Download Mitsubishi Electric SLZ-KA25VAL Service manual

Transcript
OC320-1.qxp
05.2.24 8:52 AM
Page 1
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
No. OC320
TECHNICAL & SERVICE MANUAL
Indoor unit
[Model names]
[Service Ref.]
SLZ-KA25VA.TH
SLZ-KA35VA.TH
SLZ-KA50VA.TH
SLZ-KA25VAL.TH
SLZ-KA35VAL.TH
SLZ-KA50VAL.TH
SLZ-KA25VA
SLZ-KA35VA
SLZ-KA50VA
SLZ-KA25VAL
SLZ-KA35VAL
SLZ-KA50VAL
Note :
•This manual does not cover
outdoor units. When servicing
outdoor units, please refer
to the service manual
No.OC322 together with this
manual.
CONTENTS
Model name
indication
ON/OFF
TOO
WARM
TOO
COOL
FAN
SELECT
VANE
TIME
INDOOR UNIT
AUTO COOL
HEAT DRY
1.
2.
3.
4.
5.
6.
7.
8.
9.
TEMP.
ON/OFF
MODE
RESET
SLZ-KA25,35,50VAL.TH
SLZ-KA25,35,50VA.TH
REMOTE CONTROLLER
www.ilmalämpöpumput.com
PART NAMES AND FUNCTIONS ········2
SPECIFICATIONS ·································5
OUTLINES AND DIMENSIONS ············7
WIRING DIAGRAM ·····························10
REFRIGERANT SYSTEM DIAGRAM ·······11
TROUBLESHOOTING ························12
4-WAY AIR FLOW SYSTEM ···············19
DISASSEMBLY PROCEDURE ···········21
PARTS LIST ········································24
OC320-1.qxp
05.2.24 8:52 AM
Page 2
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
1
PART NAMES AND FUNCTIONS
Indoor Unit
SLZ-KA25VAL.TH SLZ-KA25VA.TH
SLZ-KA35VAL.TH SLZ-KA35VA.TH
SLZ-KA50VAL.TH SLZ-KA50VA.TH
Filter
Remove dust and pollutants
from inhaled air
Horizontal Air Outlet
Sets airflow horizontal automatically
during cooling or dehumidifying.
Grille
Auto Air Swing Vane
Disperses airflow up and
down and adjusts the angle
of airflow direction.
Air Intake
Inhales air from room.
Wireless remote controller
SLZ-KA25VAL.TH
SLZ-KA35VAL.TH
SLZ-KA50VAL.TH
SET TEMPERATURE
button
h
ON/OFF
TOO
WARM
TOO
COOL
FAN
SELECT
VANE
TIME
SET TEMPERATURE
button sets and any
desired room temperature.
ON / OFF button
Pushing button starts
operation. Pushing again
stops operation.
AUTO COOL
HEAT DRY
TIMER SELECT button
Used for selecting timed
starting or stopping.
MODE
MODE SELECT button
This button is used to change
between auto, cooling,
heating and drying operation
modes. (SLZ)
FAN SPEED button
RESET
This button is used to set
fan speed to low, medium
or high.
VANE CONTROL button
Used to change the airflow
direction.
Attention :
● Avoid operation of buttons with fingernails or other sharp objects. Sharp objects may scratch remote controller.
www.ilmalämpöpumput.com
2
OC320-1.qxp
05.2.24 8:52 AM
Page 3
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
Wired remote controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
SLZ-KA25VA.TH
SLZ-KA35VA.TH
SLZ-KA50VA.TH
● Operation buttons [ PAR-21MAA ]
Start/Stop button
Set Temperature buttons
Down
Fan Speed button
Up
Timer Menu button
(Monitor/Set button)
Filter
button
(<return sign> button)
Mode button (Return button)
TEMP.
ON/OFF
Set Time buttons
Service button (Clear button)
Back
Ahead
Test Run button
MENU
BACK
MONITOR/SET
ON/OFF
FILTER
DAY
CHECK TEST
Airflow Up/Down button
Timer On/Off button
(Set Day button)
PAR-21MAA
CLOCK
OPERATION
CLEAR
Louver button
(
Operation button)
To preceding operation
number.
Opening the
door.
Ventilation button
Operation button)
(
To next operation number.
www.ilmalämpöpumput.com
3
OC320-1.qxp
05.2.24 8:52 AM
Page 4
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
● Display
“Sensor” indication
Displayed when the remote controller
sensor is used.
Day-of-Week
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
Shows the current day of the week.
Time/Timer Display
“Locked” indicator
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, shows the time
remaining.
Indicates that remote controller buttons have been locked.
Identifies the current operation
“Clean The Filter” indicator
Shows the operating mode, etc.
* Multilanguage display is supported.
Comes on when it is time to clean the
filter.
TIME SUN MON TUE WED THU FRI SAT
TIMER
Hr
ON
AFTER
FUNCTION
FILTER
˚F˚C
“Centrally Controlled” indicator
Indicates that operation of the remote controller has been prohibited by a master controller.
Timer indicators
AFTER OFF
ERROR CODE
˚F˚C
The indicator comes on if the corresponding timer is set.
WEEKLY
SIMPLE
AUTO OFF
ONLY1Hr.
Fan Speed indicator
Shows the selected fan speed.
“Timer Is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Up/Down Air Direction indicator
Room Temperature display
Shows the room temperature.
The indicator
shows the direction of the outcoming airflow.
Louver display
“One Hour Only” indicator
Indicates the action of the swing
louver. Does not appear if the
louver is stationary.
Displayed if the airflow is set to
weak and downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off after one
hour, at which time the airflow direction also changes.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
(Power On indicator)
Indicates that the power is on.
Caution
● Only the Power display lights when the unit is stopped and power supplied to the unit.
● When power is turned ON for the first time the (Centrally controlled) display appears to go off momentarily but this is not a
malfunction.
● “NOT AVAILABLE” is displayed when the Air speed button are pressed.This indicates that this room unit is not equipped
with the fan direction adjustment function and the louver function.
