GP-4100 Series Hardware Manual Power Cord Specifications Power Cord Diameter Simple Wire: 0.75 to 1.5mm2 Stranded Wire: 0.75 to 1mm2 (18 - 16 AWG) Conductor Type Simple or Twisted Wire Conductor Length 5mm [0.2 in.] • Use copper conductors only. • If the Conductor’s end (individual) wires are not twisted correctly, the end wires may either short against each other, or against an electrode. Power Connector Specifications GP Rear + - + 24V - 0V FG FG FG Grounding Terminal connected to the GP • The power supply connector is MKDS 1/3-3,81 (made by Phoenix Contact). Connecting the Power Cord • To avoid an electric shock, prior to connecting the GP unit’s power cord terminals to the power terminal block, confirm that the GP unit's power supply is completely turned OFF, via a breaker, or similar unit. • The temperature rating of field installed Conductors:75°C only. 4-8 (1) Confirm that the GP unit’s Power Cord is unplugged from the power supply. (2) Use a flat-blade screwdriver (Size 0.4 x 2.5) to loosen the terminal screws. (3) Strip the power cord, and attach it to the power connector.