Download Emerson ControlWave GFC Instruction manual
Transcript
ControlWave Gas Flow Computer (GFC Plus) Instruction Manual (CI-ControlWave GFC Plus) Port Loop-back Test Option Tests COM2, and COM3. The External loop-back tests require the use of a loop-back plug. Discrete I/O Checks DIs and DOs on the Process I/O board. EEPROM Checks the EEPROM. Keyboard & Display Checks the optional display/keypad hardware. WINDIAG allows you to select the communication port to test. Depending on the type of network (RS-232 or RS-485) and the port in question, a special loop-back plug is required: Port 1 - RS-232 uses a 9-pin female D-type loop-back plug (see Figure 5-6). Figure 5-6. COM1 & COM2 RS-232 Loop-back Plug/Wires Port 2 - RS-232 use loop-back wires (see Figure 5-6). Port 3 - RS-232 use loop-back wires (see Figure 5-7). Figure 5-7. COM3 RS-232 & RS-485 Loop-back Wires Revised Feb-2013 Service & Troubleshooting 5-15