● When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.
www.ilmalämpöpumput.com
4
05.2.24 8:52 AM
Page 5
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
2
SPECIFICATIONS
SLZ-KA35VAL.TH
SLZ-KA50VAL.TH
SLZ-KA25VAL.TH
SLZ-KA35VA.TH
SLZ-KA50VA.TH
SLZ-KA25VA.TH
Function
Cooling
Cooling
Heating
Cooling
Heating
Heating
Single phase
Single phase
Single phase
Power supply
230V, 50Hz
230V, 50Hz
230V, 50Hz
Capacity Air flow (High/Medium/Low) K /h
660/540/480
600/540/480
660/540/480
Power outlet
A
20
10
10
Running current ✽1
A
0.65
0.35
0.40
Power input Rated frequency
W
85
75
85
Dew prevention heater
(kW)
0.014
0.014
0.014
Power factor ✽1
94
%
97
97
90
93
94
Fan motor current ✽1
A
0.27
0.19
0.26
Model
PK6V20-LM
PK6V15-LD
PK6V20-LL
WHT-BLK : 407 BLK-BLU : 86 WHT-BLK : 393 BLK-BLU : 164 WHT-BLK : 325 BLK-BLU : 143
Winding
"
BLU-YLW : 47
BLU-YLW : 30
BLU-YLW : 47
resistance (at20:)
BRN-RED : 309
BRN-RED : 165
BRN-RED : 319
Width
mm(in)
UNIT : 570(22-7/16)
PANEL : 650(25-9/16)
Height
mm(in)
Dimensions
UNIT : 208(8-3/16)
PANEL : 20(13/16)
Depth
mm(in)
UNIT : 570(22-7/16)
PANEL : 650(25-9/16)
Weight
kg
UNIT : 16.5
PANEL : 3
Air direction
4
4
4
Sound level(High/Medium/Low) dB(A)
39/34/30
37/31/28
38/33/29
Fan speed(High/Medium/Low)
rpm
710/590/530
650/530/480
690/570/510
Fan speed regulator
3
3
3
Thermistor TH1(at25:)
k"
10
10
10
Thermistor TH2(at25:)
k"
10
10
10
Thermistor TH5(at25:)
k"
10
10
10
Fan
motor
Electrical
data
Indoor model
Special
remarks
OC320-1.qxp
NOTE : Test conditions are based on ISO 5151
Cooling : Indoor D.B. 27: W.B. 19:
Outdoor D.B. 35: W.B. 24:
Heating : Indoor D.B. 20: W.B. 15:
Outdoor D.B. 7: W.B. 6:
Refrigerant piping length (one way): 5m
✽1 Measured under rated operating frequency.
Specifications and rating conditions of main electric parts
INDOOR UNIT
Item
Model
SLZ-KA25VA.TH
Indoor fan capacitor
Fuse
SLZ-KA25VAL.TH SLZ-KA35VAL.TH SLZ-KA50VAL.TH
(C1)
SLZ-KA35VA.TH
SLZ-KA50VA.TH
1.5+ 440V
(FUSE)
250V 6.3A
Vane motor
(MV)
MSBPC20 12V 250"
Terminal block
(TB)
TO OUTDOOR UNIT : 3P TO WIRED REMOTE CONTROLLER : 2P (SLZ-KA25/35/50VA.TH)
Indoor fan motor thermal fuse
Cord Heater
145:i2:
(H2)
240V AC 15W
www.ilmalämpöpumput.com
5
OC320-1.qxp
05.2.24 8:52 AM
Page 6
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
NOISE CRITERION CURVES
<50Hz>
<50Hz>
SLZ-KA25VAL.TH
SLZ-KA25VA.TH
NOTCH SPL(dB)
High
37
Medium
31
Low
28
LINE
SLZ-KA35VAL.TH
SLZ-KA35VA.TH
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
20
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
NOTCH SPL(dB)
High
38
Medium
33
Low
29
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
10
63
125
250
500
1000
2000
4000
63
8000
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
<50Hz>
SLZ-KA50VAL.TH
SLZ-KA50VA.TH
NOTCH SPL(dB)
High
39
Medium
34
Low
30
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
UNIT
80
CEILING
70
NC-70
60
NC-60
1.5m
50
NC-50
40
NC-40
MICROPHONE
30
NC-30
20
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than displayed level under actual installation condition by surrounding echoes. The sound level
can be higher by about 2 dB than the displayed level during cooling and heating operation.
www.ilmalämpöpumput.com
6
{ 100
118
{ 73.4
Cut out hole
Emergency operation switch(heating)
15~37
576~620 Ceiling hole
Refrigerent pipe (liquid)
Emergency operation switch(cooling)
Receiver
420
Suspension bolt pitch
Refrigerent pipe (gas)
17
202
230
35 55
V/M
V/M
377
Air intake hole
Grille
Terminal block
(Case of Wired remote controller)Terminal block
650
301
Air outlet hole
15~37
199
352
335
576~620 Ceiling hole
570
530
Suspension bolt
pitch
V/M
V/M
Ceiling surface
15~37
Brand label
Vane motor
Air intake grille
Auto vane
Drain hole
Grille
SLZ-KA50VA(L)
{ 12.7mm
flared connection
1/2F
{ 9.52mm
flared connection
3/8F
{ 6.35mm
SLZ-KA35VA(L) flared connection
1/4F
{ 6.35mm
flared connection
1/4F
{ 9.52mm
flared connection
3/8F
{ 6.35mm
flared connection
1/4F
SLZ-KA25VA(L)
Refrigerent pipe
(gas)
Models
Refrigerent pipe
(liquid)
Wiring entry
Suspension bolt
M10 or 3/8
(procure locally)
Drain pipe
VP-25 connection
(O.D. { 32)
SLZ-KA25VAL.TH
SLZ-KA35VAL.TH
SLZ-KA50VAL.TH
SLZ-KA25VA.TH
SLZ-KA35VA.TH
SLZ-KA50VA.TH
DEFROST/STAND BY lamp
Operation lamp
(WIRELESS PANEL)
Ceiling surface
25
0°
3- { 2.8 hole
Burring hole
66
121
Detail drawing of fresh air intake
12
Fresh air
intake
193
15~37
93
335
31
208
570
87
235
57
56
38~58
55 35 Suspension bolt
lower edge
650
www.ilmalämpöpumput.com
301
Air outlet hole
7
20
0°
+5
27 0
12
377
Air intake hole
3
182
05.2.24 8:52 AM
48
OC320-1.qxp
Page 7
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
OUTLINES AND DIMENSIONS
Unit : mm
OC320-1.qxp
05.2.24 8:52 AM
Page 8
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
Unit : mm
WIRELESS REMOTE CONTROLLER
57
17.5
h
140
ON/OFF
TOO
WARM
TOO
COOL
FAN
SELECT
VANE
TIME
AUTO COOL
HEAT DRY
MODE
RESET
D
B
A
C
Installation area
• Area in which the remote controller is not exposed direct sunshine.
