Parameter setting examples
PROFIdrive communication profile with PPO Type 1
Drive parameter
Example setting for ACS350
1001 EXT1 COMMANDS
COMM
1103 REF1 SELECT
COMM
1601 RUN ENABLE
COMM
1604 FAULT RESET SEL
COMM
9802 COMM PROT SEL
EXT FBA
5101 FBA TYPE
5102 NODE ADDRESS
PROFIBUS DP*
3
5103 BAUDRATE
12000*
5104 PPO TYPE
1 (= PPO1)*
5105 PROFILE
0 (= PROFIdrive)
•••
5127 FBA PAR REFRESH
REFRESH
*Read-only or automatically detected
With the FPBA-01, data-consistent communication can be used,
meaning that the whole cyclic data frame is transmitted during a
single program cycle. Some PLCs handle this internally, but others
must be programmed to transmit data-consistent telegrams (for
more information, see the chapter Communication). For example,
Siemens Simatic S7 requires the use of special functions SFC15
and SFC14.