to prevent the cable from pulling on the tap. • Install cable ties or clamps on each drop cable as required for strain relief, to prevent the cable from pulling on the tap or node device connector. • Use additional ties or clamps as required to secure each cable to prevent flexing or other damage in areas of mechanical motion devices and traffic. Mounting the Tap Mount each tap at a location near its node device, preferably outside the drive controller enclosure. The tap must be near enough to the node device to allow the drop cable to reach the node device with a service loop. See Figure 16 for drop cable routing. The location must also be accessible for installing the trunk and drop cables and for future maintenance. Figure 17 shows the tap’s outer and mounting dimensions. 3.16 (80.2) Mounting Centers 2.2 (56) Hole Diameter 0.2 (5) 4.4 (112) Dim: in (mm) Figure 17: Tap Layout (Cover Open) 26 © 1998–2000 Schneider Electric All Rights Reserved