• Area in which there is no nearby heating source.
• Area in which the remote controller is not exposed to cold (or hot) winds.
• Area in which the remote controller can be operated easily
• Area in which the remote controller is beyond the reach of children.
Installation method
1 Attach the remote controller holder to the desired location using two tapping screws.
2 Place the lower end of the controller into the holder.
A Wireless remote controller (Accessory)
B Wall
C Remote controller holder (Accessory)
D Fixing screw (Accessory)
• The signal can travel up to approximately 7 meters (in a straight line) within 45
degrees to both right and left of the center line of the receiver.
In addition, the signal may not be received if there is interference of light of fluorescent
lights or strong sunlight.
www.ilmalämpöpumput.com
8
05.2.24 8:52 AM
Page 9
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
Unit : mm
WIRED REMOTE CONTROLLER
130
120
OC320-1.qxp
19
www.ilmalämpöpumput.com
9
OC320-1.qxp
05.2.24 8:52 AM
Page 10
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
4
WIRING DIAGRAM
SLZ-KA25VAL.TH SLZ-KA25VA.TH
SLZ-KA35VAL.TH SLZ-KA35VA.TH
SLZ-KA50VAL.TH SLZ-KA50VA.TH
GRILLE
TB4
S1
S2
MV
BLU
1
5
TO OUTDOOR UNIT
S3
WHT
2
MV
YLW
3
DP
P.B
2 3
ORN
W.B
9
GRY
7
PINK
8
5
7
1
1
X1
RED
3 (POWER
1
BOARD)
CNDK
FUSE
ORN
3 (POWER)
CND
1
BLU
ORN
BLU
RED
WHT
RED
YLW
BLU
3 (D·U·M)
CNP
I.B
TRANS
3
BLU
(CONTROL)
CN3C
DC13.1V
1 2 CN2S(WHT)
X6 X5 X4
ZNR
X7
9
LED2
VLT
6
BZ
3
RED
3 (D·HEATER) 1
CNC
5
BLU
CNB
1
1 2 3 AC220-240V
CNSK(RED)
4
YLW
WHT
9 (FAN)
FAN
3
YLW
YLW
RED
1
RED
YLW
9
C1
BRN
BLU
H2
1
ORN
WHT
YLW
BLK
YLW
YLW
5
MV
MF
5 10 8
RED
7 4
5
6
ORN
5
BRN
5
MV
SKY BLU
X6 X5 X4
LED1
X7
SW1
SW2
<fig:w1>
LED1
CN2L
ON
OFF
GRN
(VANE)
CN6V
CN41
1
2
3
4
5
RED
CN51
BLU
CN32
WHT
12345
YLW
ORN
RU
WHT
LED3
12345
SW2
BLK
WHT
(POWER 1
BOARD)
2
CN2D
X1
SW3
SWE
ON
ON
OFF
OFF
CN90
(WIRELESS)
WHT
6
1
2
REMOTE
CONTROLLER
3
4
5
6
WHT
(DRAIN)
CN31
7
8
9
1
2
BLK
RED
(2 PHASE) (INTAKE)
CN20
CN29
1
2
1
2
3
MODELS
LED2
KA25
SW2
ON
OFF
1 2 3 4 5
WHT
(LIQUID)
CN21
1
2
BLU
(REMOCON)
CN22
1
KA35
ON
OFF
KA50
ON
OFF
1 2 3 4 5
2
BLU
BLU
VLT
GRY
PINK
BLU
RED
5
SKYBLU
See fig:w1
YLW
W.R
ORN
BRN
1 2 3 4 5
* Case of wired model
9
TB15
1
2
DS
TH5
TH1
TH2
* Case of wireress model
[LEGEND]
SYMBOL
P.B
NAME
INDOOR POWER BOARD
SYMBOL
NAME
WIRELESS REMOTE CONTROLLER BOARD
W.B
INDOOR CONTROLLER BOARD
RU
RECEIVING UNIT
CN2L
CONNECTOR(LOSSNAY)
BZ
BUZZER
CN32
CONNECTOR(REMOTE SWITCH)
LED1
LED(RUN INDICATOR)
CN41
CONNECTOR(HA TERMINAL-A)
LED2
LED(HOT ADJUST)
CN51
CENTRALLY CONTROL
SW1
SWITCH(HEATING ON/OFF)
FUSE
FUSE(T6.3AL250V)
SW2
SWITCH(COOLING ON/OFF)
LED1
POWER SUPPLY(I.B)
C1
CAPACITOR(FAN MOTOR)
LED2
POWER SUPPLY(I.B)
DP
DRAIN-UP MACHINE
LED3
TRANSMISSION(INDOOR-OUTDOOR)
DS
DRAIN SENSOR
SW2
SWITCH(CAPACITY CODE)
H2
DEW PREVENTION HEATER
SW3
SWITCH(MODE SELECTION)
MF
FAN MOTOR
SWE
SWITCH(EMERGENCY OPERATION)
MV
X1
DRAIN PUMP/DEW PREVENTION HEATER
X4
RELAY(FAN MOTOR LL)
X5
RELAY(FAN MOTOR Lo)
X6
RELAY(FAN MOTOR Hi)
X7
RELAY(FAN MOTOR Me)
ZNR
VARISTOR
I.B
TB4
VANE MOTOR
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TB15
TRANSMISSION LINE)
ROOM TEMP.THERMISTOR
TH1
(0°C/15kΩ,25°C/5.4kΩ DETECT)
PIPE TEMP.THERMISTOR/LIQUID
TH2
(0°C/15kΩ,25°C/5.4kΩ DETECT)
COND./EVA.TEMP.THERMISTOR
TH5
(0°C/15kΩ,25°C/5.4kΩ DETECT)
NOTES: 1.Since the outdoor side electric wiring may change be sure to
check the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with polarities,make
wiring matching terminal numbers(S1,S2,S3).
