Download Columbia CSVB-3 Operating instructions
Transcript
SEQUENCE OF OPERATION Sequence of Operation -See Figure 12, Page 23 1. Thermostat calls for heat, control relay contacts. 2. Circulator pump is powered through terminals C1 and C2. Control holds off burner and attempts to satisfy thermostat with residual boiler heat. 3. Induced draft blower and transformer primary are powered. 4. When blower gets up to speed and blower suction pressure reaches pressure switch set point, pressure switch contacts close sending 24 volts to pilot control from transformer secondary. 5. Pilot gas valve opens and spark initiates to light pilot burner. 6. When pilot flame is proven, spark drops out. 7. Main gas valve opens and pilot burner ignites main burners. 8. If boiler water temperature reaches high limit set point, high limit contacts open, cutting power to blower and pilot control. Burners extinguish and blower stops. Circulator pump continues to run as long as the thermostat continues to call for heat. When boiler water temperature drops past the high limit set point and through the differential, high limit contacts close, repeating steps 3-7. 9. If venting system becomes blocked, blower suction pressure will drop below pressure switch set point, opening pressure switch contacts and cutting power to pilot control. Burners will extinguish, but blower will remain powered as long as thermostat continues to call for heat. If venting system clears, steps 4-7 will repeat. 10. Thermostat is satisfied, ending call for heat. Relay coil is de-energized, opening contacts. Burners extinguish. Blower and circulator pump stop. 22