Download Siemens IC60 User manual
Transcript
Outputs 16.5 Assigning a time zone to an output Time Zones to Output P44E 1-8E 1-8E (O/P#) Value = time zone 1-8 Any of the 8 time zones can be assigned to outputs 1-8. If a time zone is assigned to an output it will turn the output on when the time zones starts and turn the output off when the time zones ends. You should un-map the output at P43E first before assigning the time zones to ensure that only the time zones will control the state of the output. 88 Building Technologies Fire Safety & Security Products