:Connector, :Terminal (block).
3.Symbols used in wiring diagram above are,
w For details on how to operate self-diagnosis
refer to the technical manuals etc.
www.ilmalämpöpumput.com
10
TO MA-REMOTE
} CONTROLLER
DC8.7-13V
OC320-1.qxp
05.2.24 8:52 AM
Page 11
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
5
REFRIGERANT SYSTEM DIAGRAM
SLZ-KA25VAL.TH SLZ-KA25VA.TH
SLZ-KA35VAL.TH SLZ-KA35VA.TH
SLZ-KA50VAL.TH SLZ-KA50VA.TH
Strainer
#50
Heat exchanger
Refrigerant GAS pipe connection
(Flare)
Condenser/evaporator
temperature thermistor
(TH5)
Refrigerant flow in cooling
Refrigerant flow in heating
Refrigerant LIQUID pipe connection
(Flare)
Pipe temperature
thermistor/liquid
(TH2)
Room temperature
thermistor (TH1)
Distributor
with strainer
#50
Strainer
#50
www.ilmalämpöpumput.com
11
OC320-1.qxp
05.2.24 8:52 AM
Page 12
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
6
TROUBLESHOOTING
6-1. Cautions on troubleshooting
(1) Before troubleshooting, check the followings:
1Check the power supply voltage.
2Check the indoor/outdoor connecting wire for mis-wiring.
(2) Take care the followings during servicing.
1 Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then turn
off the breaker.
2 When removing the indoor controller board, hold the edge of the board with care NOT to apply stress on the
components.
3 When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
6-2. Self-check
6-2-1. Wired remote controller
B
E D
˚C
˚C
SIMPLE
TEMP.
C
MENU
BACK
ON/OFF
FILTER
DAY
MONITOR/SET
PAR-21MAA
ON/OFF
CLOCK
CHECK TEST
OPERATION
CLEAR
A
A
B
C
D
CHECK button
Refrigerant address
TEMP. button
IC:Indoor unit
OC:Outdoor unit
E Check code
1
2
3
4
Turn on the power.
Press the [CHECK] button twice.
Set refrigerant address with [TEMP] button if system control is used.
Press the [ON/OFF] button to stop the self-check.
6-2-2. Wireless remote controller
TO O
TO O
CO OL
CT
FAN
AUTO
COOL
HEAT
DRY
VANE
SELE
TIME
RES
ET
OPERATION INDICATOR lamp
h
ON/OFF
TOO
WARM
TOO
COOL
The following indication
applies regardless of shape
.
of the indicator
1 Turn ON the power.
2 During pressing both the MODE SELECT button and TOO COOL button on the
remote controller at the same time, press the RESET button.
3 At first, release the RESET button.
4 And release the other two buttons since all LCD in operation display section of the
remote controller is displayed after 3 seconds.
5 Transmit the signal of remote controller, pressing OPERATE/STOP (ON/OFF)
button on the remote controller
.
(The above procedure allows OPERATION INDICATOR lamp to indicate the failure-mode.)
6 Transmit the signal of remote controller, pressing OPERATE/STOP (ON/OFF)
button to stop the self-check.
www.ilmalämpöpumput.com
12
OC320-1.qxp
05.2.24 8:52 AM
Page 13
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
• Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds
OPERATION
INDICATOR
lamp flash
pattern
Beep
Beep Beep Beep
Off
Beep
1st
2 nd
3 rd
nth
On
On
On
On
Beep Beep
1st
Off
On
2 nd · · · Repeated
On
0.5 sec. Approx. 2.5 sec. 0.5 sec. 0.5 sec.
Self-check Approx. 2.5 sec. 0.5 sec. 0.5 sec. 0.5 sec.
starts
(Start signal
Number of flashes/beeps in pattern indicates the check Number of flashes/beeps in pattern indicates
received)
code in the following table (i.e., n=5 for “P5”)
the check code in the following table
[Output pattern B]
Beeper sounds
OPERATION
INDICATOR
lamp flash
pattern
Beep
Beep Beep Beep
1st
Off
On
Approx. 3 sec.
Self-check Approx. 2.5 sec.
starts
(Start signal
received)
2nd
3 rd
On
On
On
0.5 sec. 0.5 sec. 0.5 sec.
Beep
Beep
nth
1st
On
Off
0.5 sec. Approx. 2.5 sec.
Number of flashes/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
On
Approx. 3 sec.
Beep
2 nd · · · Repeated
On
On
0.5 sec. 0.5 sec.
Number of flashes/beeps in pattern indicates
the check code in the following table
[Output pattern A] Errors detected by indoor unit
Wireless remote controller Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes 1 Check code
(Number of times)
1
P1
P2
2
P9
3
E6,E7
4
P4
5
P5
6
P6
7
EE
8
P8
9
E4, E5
–
10
–
11
12
Fb
E0, E3
–
–
E1, E2
Symptom
Remark
Intake sensor error
Pipe (TH2) sensor error
Pipe (TH5) sensor error
Indoor/outdoor unit communication error
Drain sensor error
Drain pump error
Freeing/Overheating safeguard operation
Communication error between indoor and outdoor units
Pipe temperature error
Remote controller signal receiving error
–
–
Indoor unit control system error (memory error, etc.)
Remote controller transmission error
Remote controller control board error
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wireless remote controller Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes 1 Check code
(Number of times)
1
E9
2
3
4
UP
U3,U4
UF
5
U2
6
U1,Ud
7
8
9
10
U5
U8
U6
U7
11
U9,UH
Symptom
Indoor/outdoor unit communication error
(Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49C worked/
insufficient refrigerant
Abnormal high pressure (63H worked)/Overheating
safeguard operation
Abnormal temperature of heat sink
Outdoor unit fan safeguard stop
Compressor overcurrent interruption/Abnormal of power module
Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
–
–
Other errors (Refer to the technical manual for the outdoor unit.)
