Download Siemens SITRANS P Operating instructions
Transcript
Installing/mounting 4.3 Installation (except level) ● Easily accessible ● As close as possible to the measuring point ● Vibration-free ● Within the permitted ambient temperature values Installation configuration The transmitter may in principle be configured above or below the pressure tapping point. The recommended configuration depends on the aggregate state of the medium. Installation configuration for gases Install the transmitter above the pressure tapping point. Lay the pressure tubing with a constant gradient to the pressure tapping point, so that any condensation produced can drain in the main line and thereby avoid corruption of the measured values. Installation configuration for vapor and liquid Install the transmitter below the pressure tapping point. Lay the pressure tubing with a constant gradient to the pressure tapping point so that any gas pockets can escape in the main line. 4.3.2 Installation (except level) Note Damage to measuring cell When installing the process connection of the pressure transmitter, do not rotate the housing. Rotating the housing may damage the measuring cell. To avoid damage to the device, tighten the threaded nuts of the measuring cell using a wrench. Procedure Attach the transmitter to the process connection with an appropriate tool. See also Introduction to commissioning (Page 150) 40 SITRANS P, DS III series with HART Operating Instructions, 09/2012, A5E00047092-08