Remark
For details, check
the LED display
of the outdoor
controller board.
As for outdoor
unit, refer to
service manual
OC322.
–
12
–
13
Others
14
*1 If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and
the OPERATION INDICATOR lamp does not come on, there are no error records.
*2 If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
To be continued on the next page.
www.ilmalämpöpumput.com
13
OC320-1.qxp
05.2.24 8:52 AM
Page 14
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
• On wireless remote controller
2The continuous buzzer sounds from receiving section of indoor unit.
3Blink of operation lamp
• On wired remote controller
1Check code displayed in the LCD.
• If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
Symptom
Cause
Wired remote controller
LED 1, 2 (PCB in outdoor unit)
For about 2
After LED 1, 2 are lighted, LED 2 is •For about 2 minutes following power-on,opPLEASE WAIT
minutes follow- turned off, then only LED 1 is
eration of the remote controller is not possible
lighted. (Correct operation)
ing power-on
due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection
Only LED 1 is lighted. →
device is not con-nected.
PLEASE WAIT → Error code
LED 1, 2 blink. •Reverse or open phase wiring for the outdoor
After about 2
unit’s power terminal block (L1, L2, L3)
minutes has
expired followDisplay messages do not
•Incorrect wiring between indoor and outdoor
ing power-on Only LED 1 is lighted. →
appear even when operation
LED 1 blinks twice, units (incorrect polarity of S1, S2, S3)
switch is turned ON (operation
LED 2 blinks once. •Remote controller wire short
lamp does not light up).
On the wireless remote controller with condition above, following phenomena takes place.
• No signals from the remote controller are accepted.
• OPE lamp is blinking.
• The buzzer makes a short piping sound.
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer)
LED2 (power for remote controller)
Indicates whether control power is supplied. Make sure that this LED is
always lit.
Indicates whether power is supplied to the remote controller.
This LED lights only in the case of the indoor unit which is connected to the
outdoor unit refrigerant address “0”.
LED3 (communication between indoor and
outdoor units)
Indicates state of communication between the indoor and outdoor units.
Make sure that this LED is always blinking.
www.ilmalämpöpumput.com
14
OC320-1.qxp
05.2.24 8:52 AM
Page 15
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
6-3. Test point diagram
6-3-1. Indoor power board
SLZ-KA25VAL.TH SLZ-KA25VA.TH
SLZ-KA35VAL.TH SLZ-KA35VA.TH
SLZ-KA50VAL.TH SLZ-KA50VA.TH
CN2S
Connect to the indoor controller board (CN2D)
1 (+))
Between 1 to 3 12.6-13.7V DC (Pin1
CNSK
Connect to the indoor controller board
(CNDK)
Between 1 to 3 220-240V AC
www.ilmalämpöpumput.com
15
OC320-1.qxp
05.2.24 8:52 AM
Page 16
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
6-3-2. Indoor controller board
SLZ-KA25VAL.TH SLZ-KA25VA.TH
SLZ-KA35VAL.TH SLZ-KA35VA.TH
SLZ-KA50VAL.TH SLZ-KA50VA.TH
+
LED3
Transmission
(Indoor/outdoor)
–
CN22
Remote controller
connecting wire
– (10.4~14.6V DC)
CN20
Room temperature
thermistor (TH1)
CN21
Pipe temperature
thermistor/Liquid
(TH2)
CN29
Condenser/evaporator
temperature thermistor
(TH5)
CN31
Drain sensor (DS)
+
CN3C
Transmission
(Indoor/outdoor)
(0~24V DC)
LED1
Power supply LED2
Power supply
(I.B)
(R.B)
}
CN2D
Connector to the indoor
power board (CN2S)
(12.5~13.7V DC)
Non polarity
CND
Power
supply input
(220~240V AC)
FUSE
(6.3A 250V)
CNDK
Connect to the indoor
power board (CNSK)
(220~240V AC)
}
CN90
Connect to the
wireless remote
controller board
(CNB)
CNC
Dew prevention
heater (H2)
(220~240V AC)
CN41
Connector
(HA terminal-A)
CNP
Drain-pump output
(DP)
(220~240V AC)
CN6V
Vane motor output
(MV)
CN51
Centrally control
CN2L
Connector
(LOSSNAY)
FAN
Fan motor output
Jumper connector
J11~J15
Unit setting
SW3
SWE
Mode selection Emergency operation
www.ilmalämpöpumput.com
16
SW2
Capacity setting
OC320-1.qxp
05.2.24 8:52 AM
Page 17
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
6-4. Trouble criterion of main parts
SLZ-KA25VAL.TH SLZ-KA25VA.TH
SLZ-KA35VAL.TH SLZ-KA35VA.TH
SLZ-KA50VAL.TH SLZ-KA50VA.TH
Part name
Check method and criterion
Room temperature
thermistor
(TH1)
Measure the resistance with a tester.
(Part temperature 10°C ~ 30°C)
Pipe temperature
thermistor/liquid
(TH2)
Condenser/evaporator
temperature thermistor
(TH5)
Normal
Abnormal
4.3kΩ~9.6k"
Opened or short-circuited
Measure the resistance between the terminals with a tester.
(Coil wiring temperature 10°C ~ 30°C)
Indoor fan motor
(MF)
Normal
KA35VA(L)
KA50VA(L)
WHT-BLK
386~428"
373~413"
308~341"
BLK-BLU
81~91"
155~172"
135~151"
Opened or
BLU-YLW
28~32"
44~49"
44~49"
short-circuited
BRN-RED
157~174"
302~335"
293~324"
P
BLK BLU YLW BRN RED ORN
WHT
Abnormal
KA25VA(L)
P : Thermal fuse 145 ± 2˚C
Vane motor (MV)
White 4
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:~30:)
Connector
M
Normal
Abnormal
300"
Open or short
Red — Yellow
Orange 2
Red — Blue
Red 1
5
3
Blue
Yellow
Drain pump (DP)
Red — Orange
Red — White
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:~30:)
Yellow
1
Normal
Abnormal
2
290"
Open or short
Yellow
Drain sensor (DS)
1
2
3
Measure the resistance between the terminals using a tester.
Measure the resistance after 3 minutes have passed since the power supply was intercepted.
(Surrounding temperature 0:~60:)
Normal
Abnormal
0.6k"~6.0k"
Open or short
www.ilmalämpöpumput.com
17
(Refer to the thermistor)
OC320-1.qxp
05.2.24 8:52 AM
Page 18
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
<Thermistor Characteristic graph>
Thermistor for
lower temperature
•Room temperature thermistor (TH1)
•Pipe temperature thermistor/liquid (TH2)
•Condenser/evaporator temperature
thermistor (TH5)
< Thermistor for lower temperature >
50
40
Rt=15exp { 3480( 1
273+t
0:
15k'
10:
9.6k'
20:
6.3k'
25:
5.2k'
30:
4.3k'
40:
3.0k'
Resistance (k")
Thermistor R0=15k' ± 3%
Fixed number of B=3480 ± 2%
1 )}
273
30
20
10
0
Thermistor for
drain sensor
10
< Thermistor for drain sensor >
9
Thermistor R0=6.0k' ±5%
Fixed number of B=3390 ± 2%
8
1 )}
273
7
Resistance (k")
Rt=6exp { 3390( 1
273+t
0:
6.0k'
10:
3.9k'
20:
2.6k'
25:
2.2k'
30:
1.8k'
40:
1.3k'
60:
0.6k'
-20 -10 0 10 20 30 40 50
Temperature (:)
6
5
4
3
2
1
0
www.ilmalämpöpumput.com
18
-20
0
20 40 60
Temperature (:)
80
05.2.24 8:52 AM
Page 19
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
7
4-WAY AIR FLOW SYSTEM
7-1. Fresh air intake (Location for installation)
At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when required.
Fresh air intake
Detail drawing of fresh air intake
25
[100
[73.4
Cut out hole
3-[2.8 hole
Burring hole
0°
12
12
0°
118
Ceiling surface
Refrigerant pipe
Electrical Box
Drain pipe
7-2. Fresh air intake amount & static pressure characteristics
SLZ-KA25VAL.TH SLZ-KA25VA.TH
SLZ-KA35VAL.TH SLZ-KA35VA.TH
SLZ-KA50VAL.TH SLZ-KA50VA.TH
Taking air into the unit
Duct characteristics
at site
0
A
2.5
Curve in the
left praphs.
1
C
2.0
Air flow : Q [m3/min]
3.0 3.5
B
Static pressure : P [Pa]
50
0.5 1.0 1.5
0
How to read curves
Q
-50
-100
C
A
2
E
-150
-200
Q
-250
3
D
-300
NOTE: Fresh air intake amount should be 20% or less of
whole air amount to prevent dew dripping.
Q…Planned amount of fresh air intake
<m3/min>
A…Static pressure loss of fresh air
intake duct system with air flow
<Pa>
amount Q
…
B Forced static pressure at air conditioner inlet with air flow amount Q
<Pa>
C…Static pressure of booster fan with
<Pa>
air flow amount Q
D…Static pressure loss increase
amount of fresh air intake dust system for air flow amount Q <Pa>
E…Static pressure of indoor unit with air
<Pa>
flow amount Q
Qa…Estimated amount of fresh air
intake with out D
<m3/min>
A
OC320-1.qxp
Q
Qa
7-3. Interlocking operation method with duct fan (Booster fan)
●Whenever the indoor unit is operating,
the duct fun
operates.
(1)Connect the optional multiple remote
controller adapter(PAC-SA88HAE)to the connector CN51 on the
indoor controller board.
(2)Drive the relay after connecting the
12V DC relay between the Yellow
and Orange connector lines.
Use a relay under 1W.
MB: Electromagnetic switch power
relay for duct fan.
X: Auxiliary relay (12V DC LY-1F)
Be sure to secure insulation
material by tape and such
CN51
on
indoor unit
board
5
~
Green
Yellow
1
Connector (5P)
Orange
MB
Red
Brown
Package side
Multiplr remote
controller adapter
PAC-SA88HA-E
Installation at site
Be sure to secure insulation
material by tape and such
Indoor controller board
Multiple remote
controller adapter
PAC-SA88HA-E
Distance between indoor
controller board and relay
must be within 10m.
CN51(WHT)
CN51
www.ilmalämpöpumput.com
19
OC320-1.qxp
05.2.24 8:52 AM
Page 20
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
7-4. Fixing of horizontal vane
Horizontal vane of each air outlet can be fixed according to the environment, which is installed.
Setting procedure
1) Turn off a main power supply (Turn off a breaker).
2) Disconnect the vane motor connector of the direction of the arrow with pressing the unlocking button as shown in figure
below.
Electricity insulate the disconnected connector with the vinyl tape.
Vane motor
Vane motor
Connector
Unlocking button
Horizontal vane
3) Set a vertical vane of the air outlet, which tries to fixed by the hand slowly within the range in the table below.
Measured standard
position of the grille
Horizontal vane
<Set range>
Standard of
horizontal position
Level 30°
(Min.)
Downward 45°
Downward 55°
Downward 70°
(Max.)
Dimension A (mm)
21
25
28
30
w Dimension between 21 mm and 30 mm can be arbitrarily set.
Caution
.
Do not set the dimension out of the range.
Erroneous setting could cause dew drips, smudge on ceiling or malfunction of unit.
www.ilmalämpöpumput.com
20
OC320-1.qxp
05.2.24 8:52 AM
Page 21
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
8
DISASSEMBLY PROCEDURE
SLZ-KA25VAL.TH SLZ-KA35VAL.TH SLZ-KA50VAL.TH
OPERATING PROCEDURE
Be careful on removing heavy parts.
PHOTOS&ILLUSTRATIONS
1. Removing the air intake grille
(1) Slide the knob of air intake grille to the direction of the
arrow 1 to open the air intake grille.
(2) Remove the hook for secure belt on air inlet grille from the
panel.
(3) Slide the shaft in the hinge to the direction of the arrow 2
and remove the air intake grille.
Figure 1
Air intake grille
Grille
Air intake grille knob
2. Removing the fan guard
(1) Open the air intake grille.
(2) Remove the 3 screws of fan guard.
Photo 1
Fan guard
Screws
Air intake grille
3. Removing the panel
(1) Remove the air intake grille. (Refer to 1)
Corner panel (See figure 2)
(1) Remove the screw of the corner.
(2) Slide the corner panel to the direction of the arrow 3, and
remove the corner panel.
Panel (See photo 2)
(1) Disconnect the connector that connects with the unit.
(2) Remove the 2 screws from the panel and loose another 2
screws, which fixed to the oval hole, have different diameter.
(3) Rotate the panel a little to remove the screws.(Slide the
panel so that the screw comes to a large diameter of the
oval hole, which has two different diameters.)
4. Removing the electrical parts
(1) Remove the 2 screws and the control box cover.
<Electrical parts in the control box>
• Indoor controller board (I.B)
• Terminal block (TB4)
• Indoor power board (P.B)
Figure 2
Corner
Screw panel
Panel
Corner
panel
Photo 2
Screws
Connectors
Screws
Panel
Photo 3
Indoor power board
(P.B)
Indoor controller board
(I.B)
www.ilmalämpöpumput.com
21
Terminal block
(TB4)
OC320-1.qxp
05.2.24 8:52 AM
Page 22
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
OPERATING PROCEDURE
PHOTOS&ILLUSTRATIONS
5. Remove the room temperature thermistor (TH1)
(1) Remove the panel. (Refer to 3)
(2) Pull out the room temperature thermistor from the drain
pan.
(3) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(4) Remove the connector (CN20) from the indoor controller
board, and disconnect the room temperature thermistor.
Photo 4
Connectors
Drain plug
Control box
Screw
Screw
Room
temperature
thermistor
(TH1)
6. Remove the drain pan
(1) Remove the panel. (Refer to 3)
(2) Remove the room temperature thermistor and the 2 lead
wires held with fastener; wireless controller board relay
connector (9P red) and panel relay connector (10P white).
(3) Remove the 4 screws fixed to the drain pan, and remove
the drain pan.
(4) Remove the fan guard. (Refer to 2)
7. Removing the pipe temperature thermistor/liquid (TH2)
and condenser/evaporator temperature thermistor (TH5)
(1) Remove the panel. (Refer to 3)
(2) Remove the drain pan. (Refer to 6)
(3) Disconnect the indoor coil thermistor from the holder.
(4) Remove the 3 screws fixed to the piping cover, and
remove the piping cover. (See photo 9)
(5) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
Drain pan
Screw
Screw
Fan guard
Control box
Photo 5
Pipe temperature thermistor/liquid (TH2)
(6) Remove the connector (CN21) from the indoor controller
board, and disconnect the pipe temperature thermistor/liquid.
Condenser/evaporator temperature thermistor (TH5)
(6) Remove the connector (CN29) from the indoor controller
board, and disconnect the condenser/evaporator temperature
thermistor.
Pipe temperature
thermistor/liquid
(TH2)
8. Remove the fan motor (MF)
(1) Remove the panel. (Refer to 3)
(2) Remove the drain pan. (Refer to 6)
(3) Remove the nut and the washer from the turbo fan, and
remove the turbo fan.
(4) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(5) Disconnect the connectors of the (fan 1) and the (fan 2)
from the indoor controller board.
(6) Remove the 3 screws fixed to the piping cover, and
remove the piping cover. (See photo 9)
(7) Remove the 6 screws fixed to the flat plate, and remove
the flat plate.
(8) Disconnect the lead wires to the direction of the fan motor,
and remove the 3 nuts of the fan motor.
Photo 6
Flat plate
Screws
Screw
Nut
Fan motor
(MF)
Nut
Lead
wires
www.ilmalämpöpumput.com
22
Condenser/evaporator
temperature thermistor
(TH5)
Screws
Screw
Nut
OC320-1.qxp
05.2.24 8:52 AM
Page 23
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
OPERATING PROCEDURE
PHOTOS&ILLUSTRATIONS
9. Removing the drain pump (DP) and drain sensor (DS)
(1) Remove the panel. (Refer to 3 )
(2) Remove the drain pan. (Refer to 6)
(3) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(4) Remove the connectors of the (CNP) and the (CN31)
from the indoor controller board.
(5) Remove the 1 screw fixed to the cover, and remove the
cover.
(6) Disconnect the lead wires to the direction of the drain
pump.(See photo 7)
(7) Remove the 3 screws of the drain pump.
(8) Cut the drain hose band, pull out the drain hose from the
drain pump.
(9) Pull out the drain pump.
(10) Remove the drain sensor and the holder.
Photo 7
Cover
Screw
Control
box
Lead wires
Photo 8
Drain sensor (DS)
Drain pump (DP)
Drain
hose
Screws
Screw
Fixing band
10. Removing the heat exchanger
(1) Remove the panel. (Refer to 3 )
(2) Remove the drain pan. (Refer to 6)
(3) Remove the nut and the washer from the turbo fan, and
remove the turbo fan.
(4) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(5) Disconnect the connector of the (fan) from the indoor controller board.
(6) Remove the 3 screws fixed to the piping cover, and
remove the piping cover. (See photo 9)
(7) Remove the pipe temperature thermistor/liquid and
condenser/evaporator temperature thermistor. (Refer to 7)
(8) Disconnect the lead wires to the direction of the fan motor.
(9) Remove the 1 coil support screw, the 2 inside coil screws
(See photo 10), and the 4 outside coil screws (See photo 9)
from the heat exchanger, and remove the heat exchanger.
Control box
Photo 9
Screws of
piping cover
Coil
screws
Coil
screws
Piping cover
Lead wires
Control box
Photo 10
Coil screws
Coil
support
Coil
support
Screw
Heat exchanger
www.ilmalämpöpumput.com
23
OC320-1.qxp
05.2.24 8:52 AM
Page 24
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
9
PARTS LIST
PANEL PARTS
SLP-2AL
SLP-2AA
10
9
8
3
2
7
1
4
5
6
Price
Wiring RecomRemarks
(Drawing No.) Diagram mended Unit Amount
SLP-2AL SLP-2AA
Symbol
Q'ty
Q'ty/set
No.
1
Parts No.
Parts name
E07 103 003 AIR OUTLET GRILLE
Specification
1
1
E07 158 003 AIR OUTLET GRILLE
W.B
2 E07 103 317 WIRELSS REMOTE CONTROL BOARD
1
3 E07 103 037 AUTO VANE
4
4
4 E07 103 975 CORNER PANEL
4
4
5 E07 103 100 AIR FILTER
1
1
6 E07 103 010 INTAKE GRILLE
1
1
7 E07 103 303 VANE MOTOR
4
4
8 E07 103 044 VANE BUSH
8
8
9 E07 103 031 GEAR (V)
4
4
10 E07 103 032 GEAR (M)
4
4
www.ilmalämpöpumput.com
24
MV
05.2.24 8:52 AM
Page 25
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
ELECTRICAL PARTS
SLZ-KA25VAL.TH SLZ-KA25VA.TH
SLZ-KA35VAL.TH SLZ-KA35VA.TH
SLZ-KA50VAL.TH SLZ-KA50VA.TH
6
5
1
No.
Parts No.
2
4
UNIT
7
TO OUTDOOR
OC320-1.qxp
3
Q'ty/set
Remarks
SLZ-KA
Specification
25 35 50 25 35 50 (Drawing No.)
VAL.TH VA.TH
1 1 1 1 1 1
250V 6.3A
Parts name
1 E07 006 382 FUSE
2 E02 661 385 VARISTOR
1 1
1
3 E07 164 447 INDOOR CONTROLLER BOARD
1 1
1
5 E07 156 375 TERMINAL BLOCK
6 E07 154 440 INDOOR POWER BOARD
7 E02 095 350 INDOOR FAN CAPACITOR
ZNR
I.B
1
1
E07 166 447 INDOOR CONTROLLER BOARD
FUSE
I.B
1
1
4 E07 162 375 TERMINAL BLOCK
1
1
1
E07 162 447 INDOOR CONTROLLER BOARD
1 1
Wiring RecomPrice
Diagram mended
Symbol Q'ty Unit Amount
I.B
1 1
1 3P
TB4
1 1
1 2P
TB15
1 1
1
1 1
1
P.B
1.5+/ 440VAC 1 1
1
1 1
1
C1
www.ilmalämpöpumput.com
25
OC320-1.qxp
05.2.24 8:52 AM
Page 26
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
FUNCTIONAL PARTS
SLZ-KA25VAL.TH
SLZ-KA35VAL.TH
SLZ-KA50VAL.TH
SLZ-KA25VA.TH
SLZ-KA35VA.TH 1
SLZ-KA50VA.TH
23
22
3
2
22
3
21
4
20
5
19
18
17
6
16
15
7
8
ON/OFF
TOO
WARM
TOO
COOL
FAN
SELECT
VANE
TIME
AUTO COOL
HEAT DRY
24
MODE
9
RESET
10
25
11
TEMP.
12
ON/OFF
26
13
14
27
www.ilmalämpöpumput.com
26
OC320-1.qxp
05.2.24 8:52 AM
Page 27
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
No.
Parts No.
Q'ty/set
Price
Wiring RecomSLZRemarks
Specification
Diagram
mended
25 35 50 25 35 50 (Drawing No.)
Symbol Q'ty Unit Amount
VAL.TH VA.TH
1 1 1 1 1 1
Parts name
1 E07 104 290 BASE
2 E07 104 124 DRUM-1
1 1
1
1 1
1
3 E07 104 808 LEG-1
2 2
2
2 2
2
1
1 1
1
4 E07 105 124 DRUM-2
1 1
E07 140 620 INDOOR HEAT EXCHANGER
1
1
5 E07 141 620 INDOOR HEAT EXCHANGER
1
1
E07 142 620 INDOOR HEAT EXCHANGER
6 E07 104 105 MOTOR MOUNT
3 3
E07 162 300 INDOOR FAN MOTOR
1
1
3
PK6V20-LL
E07 166 300 INDOOR FAN MOTOR
PK6V20-LM
3 3PCS/SET
1
PK6V15-LD 1
7 E07 164 300 INDOOR FAN MOTOR
3 3
MF
1
1
MF
1
1
MF
8 E07 104 816 FLAT PLATE
1 1
1
1 1
1
9 E07 104 502 TURBO FAN
1 1
1
1 1
1
10 E07 104 097 SPL WASHER
1 1
1
1 1
1
11 E07 104 700 DRAIN PAN
1 1
1
1 1
1
12 E07 154 308 ROOM TEMPERATURE THERMISTOR
1 1
1
1 1
1
13 E07 104 520 FAN GUARD
1 1
1
1 1
1
14 E07 104 524 DRAIN PLUG
1 1
1
1 1
1
15 E07 104 648 COIL SUPPORT
1 1
1
1 1
1
/ EVAPORATOR
16 E07 154 309 CONDENSER
TEMPERATURE THERMISTOR
1 1
1
1 1
1
TH5
17 E07 154 307 PIPE TEMPERATURE THERMISTOR / LIQUID
1 1
1
1 1
1
TH2
18 E07 104 702 DRAIN HOSE
1 1
1
1 1
1
19 E07 104 266 DRAIN SENSOR
1 1
1
1 1
1
1
20 E07 104 241 SENSOR HOLDER
1 1
1
1 1
21 E07 104 355 DRAIN PUMP
1 1
1
1 1
1
22 E07 104 809 LEG-2
2 2
2
2 2
2
23 E07 154 006 COVER (DRUM)
1 1
1
1 1
1
24 E07 140 426 WIRELESS REMOTE CONTROLLER
1 1
1
25 E02 527 083 REMOTE CONTROLLER HOLDER
1 1
1
1 1
1
27 E07 018 089 REMOTE CONTROLLER CABLE
1 1
1
27
DS
DP
W.R
26 E07 159 426 REMOTE CONTROLLER
www.ilmalämpöpumput.com
TH1
OC320-1.qxp
05.2.24 8:52 AM
Page 28
Mitsubishi ilmalämpöpumput korjaa ja huoltaa: Jäähdytinpalvelu RefGroup Oy (pääkaupunkiseutu)
HEAD OFFICE : MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Feb. 2005 No.OC320 PDF 8
Made in Japan.
New publication, effective Feb. 2005.
Specifications subject to change without notice.
www.ilmalämpöpumput.com